1461 St Nicholas Avenue
Manhattan, NY 10033BBL 1-02165-0069Map
Owner of record: Nestle Realty Holding Cp
1461 St Nicholas Avenue is an office building built in 1928 in Manhattan, 10033. The owner of record is Nestle Realty Holding Cp. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 57
- ECB violations
- 105
- HPD complaints
- 5
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 57
- Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 3, 2020
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 3, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 3, 2019
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 3, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed
Show 40 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 20, 2016
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 1, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 11, 2012
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 21, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 24, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 20, 2006
Vw*-violation - work w/o permit dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 20, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 7, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 7, 2005
Vw*-violation - work w/o permit dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 23, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 23, 2002
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Elevator elevatorrequired
1s1114
Jan 8, 2002
Dob violation - resolved - Elevator elevatorrequired
1p10824
May 11, 2001
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatorrequired
1s1114
Apr 24, 2000
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 10, 2000
Dob violation - dismissed - Elevator elevatorrequired
1s1114
Aug 25, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 17, 1997
Vp*-violation unserved ecb- dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 10, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 27, 1995
Vp-violation unserved ecb-active - Construction other optional
C-construction other optional
Apr 27, 1995
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 13, 1995
Vp*-violation unserved ecb- dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 13, 1995
Vp*-violation unserved ecb- dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed
ECB violations · 105
- Class - 2
Occupancy contrary to that allowed by the certificate of occupancy or building department records.noted at first floor space used as a gym contrary to certificate of occupancy#59485 issued on 04/20/1964 allowin
May 12, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. several emergency lights in the building not working. remedy: repair and/or replace.
Feb 17, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: bulkheadwalls at stair b spalling plaster. remedy: repair and/or replace.
Feb 17, 2026 · Penalty $1,250
Resolve - Class - 2
Reissue ecb #35691803r. exit door not self-closing. noted: exit door #2 not self-closing. remedy: repair and/or replace.
Feb 17, 2026 · Penalty $625
Resolve - Class - 2
Reissue#35672547n exit door not self closing properly.exit#2 from cellar is in disrepair.rem:comply with code.
Feb 21, 2025 · Penalty $1,562
Resolve - Class - 2
Reissue#35657845x exit door not self-closing.first door main entrance right side solo door rusted at hinges and not self closing.rem:comply with code.
Feb 21, 2025 · Penalty $1,562
Resolve - Class - 2
Re-issue #35672548p-emergency signs at elevator call stations missing,defective or non-compliant with section requirements. noted: observed at flr. and cellar level, elevator bank/landing is missing the emergen
Mar 5, 2024 · Penalty $1,562
Resolve - Class - 2
Re-issue #35672547n-exit door not self-closing. noted: observed 1 flr., exit #2 to allow exit from cellar level has door and door frame in state of disrepair due to corrosion and rusted lower section which is r
Mar 5, 2024 · Penalty $1,562
Resolve - Class - 2
Emergency signs at elevator call stations missing, defective or non-compliant with section requirement. noted at 3rd level & cellar level missing emergecy signs at elevator call stations. remedy: install and/or
Jun 15, 2023 · Penalty $625
Resolve - Class - 2
Reissue #3567845x exit door not self-closing properly. noted exit #2 door from cellar level in disrepair with frame heavily rusted on the bottom. door rubs on frame and does not fully self close. remedy: repair
Jun 15, 2023 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code complaint manner.illumination for exits exit discharges & public corridors per bc 1006.1;27-381 at time of inspection observed at 1st floor gym two emergency exit lights not
Jun 10, 2022 · Penalty $625
Resolve - Class - 2
Exit doors not self closing properly at time of inspection at first floor main entreance right side one exit door not self closing properly at first floor gym one emer exit door(going to outside)not self closin
Jun 10, 2022 · Penalty $625
Resolve - Class - 2
28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.2 note @2nd floor in corridoor in front of room 203 art wprk greater than 20% consisted of paper to look like tree
May 18, 2020 · Penalty $1,250
Resolve - Class - 2
Respondent failed to allow mandatory inspection by the department as per 28-304.6.1 and appendix k of the building code. remedy; arrange for inspection to be made by this department by emailing [email protected]
Mar 16, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to comply w/ commissioner's order contained in summons/violation#38260855n issued on 1/22/18, and to file a certificate of correction pursuant to 28.201.1 and 1rcny 102-01(d)(2). an acceptable certifica
Nov 20, 2018 · Penalty $3,125
Resolve - Class - 2
Reissue #35296815y issued on 08/24/17 exit doors not self closing @main entrance vestible smoke door not operational.rem:repair/replace door.
Mar 28, 2018 · Penalty $3,125
Resolve - Class - 2
Reissue #35296816x issued on 8/24/17 failure to maintain bldg in code compliant manner no file stopping per bc 712.3 27-345 no file stopping @cellar electrical rm.rem:provide/maintain fire stopping.
Mar 28, 2018 · Penalty $5,000
Resolve - Class - 2
13x10,10h11,44h8,41t7,40q3,42l10,70z2,59u15. (41t)label mr door. (40q)provide guards @ mr landing, fall hazard. (42l)repair defective insp switch on controller.
Jan 22, 2018 · Penalty $500
Active - Class - 2
Reissue#35207817k exit door not self closing 1st fl main entrance vestibule door not closing. remedy: repair/replace door.
Aug 24, 2017
Resolve - Class - 2
Re-issue#35207818m.failure to maintain bldg incode-compliant manner illumination for exits,exit discharges and public corridors per bc 1006-1;27.381.defective exit sign at exit#2.rem:repair/replace lighting
Aug 24, 2017
Resolve - Class - 2
Reissue#35207818m failure to maintain bldg in code compliant manner illumination for exit,exit discharges & public corridors per bc 1006-1.27-381. defective exit sign at exit(2). remedy: repair/replace lighting
Aug 24, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner no fire stopping per bc 712.3;27-345. missing fire stopping at cellar electrical room. remedy: provide/maintain fire stopping.
Aug 24, 2017
Resolve - Class - 2
Re issue#35207817k exit dorrd not self closing.first fl main entrance vestibule door not closing.rem:repair/replace
Aug 24, 2017
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.no fire stopping per bc 712.3,27-345 missing fire stopping at cellar electric rm.rem:provied/maintain fire stopping
Aug 24, 2017
Resolve - Class - 2
57bb11,99bb5,98bb5,21j10,70p16,39p16,16j16. 57bb11-fire extinguisher is expired. 99bb5-one year tags not up to date; 98bb5-perform 5year test and file; 21j10-5stop interlock is misaligned causing elevator to
Feb 22, 2017
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances. noted: several cracks throughout exteiror walls at elevator rom, roof, and rain leader missing was observed. rmdy: maintain exterior building wall.
Sep 14, 2016
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: loose plaster as a result of water penetrating at ceiling and walls at bulkhead area, north wall at 2nd and 34d story intermediate landing staircase
Sep 14, 2016
Resolve - Class - 2
Exit door not self-closing. noted: not self-closing door at exit 1 from vestibule and not self-closing door at lobby, leading to security area at 1st floor. rmdy: repair/replace door.
Sep 14, 2016
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexit, exit discharges and public corridors per bc 1006.1; 27-381. defective exit sign at exit 2. rmdy: repair/replace lighting.
Sep 14, 2016
Resolve - Class - 2
Exit door not self-closing. at exit 2 discharge door not self closing with base of steel door jamb rusted through and preventing proper sealcompromising fire-rating of door. rmdy: repair and/or replace door/doo
Jul 14, 2015
Resolve - Class - 2
Failure to maintain building in code compliant manner. at 2nd story south wall of room 201 cracked roof drain pipe allowing water to penetrate into classroom. rmdy: repair defect noted.
Jul 14, 2015
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. at west elevation facade 1st sty water penetration damaging interior plaster wall. remedy: repair defect noted.
Jul 14, 2015 · Penalty $500
Resolve - Class - 2
The plaster on the wall is spalling located in room 207 on the 2nd flrlevel. remedy: repair and/or replace plaster.
Jan 22, 2013
Resolve - Class - 2
Reissue: 34958261p stairway exit "b" 3rd floor level is missing the sign i.d.# on the corridor side. remedy: provide sign i.d.
Jan 22, 2013
Resolve - Class - 2
Reissue 34908369l. 2nd flr plaster spalling from ceiling in corridor across from elevator. at cellar level room b1 plaster spalling from ceiling. rem:repair plaster ceilings.
May 22, 2012
Resolve - Class - 2
28-301.1: 3rd flr stairway "b" stairway id sign is missing on corridorside. rem:provide stairway id sign.
May 22, 2012
Resolve - Class - 2
Reissue 34908368j. 2nd flr stairway "a" door not closing. 1st flr exitdoor to st nicholas ave from 106 door not closing. cellar level stairway "c" & cafeteria doors are all racked. rem:repair/replace doors
May 22, 2012
Resolve - Class - 2
Missing handrail.@ lobby to cellar on right missing handrail going down.rem:replace handrail
May 6, 2011
Resolve - Class - 2
Prohibited hardware per bc 1008.1.8, 27-371(j)@ all flrs all stairways,installed kick stops prevent proper operation of fire proof self closing doors.rem:repmove prohibitied hardware
May 6, 2011
Resolve - Class - 2
Partial corridor obstruction @ 2nd flr,partial fire corridor obstruction w/large table and six chairs.rem:remove items,maintain corridor width clear.
May 6, 2011
Resolve - Class - 3
Defective plaster surface.@ 3rd flr room 302, & cellar level room b1 spalling plaster with areas crumbling.rem:repair plaster surface
May 6, 2011
Resolve - Class - 2
Defective doors @ 3rd flr stairway b,cellar level stairway c,the fire proof self closing doors are racked to frame & not operating properly.rem:repair doors to properly open & self close
May 6, 2011
Resolve - Class - 3
Work w.o a permit. noted: reissue nov 34777360r, 34646446z 1st floor entrance w 183 st. erected partition separating vestibule into two different egress corridors from cellar an from 1st floor. remedy: obtain
Jul 28, 2010
Resolve - Class - 2
Fail to maintain bldg in code compliant manner. noted: 2nd floor corridor. missing sections at drywall exposing studs compromising fire proofing. remedy: maintain bldg repair/replace
Jul 28, 2010
Resolve - Class - 2
97r9 16k10 97-illegal remover is1114 file for permit for proper removed 16-repair sidewalk door
Mar 24, 2010 · Penalty $2,500
Resolve - Class - 3
Reissue 34646446z at 183 st entrance vestibule erected full height partition seperating vestibule into two different egress corridores on leading from cellar to street one leading from first fl to street restri
May 12, 2009
Resolve - Class - 3
Reissue 34646447k plaster on chase column spalling missing at cellar level between rms b7 and b8 also waste line located in chase leaking water remedy:repair pipe and wall
May 12, 2009
Resolve - Hazardous
Plaster on the walls is spalling located in the corridor hallway adjacent to room b7 & b8 on basement level. remedy: repair plaster on walls
Jun 5, 2008
Resolve - Hazardous
Reissue: 34124427p erected full height partition wall between exit 1 &2 adjacent to 183 st 1st flr level & increase width of doorway at stairway #2 leading to cellar level w/o proper permits. remedy: obtain per
Jun 5, 2008
Resolve - Hazardous
Failure to maintain building - interior. electric room is being used as storage room. remedy: remove storage.
May 30, 2006
Resolve
Complaints
- Heat/hot water
Entire building
Dec 23, 2022 · Apt 62
Close - Heat/hot water
Entire building
Feb 10, 2020 · Apt BLDG
Close - Plumbing
Water supply
Aug 6, 2016 · Apt BLDG
Close - Electric
Power outage
Aug 6, 2016 · Apt BLDG
Close - Heating
Heat related
Mar 25, 2010 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Office building (O5)
- Year built
- 1928
- Floors
- 3
- Residential units
- —
- Building area
- 33,779 ft²
- Lot area
- 7,492 ft²
- Zoning
- R7-2
- Community board
- 112
- Council district
- 10
- Block / lot
- 2165 / 69
- Assessed value
- $4,691,700
- Landmark / historic district
- No
Questions about 1461 St Nicholas Avenue
Who owns 1461 St Nicholas Avenue?
The owner of record in NYC Department of City Planning PLUTO data is Nestle Realty Holding Cp.
Does 1461 St Nicholas Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 1461 St Nicholas Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1461 St Nicholas Avenue built?
City records list 1928 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.