304 Brook Avenue

Bronx, NY 10454BBL 2-02267-0015Map

Owner of record: NYC Department Of Education

304 Brook Avenue is a school building built in 1961 in Bronx, 10454. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
14
ECB violations
41
HPD complaints
2

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 14

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
Show 4 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 9, 1994

    Dob violation - dismissed

ECB violations · 41

  • Class - 2

    Failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close when tested at 2nd flr-library.1st flr-staircase e and h.rem:repair and/or replace.

    Jun 11, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing.noted:on the 1st floor,exterior exit at staircase a did not self-close because door closer was broken.rem:repair/replace door.

    Jun 11, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:on the 1st floor all emergency lights are inoperative when tested.rem:

    Jun 11, 2026 · Penalty $1,250

    Active
  • Class - 2

    28-301.1 unlawful placement of furnishings,decorative or other objectsat exits that obstruct access to,egress from or visibility thereof perfdny 2008 code;fc 1027.4.noted:in the gym at rear exit,there was 4 fol

    Jun 11, 2026 · Penalty $1,250

    Active
  • Class - 2

    I found a national boiler with a oil leak under burner/drop light on smoke alarm/boiler door has a stopper/combustible material in boiler room/ correct all violating condition/submit certificate of correction.

    Aug 11, 2025 · Penalty $1,250

    Active
  • Class - 2

    Noted: observed no lights under sidewalk shed, along east 141st street, causing a hazard to pedestrians (trips, slips, falls). site is under active ahv permit # x4273779., comply to code specifications

    Jan 30, 2025 · Penalty $5,000

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:next to room 116,two lights,exit h four lights,auditorium four lights

    Sep 18, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit doors not self-closing.noted:exit 5 one door,exit 6 two doors,andexit 3 one door all these doors were not opening and closing properly.rem:repair/replace door.

    Sep 18, 2024 · Penalty $625

    Active
  • Class - 3

    Re-issue #35560743y failure to maintain buildin wall(s)or appurtenances.at time of inspection observed at exp #3 window gate has become loose detaching from building violation #35560743y issued 4/15/21 need to

    Mar 24, 2022 · Penalty $500

    Resolve
  • Class - 2

    Work without a permit.noted:observed at exposure#1 and exposure#4 approx 480 l.f. of sidewalk shed erected along the exterior perimeter of school 141 street and brook avenue side also at exposure#3(rear)approx

    Apr 15, 2021 · Penalty $1,250

    Resolve
Show 31 more ↓
  • Class - 2

    Exit door not self-closing noted:observed exterior exit door at exit#6brook avenue side,do not self-closing due to horizontal brace of the sidewalk shed,door is getting wedged under the brace.rem:repair/replace

    Apr 15, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:noted:observed at 3rd floor-fire proof self closing door leading onto small roof do not self closing properly and does not open easily extreme force must be

    Apr 15, 2021 · Penalty $625

    Resolve
  • Class - 3

    35473384x re-issued failure to maintain building walls or appurtenances noted:observed at exposure#3 window gates have become loose and detaching from building.rem:maintain exterior building wall.

    Apr 15, 2021 · Penalty $500

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits ,eixt discharges an dpublci corridors per bc 1006.1;27-381 noet at main entrance 2 emergency lights not working did not light when ts

    Apr 16, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances noe at exposure #3 rear yard 3rd floor window grates pulling away from walls repair and or replace

    Apr 16, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1 unlawful placement of furnishings, decorations or other objects at exits that obstruct access to egress from 0r visibility thereofper fdny 2008 code; fc 1027.4. noted: apprx (6) cardboard boxes and

    Apr 6, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: defective emergency lighting throughout the 1st fl

    Apr 6, 2018

    Resolve
  • Class - 1

    05m07, cease use-59n10. 05m07-missing door restrictor, provide; 59n10 replace allparts make operable.

    Sep 21, 2016 · Penalty $1,000

    Active
  • Class - 2

    Failure to maintain bldg in code-compliant manner - oil tank room. foundation wall dripping of oil down supply side wall oil leak at tank #2oil lone. remedy: maintain bldg as per code.

    Feb 4, 2014

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. oil tank room. brick walls and mortar eroded ie. foundation wall and brick wall - eroded exposing metal. remedy: maintain bldg as per code.

    Feb 4, 2014

    Resolve
  • Class - 2

    Roof bulkhead doors - not self-closing doors warped. remedy: replace doors, hardware - remove slide bolts.

    Feb 4, 2014

    Resolve
  • Class - 2

    Doors not closing. at 2nd sty stair "d" (2 doors) at 4th sty stair e &h (4 doors). remedy: repair/replace noted.

    Apr 16, 2013

    Resolve
  • Class - 2

    Exit (stairway 'b')door is not self closing on the 1st flr level.noted:closer is defective.rem:repair door closer.

    May 13, 2011

    Resolve
  • Class - 2

    The plaster on the wall is spalling located in room 404 on the 4 flr level.rem:repair &/or replace plaster.

    May 13, 2011

    Resolve
  • Class - 2

    The corridor hallway is partially obstructed by wooden shelves approx 4' in height throughout the 3 flr level.rem:remove obstruction.

    May 13, 2011

    Resolve
  • Class - 2

    4th flr stwy b door check defective door not closing .3rd flr stwy b drs not closing 1st flr vestibule dr at stwy c not closing remedy repair replace doors.

    Jan 15, 2010

    Resolve
  • Class - 2

    Crack in glazed block wall tire at 3rd flr near stwy e also note at bsmt level in gas meter rm hole in wall approx 2'x3' remedy repair walls.

    Jan 15, 2010

    Resolve
  • Class - 2

    Gas meter rm at bsmt level is being used to store boxs,plywood,etc remedy remove storage items from gas meter room.

    Jan 15, 2010

    Resolve
  • Hazardous

    B51 27-201 sidewalk shed not adequately maintained sidewalk shed erected under permit # 200965303 has section of wood decking not plumb,loose,sticking out onto roadway. remedy: maintain sidewalk shed.

    Feb 28, 2008

    Resolve
  • Hazardous

    Missing 2 panic hardware located at the exit from the cafeteria at basement level. noted: (place of assembly is for 450 person). pa-200474780. remedy: install panic hardware.

    May 15, 2007

    Resolve
  • Non-hazardous

    Failure to maintain building. noted: first fl. auditorium, right side door is missing a door check. (not self closing) remedy: maintain building. install check.

    Jan 5, 2005

    Resolve
  • Non-hazardous

    Smoke stop doors. noted:second through fourth floor corridor doors are solid with no glass openings. minimum 600 sq.inches per door with clear wire glass & maximum 1,269 sq. inches per door. remedy: install gal

    Jan 5, 2005

    Resolve
  • Non-hazardous

    Failure to provide panic hardware where required by law. location: gymnasium 7 cafeteria defect areas all exit doors. occupancy of 320 people easch area remedy; provide panic hardware.

    Feb 11, 2003

    Resolve
  • Non-hazardous

    49-pipes leaking -replace 2 elbow on feed line and union on equalizing line

    Jul 10, 2001

    Resolve
  • Non-hazardous

    Failure to provide adequate emergency powr exit lights on floors 2nd,3rd,4th and stasirs.failure to provide emergency power toexit lights on floors 2nd ,3rd,4th and stairs.failure to provide emergency power to

    Mar 21, 2001

    Resolve
  • Non-hazardous

    Work without a permit expired permit.expired permit #200462622,expired 7/10/00 for sidewalk shed.remedy:renew permit.

    Jan 3, 2001

    Resolve
  • Non-hazardous

    Failure to provide emergency light-fixture in corridor & stair en- closure on floor 2 to 4. failure to provide emergency power to light- fixture in corridor & stair enclosure on floor 1 to 4. remedy: provide

    Aug 5, 1999

    Resolve
  • Non-hazardous

    Failure to provide 3"high numerical sign indicating the floor number within stair enclosure on floor 1 to 4. failure to provide 3"high al- phabetic letter of identification over the occupancy side of stair

    Aug 5, 1999

    Resolve
  • Hazardous

    Failure to maintain exterior building wall. defects are: 1) masonry mortar pulling away & defective. location: 141 st. side. 2) vertical cracks "corner). location: 141 st. & brook ave. remedy: provide side-

    Apr 15, 1999

    Resolve
  • Non-hazardous

    Failure to maintain . "roof" water leaking into classrooms 425 & 427 also hallway. remedy: make all necessary repair to roof and to class- rooms.

    Apr 15, 1999

    Resolve
  • Hazardous

    Failure to maintain exterior wall. bricks above the main entrance are loose and mortar is missing on the joints. remedy: provide sidewalk shed and make all necessary repairs immediately.

    Jan 30, 1998 · Penalty $2,500

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Dec 7, 2020 · Apt BLDG

    Close
  • Heating

    Heat related

    Jan 23, 2014 · Apt 3F

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1961
Floors
4
Residential units
—
Building area
96,750 ft²
Lot area
53,579 ft²
Zoning
R6
Community board
201
Council district
8
Block / lot
2267 / 15
Assessed value
$6,680,700
Landmark / historic district
No

Questions about 304 Brook Avenue

Who owns 304 Brook Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 304 Brook Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 304 Brook Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 304 Brook Avenue built?

City records list 1961 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.