roofy

341 Audubon Avenue

Manhattan, NY 10033BBL 1-02155-0035Map

Owner of record: NYC Department Of Education

341 Audubon Avenue is a school building built in 1965 in Manhattan, 10033. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
105
ECB violations
89
HPD complaints
18

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 105

  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    Cease use

    Dec 18, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Plumbing none

    Access to premises to inspect active application #103647662 was denied

    Jul 6, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 17, 2015

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
Show 40 more ↓
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Sep 28, 2012

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Sep 28, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 13, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 31, 2005

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed

ECB violations · 89

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: upon inspection, fire rated and smoke doors not self-closing due to hardware or binding or classrooms 400, 401, 415(2) doors, 412, 422, 426(2) doors

    Feb 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted: upon inspection box g and several other boxes of e

    Feb 19, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: observed at various locations throughout the occupied 4-story sc

    Feb 7, 2024 · Penalty $625

    Resolve
  • Class - 2

    Stair and/or floor identification signs missing and/or defective. noted: observed at various staircase landings/corridors throughout the occupied 4-story school building. the location id signs are not adequatel

    Feb 7, 2024 · Penalty $625

    Resolve
  • Class - 2

    Emergency signs at elevator call stations missing, defective or non-compliant with section requirements. noted: observed at 4 flr., elevatorbank is missing the emergency call station. which is creating a hazard

    Feb 5, 2024 · Penalty $625

    Resolve
  • Class - 1

    Reissue #35658029m failure to maintain building in code compliant manner. at time of my inspection i observed at exposure #3 facade with multiple area crack and/or missing masonry sidewalk shed installed condit

    Jun 15, 2023 · Penalty $3,125

    Active
  • Class - 1

    Reissue #36586768x failure to maintain building in code compliant manner.at time of inspection observed at exp #3 facade with multiple areas of cracking &/or missing masonry side walk shed was installed violati

    Jun 9, 2022 · Penalty $3,125

    Active
  • Class - 1

    Failure to maintain building in code compliant manner.noted:at time of inspection observed at exp #3 facade with multiple areas of cracked and/or missing masonry with no overhead protection for pedestrians on 1

    Jul 26, 2021 · Penalty $3,125

    Active
  • Class - 1

    Failure to maintain building in code compliant manner.at time of inspection noted facade at exp #3 multiple areas of cracked and/or missing masory with no overhead protection for pedestrians on 183 st side of

    Jun 18, 2021 · Penalty $1,250

    Active
  • Class - 2

    05l10: (05-l-10) car door gate not locking when lift moves. remedy: repair door gate switch

    Feb 11, 2020 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue #35326292z date of issue 4/6/18 failure to maintain building in code compliant manner. illumination for exits exit discharges and public corridors per bc 1006.1.27-381 at 1st floor gym one place

    May 15, 2019

    Resolve
  • Class - 2

    Exit door not self closing at 4th floor at stair way "b" left side one exit door is not self closing properly at 4th floor near room no 412 one corridor exit door not self closing properly.at 2nd floor near

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. illumination for exits, exit discharges and public corridors per bc 1006. 1.27.381. at gymnasium and auditorium emergency lights not operational when test

    Apr 6, 2018

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances noted at exterior of building concrete awning at exit 3 cracked also vertical cracks near exit 5. rmdy: maintain building walls and appurtenances.

    Apr 6, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: no fire stopping per bc712.3; 27-345 observed @ boiler & electrical room. rem: provide/maintain fire stopping.

    Oct 14, 2016

    Resolve
  • Class - 2

    97x10. return to service immediately.

    May 31, 2016

    Resolve
  • Class - 2

    Gym exit sign missing near room 150.auditorium stage left exit sign lights.rem:repair/replace exit signs.

    Feb 27, 2014

    Resolve
  • Class - 2

    Auditorium stage right exit door partial obstruction,musical instruments partly blocking exit.rem:remove obstructive forth with.

    Feb 27, 2014

    Resolve
  • Class - 2

    3rd fl stwy "a" racked.1st fl stwy "c" door racked.cafeteria doors racked.cellar stwy "b" doors racked.auditorium stage left door not closing.rem:repair/replace doors.

    Feb 27, 2014

    Resolve
  • Class - 2

    Gas meter room being used for storage tables,tvs,piano ect.rem:remove storage items.

    Feb 27, 2014

    Resolve
  • Class - 2

    Reissue: 34910517r at 3 bulkhead doors to roof are racked. 3rd fl stwy"a & b"doors racked. 1st fl stwy a & c doors racked. cafeteria north door racked & south door not closing. basement level auditorium stage

    May 15, 2012

    Resolve
  • Class - 2

    Sec. 27-369 reissue: 34910520h excassive combustible material at 3rd &4th fl corridors. also note combustible material hanging from light fixtures in rooms 406,401,305 & 312. remedy: remove combustible material

    May 15, 2012

    Resolve
  • Class - 2

    Defective exit lighting per bc1006,bc2702,27-381. at gym exit adjacentto room 150,the exit lighting is broken off leaving the mounting plate & wires. remedy: replace exit lighting.

    Apr 20, 2011

    Resolve
  • Class - 2

    Broken door hardware. at 4th fl restroom #425,interior door handle is broken,when door closes the occupants can not exit. door tied open at the time of inspection,school not in session. remedy: repair hardware

    Apr 20, 2011

    Resolve
  • Class - 2

    Excessive combustible material. at 3rd & 4th fl fire corridors,combustible art work from floor to ceiling & protruding from walls & suspended wall to wall. remedy: remove combustible material from fire corridor

    Apr 20, 2011

    Resolve
  • Class - 2

    Defective ceiling tile. at basement level room b28,the ceiling tile is loose,missing,& hanging throughout classroom. remedy: properly replace ceiling tile.

    Apr 20, 2011

    Resolve
  • Class - 2

    Defective exit door. at 1st fl stairway a,the exit door (1 of 3) is racked & jammed into frame requiring excessive force to open. remedy: repair door to properly open & self close.

    Apr 20, 2011

    Resolve
  • Class - 2

    Reissue #34862122z defective doors. at stairway b & c,the bulkhead doors are racked & jammed into frames with broken hinges & will not operate. remedy: replace doors &/or frames.

    Apr 20, 2011

    Resolve
  • Class - 2

    Reissue #34862125y defective roof ladder. at 2nd fl fan room access togym roof,the steel ladder has bolts detached & missing leading ladder loose & unsafe. remedy: properly secure access ladder.

    Apr 20, 2011

    Resolve
  • Class - 2

    Reissue #34862126x excessive storage. at 2nd fl fan room,excessive storage of school supplies,ie: desks,chairs,computer hardware,& printers.remedy: remove all school material.

    Apr 20, 2011

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: 2nd fl fan room, excessive amount of storage consisting of school supplies desks,chairs. remedy: maintain bldg replace/repair

    Jul 28, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg walls & appurtenances. noted: exit from fan room2nd fl ladder to roof of gym defective, loose, bolts detached from wall. remedy: maintain bldg repair/replace

    Jul 28, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: gym basket ballbackboard which bolts not fully set to wall. remedy: maintain bldg repair/replace

    Jul 28, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg in code compliant manner. noted: rm 232 door & door lock defective not operating does not open. remedy: maintain bldg replace/repair

    Jul 28, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg walls or appurtenances. noted: 3 bulkhead doors defective not operating correctly and/or not operating at all (stair way c) remedy: maintain bldg repair/replace

    Jul 28, 2010

    Resolve
  • Class - 2

    Utility rooms defective. gas meter room used for storage. water meter room used for storage. 2nd flr fan room used storage & garbage. remedymaintain adequate housekeeping - remove all storage from utility rooms

    May 21, 2009

    Resolve
  • Class - 2

    Provision of law 27-369 failure to provide stair width auditorium- exit stairs to gym- used for storage. rem: provide stair width as per code.

    May 21, 2009

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by certificate of occupancy c.o. #63613 1- full kitchen in boiler room- microwave gas stove, full size refrigerator-sink rem: discontinue illegal use and/or amend certificate

    May 21, 2009

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. 1)4th flr stwy 6/7 door not self closing. 2)2nd flr stwy 3/4 exit door missing closer. 3)1st flr stwy 3/4 wood exit door - not operable fully - hdur-difficult

    May 21, 2009

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. exit signs 1)boiler rm at ramp - exit light out. 2)exit signs missing behind auditorium corridor. 3)exit sign door "d" - no exit sign (adjacent to b-20) 4) caf

    May 21, 2009

    Resolve
  • Class - 2

    Section bc1017.1. failure to maintain bldg in code compliant manner. secondary/primary means of egress blocked. 1)from boiler room - door bolted & gate locked onto audobon ave. 2) cellar-music rm- egress blocke

    May 21, 2009

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner-interior. 1)stwy #7 -spalling at ceiling. 2)study #5 - 4th flr spalling at inside/outside window. 3)near rm 222@exit 3/4c -upper wall plaster bldg. 4)kitchen

    May 21, 2009

    Resolve
  • Hazardous

    Concrete block wall has shifted from side to side creating an open gap on the 1st flr level in the gymnasium. remedy: repair concrete block wall.

    May 22, 2008

    Resolve
  • Hazardous

    Reissue: 34593119p ceiling tiles are missing located on the 4th flr level adjacent to room 403 & 405. remedy: replace missing ceiling tiles.

    May 22, 2008

    Resolve
  • Non-hazardous

    Reissue 34445569h interior f.p.s.c. stairway doors are defective with door closers noted:doors do not close properly on the 1st fl level.remedy:repair doors

    Sep 7, 2007

    Resolve
  • Non-hazardous

    Reissue 34445677p (partial) interior ceiling tiles are missing (approx20 tiles)located on the 4th fl level near room 405 & 403.remedy replace missing tiles.

    Sep 7, 2007

    Resolve
  • Non-hazardous

    Reissue 34481856z roof level bulkhead has a keyed cylinder.remedy: remove illegal harware at door bulkhead

    Sep 7, 2007

    Resolve
  • Hazardous

    Failure to maintain exterior bldg wall. noted:south elevation cellar level drains,below sidewalk grate clogged w/litter.north elevation side yard at grade level clogged w/sediment deposits around it

    May 9, 2006

    Resolve
  • Hazardous

    Failure to maintain bldg-interior noted:numerous defective f.p.s.c.,stairwell doors w/defective closers,jamming & non-shutting. remedy:repair/replace & maintain bldg fpsc doors

    May 9, 2006

    Resolve
  • Non-hazardous

    Failure to maintain bldg interior.noted:cracked plaster in rooms 431,415.remedy:repair defects.

    May 9, 2006

    Resolve

Complaints

  • Electric

    No lighting

    Dec 11, 2024 · Apt 4A

    Close
  • Heat/hot water

    Entire building

    Dec 11, 2024 · Apt BLDG

    Close
  • Plumbing

    Water supply

    Feb 14, 2023 · Apt 61

    Close
  • Plumbing

    Water supply

    Feb 14, 2023 · Apt 41

    Close
  • Plumbing

    Water supply

    Feb 13, 2023 · Apt 51

    Close
  • Elevator

    Maintenance

    Feb 13, 2023 · Apt 51

    Close
  • Heat/hot water

    Entire building

    Feb 8, 2023 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 30, 2022 · Apt 5A

    Close
  • Heat/hot water

    Apartment only

    Jan 28, 2022 · Apt 7

    Close
  • Heat/hot water

    Apartment only

    Oct 20, 2015 · Apt 4C

    Close
Show 8 more ↓
  • Electric

    Lighting

    Oct 20, 2015 · Apt 4C

    Close
  • Plumbing

    Bathtub/shower

    Oct 20, 2015 · Apt 4C

    Close
  • Heat/hot water

    Apartment only

    Sep 4, 2015 · Apt 4C

    Close
  • Plumbing

    Basin/sink

    Sep 4, 2015 · Apt 4C

    Close
  • Electric

    Lighting

    Sep 4, 2015 · Apt 4C

    Close
  • Appliance

    Refrigerator

    Aug 18, 2005 · Apt 41D

    Close
  • Electric

    Electric-supply

    Jul 19, 2005 · Apt 41D

    Close
  • Heating

    Heat related

    Jan 17, 2004 · Apt BLDG.

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1965
Floors
4
Residential units
—
Building area
170,654 ft²
Lot area
57,825 ft²
Zoning
R7-2
Community board
112
Council district
10
Block / lot
2155 / 35
Assessed value
$10,228,050
Landmark / historic district
No

Questions about 341 Audubon Avenue

Who owns 341 Audubon Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 341 Audubon Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 341 Audubon Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 341 Audubon Avenue built?

City records list 1965 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.