507 West 181 Street is a hotel built in 2009 in Manhattan, 10033. The owner of record is 505 Wash LLC. HPD has recorded 15 housing violations here, most recently on November 17, 2025.

HPD violations
15
DOB violations
34
ECB violations
51
HPD complaints
21

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Nov 17, 2025

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 15

  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 17, 2025

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Jun 13, 2025

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 22, 2024

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 17, 2024

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 15, 2023

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 31, 2023

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 2, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 10, 2022

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Mar 10, 2022

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 20, 2021

    Closed — Violation dismissed
Show 5 more ↓
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Apr 20, 2021

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 6, 2019

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 29, 2018

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Dec 12, 2017

    Closed — Violation dismissed
  • C

    Provide adequate supply of hot water for the fixtures the shower body in the bathroom located at apt 705, 7th story, 1st apartment from east at south

    Sep 5, 2016 · Apt 705

    Closed — Violation closed

DOB building violations · 34

  • Construction other optional

    Structure rendered non-compliant due to gravity water tank leaking with flooding in the cellar level

    Mar 25, 2025

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 16, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Aug 7, 2024

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    May 29, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Apr 3, 2024

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 3, 2024

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 4, 2023

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Feb 2, 2023

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2022

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Nov 2, 2022

    Dob violation - dismissed
Show 24 more ↓
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2022

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jun 1, 2022

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9a technical report by 02/21/2022

    Feb 22, 2022

    Dob violation - active
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Feb 2, 2022

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Nov 2, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jun 2, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 11, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 16, 2020

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2020

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2020

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 18, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 18, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 16, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 16, 2016

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Nov 2, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 23, 2015

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 23, 2011

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 9, 2011

    Dob violation - dismissed
  • Immediate emergency anythingoptional

    Imegncy-immediate emergency anythingoptional

    Nov 26, 2010

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 18, 2008

    Vw*-violation - work w/o permit dismissed

ECB violations · 51

  • Class - 2

    Failure to submit certificate of correction of violation #39142714z issued on 03-25-2025 for failure to maintain building wall(s) or appurtenances., file a certificate of correction

    Sep 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to submit certificate of correction of violation #39142762n issued on 03-25-2025 for failure to provide unobstructed exit passageway., file a certificate of correction

    Sep 18, 2026 · Penalty $1,250

    Active
  • Class - 2

    Class 2 items: in car communication inoperative. cat 5 tag missing in controller. relay in controller needs to be propperly secured. in car operating panel button needs to be repaired.

    Mar 3, 2026 · Penalty $625

    Active
  • Class - 1

    Upon re-insection of the device is not restored to service rucuring condition. remedy: repair device then contactnycdob for re-inspection

    Jul 8, 2025 · Penalty $3,125

    Active
  • Class - 1

    Failure to maintain building - appurtenance - gravity tank at roof-top level currently leaking from the top of the tank and draining into the roof-drain - system tied into their sprinkler / fire alarm system, m

    Mar 25, 2025 · Penalty $25,000

    Active
  • Class - 2

    Observed on the roof water tank leaking, sprinkler system compromised ,lack water pressure in the sprinkler system, tamper switch valve closed to the sprinkler system, water pump that supply water to roof tank

    Mar 25, 2025 · Penalty $1,250

    Active
  • Class - 1

    Failure to provide clear egress passageway - exit designated as egress was blocked by debris deom the premises compromissing egress, remove obstruction

    Mar 25, 2025 · Penalty $6,250

    Active
  • Class - 1

    97-x-17. (97)rts-c entire device inoperative upon inspection the device is found to be out of service on a 8 story build with two elevators and both are out of service creating a hazardous condition as per 1rcn

    Sep 15, 2023 · Penalty $1,250

    Active
  • Class - 1

    97-x-17. rc(97) entire device inoperative. upon inspection the device is found to be out of service on a 8-story building with both elevators out of service for more than 4 months as per tenants this is a hazar

    Sep 15, 2023 · Penalty $625

    Active
  • Class - 1

    Elevator out or service; restore to service

    Aug 8, 2023 · Penalty $1,250

    Active
Show 40 more ↓
  • Class - 1

    Restore to service; elevator out of order

    Aug 8, 2023 · Penalty $1,250

    Active
  • Class - 1

    Device was found out of service restore device back to service. you can contact nycdob at [email protected] for a complete inspection.

    Mar 13, 2023 · Penalty $625

    Active
  • Class - 1

    Elevator currently out of service

    Jan 23, 2023

    Resolve
  • Class - 2

    Failure to submit an acceptable required cycle 8a and 9a report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#918446. remedy:submit acceptable

    Dec 2, 2022 · Penalty $1,250

    Active
  • Class - 1

    Alarm bell inoperative. phone inoperative.

    Aug 10, 2020 · Penalty $625

    Active
  • Class - 1

    Elevator out of service. remedy: return back to service

    Jun 10, 2020 · Penalty $312

    Resolve
  • Class - 2

    Unapproved /unsafe/unsuitable electrical equipment apparatus materialsdevices appliances or wiring in use. observed on rooftop defective gfci outlets along exterior walls.also noted on multiple floors in

    Mar 28, 2019 · Penalty $2,000

    Resolve
  • Class - 2

    Failure to provide /maintain /access/work space about electrical equipment.observed on rooftop mechanical room installation of equip- ment disconnect behind pump and pump control box and service

    Mar 28, 2019 · Penalty $500

    Resolve
  • Class - 3

    Observed in the cellar the ball drip installed on the fire departmetn check valve plugged thereby defeating the purpose of the ball drip. rmdy: repair and/or replace. photo taken.

    Mar 28, 2019 · Penalty $500

    Resolve
  • Class - 1

    Cu1l10,cu2l10; 3d6,12l10,cu28b14,cu79l10,80b14,cu67x10. 1l10-emergen cy stop switche works but no buzzer; 2l10-alarm bell not working no buzzer; 3d6-secure drop ceiling in car; 12l10-alarm bell not working

    Mar 7, 2019

    Resolve
  • Class - 1

    An unlawful act. failure to comply with an order of the commissioner. failure to correct and certify summons #35361579j issue don 09/20/18, for the removal of the cover for the main electrical cabinet, leaving

    Oct 31, 2018 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner .no fire stopping per bc712.3;27-345.at cellar level fire stop missing in gas meter room ceiling and wall,and also in walls going to adult care,adult day ca

    Sep 20, 2018 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. light fixtures in gas meter, oil tank, elevator and water meter rooms are inoperable: not working. note: turned toggle switch to on/off position in all roo

    Sep 20, 2018 · Penalty $310

    Resolve
  • Class - 1

    Unsafe, exposed energized wiring. observed the following violating condition inside main electrical room located in the cellar. cover for main electrical cabinet removed leaving high current carrying conductors

    Sep 20, 2018 · Penalty $400

    Resolve
  • Class - 2

    Work without a permit. observed at rear of building at roof level. the installation of an illuminated accessory sign prior to obtaining a permit sign is approximately 6ft long, 3ft wide and 75 ft high with whit

    Sep 20, 2018

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner.noted:8stry transient hotel "cliff"having defective central fire alarm system previous viol.#35169299p.rem:repair service or replace fire alarm system.

    Aug 12, 2016 · Penalty $2,500

    Resolve
  • Class - 1

    Filed a certificate of correction or other related materials contain ing material false statement noted: respondent filed a certificate of correctionon 03-11-2016 for nov#25169299p/011216cmtfkp02 upon inspecti

    Aug 12, 2016

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order to file a certificate of correction with the dob. noted: respondent failed to comply with the commissioner's order ot correct the violating condition and file a

    Aug 12, 2016

    Resolve
  • Class - 2

    Permanent dwelling used/converted for other than permanent residential purposes.certificate of occupancy #104551414 indicates. j.2 occupancy for floors 5 to 8.apt.#506 on 5th floor now converted and used for le

    Jan 12, 2016 · Penalty $800

    Resolve
  • Class - 1

    Failure to maintain bldg in code complaint manner.transient residential hotel bldg.hotel cliff in operation habing defective out of service fire alarm.(cental fire alarm).rem:repair/service firealarm system

    Jan 12, 2016 · Penalty $1,000

    Resolve
  • Class - 1

    Failure to provide unobstructed exit.passageway.noted:8story "hotel cliff having obstructed fire exit passageway on 1st floor at staircase 'a' and 'b'obstructed by stored household cleaning stuff and parcels.ne

    Jan 12, 2016 · Penalty $1,200

    Resolve
  • Class - 1

    Sec. 3303.8 failure to maintain standpipe as per code - upon inspection,noted the temporary standpipe installed in the bldg is defective & not maintained as per code. the pressure guage for alarm system has

    May 18, 2013 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to safeguard all persons & property affected by construction operation - upon inspection,noted: solid plywood construction fence exists infront of the job site. also noted numerous staple pins sticking

    May 18, 2013 · Penalty $2,400

    Resolve
  • Class - 2

    Work does not conform to approved plan - upon inspection,sidewalk shederected infront of this job site. at time of inspection noted the sidewalk shed is not conforming to the approved plan. many cross bracings

    May 18, 2013

    Resolve
  • Class - 2

    Bc3306.9.4 - water accumulation noted:at time of inspection at active job site observed water acumulation at 2 elevator pits (shaft locations), creating unsafe, unsanitary conditions for site workers.rmdy:immed

    Dec 17, 2012

    Resolve
  • Class - 2

    The permit holder or person directly in charge of any suspended scaffold supported by outrigger beams shall notify the department in a form and manner specified by the department at least 24 hours but not more

    Nov 19, 2012 · Penalty $800

    Resolve
  • Class - 1

    Sec. 3314.6.2 life line anchorage. noted: at 8 (store) concrete building w/open exposures. 2 men found working on the leading edge w/o life line. 1 worker at 7th fl installing(cold colled) steel studding on

    Jul 12, 2012 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to provide standpipe in a state of readiness during construction operations greater than 75 ft per bc 3303.8. noted 8 story concretebuilding under construction has standpipe erected to 8th fl w/no

    Jul 12, 2012 · Penalty $1,000

    Resolve
  • Class - 1

    Failure to institute/maintain safety equipment measures are temporary construction-no toe boards. noted: at 8 story concrete building under construction at numerous places at upper floors 3 to 8 toe boards

    Jul 12, 2012 · Penalty $1,000

    Resolve
  • Class - 1

    Failure to safeguard all persons & property affected by construction operations. noted 8 story concrete building under construction workingon leading edges at 7th fl exp 4 installing cold rolled steel studding

    Jul 12, 2012 · Penalty $2,400

    Resolve
  • Class - 2

    Temporary construction equipment on site - expired fence permit. noted: at time of inspection at front of job site observed expired fence permit #104551414 - on 9.22.11. remedy: renew fence permit as required

    Dec 14, 2011

    Resolve
  • Class - 1

    Failure to safeguard all persons and property affected by constructionoperations defects noted at time of insp there is no construction sitefence in place at exp#2 3 & 4 allowing unauthorized access to site by

    Nov 24, 2010 · Penalty $2,400

    Resolve
  • Class - 2

    Work w/o a permit expired permit defect noted at time of insp site fence erected at site under job application #104551414 has expired as of 2/11/10 fence installed at exp#1 only rem: renew permit

    Nov 24, 2010 · Penalty $800

    Resolve
  • Class - 1

    Failure to safeguard all persons and properrty. upon inspection children are entering the site from adjacent bldg's fire escape at exp 4 of the above site. immediate correction action is needed. remedy: provide

    Nov 12, 2010 · Penalty $2,400

    Resolve
  • Class - 2

    Fail to comply w/commissioner order to file cert of correction w/dob.noted respondent failed to comply w/the commissioner's order to correct the violating conditions & file cert of correction pursuant to 28-204

    Jul 30, 2010 · Penalty $800

    Resolve
  • Class - 2

    Work without permit expired permit noted the following conditions. permit#104551414-01-eq-fn issued on 2-23-09 has expired on 2-11-10.note stalled site fence permit mustbe current dot permits have also expir

    Mar 20, 2010 · Penalty $800

    Resolve
  • Class - 1

    Work without permit noted the following conditions.sidewalk shed has been erected and theres no record of a permit being issued for this sidewalk shed.having not filed for a permit is hazardous to the safety of

    Mar 20, 2010

    Resolve
  • Class - 1

    Failure to institute/maintain safety equipment measures or temporary construction no guard rails noted the following condition the upper fl oors of this project does not have netting at fall protection perimete

    Mar 20, 2010 · Penalty $12,000

    Resolve
  • Class - 2

    Failure to safeguard public and property affected by construction operations (all person) on inspection concrete operation in progress, wiht pump hose running from pump truck to form work across public sidewa

    Sep 19, 2008 · Penalty $1,200

    Resolve
  • Class - 2

    No dot permit for street/ sidewalk closing not post as per code. concrete pump and truck was parked in the street/ sidewalk without permit for sidealk closing. rem: post d.o.t permits as per code stop illegal u

    Sep 19, 2008

    Resolve

Complaints

  • Unsanitary condition

    Pests

    Jan 29, 2026 · Apt 308

    Close
  • Electric

    No lighting

    May 11, 2024 · Apt 804

    Close
  • Heat/hot water

    Apartment only

    May 11, 2024 · Apt 804

    Close
  • Plumbing

    Water supply

    May 11, 2024 · Apt 804

    Close
  • Plumbing

    Water supply

    May 11, 2024 · Apt 804

    Close
  • Heat/hot water

    Entire building

    Oct 27, 2020 · Apt 306

    Close
  • Safety

    Window guard broken/missing

    Jan 27, 2020 · Apt 402

    Close
  • Unsanitary condition

    Mold

    Jan 27, 2020 · Apt 402

    Close
  • Heat/hot water

    Entire building

    Dec 8, 2019 · Apt 705

    Close
  • Plumbing

    Radiator

    Mar 28, 2019 · Apt 5RW

    Close
Show 11 more ↓
  • Water leak

    Heavy flow

    Mar 28, 2019 · Apt 5RW

    Close
  • Unsanitary condition

    Mold

    Mar 28, 2019 · Apt 5RW

    Close
  • Flooring/stairs

    Floor

    Mar 28, 2019 · Apt 5RW

    Close
  • Plumbing

    Bathtub/shower

    Mar 28, 2019 · Apt 5RW

    Close
  • Door/window

    Door

    Mar 28, 2019 · Apt 5RW

    Close
  • Door/window

    Window frame

    Mar 28, 2019 · Apt 5RW

    Close
  • Paint/plaster

    Wall

    Mar 28, 2019 · Apt 5RW

    Close
  • General

    Cabinet

    Mar 28, 2019 · Apt 5RW

    Close
  • Outside building

    Roofing

    Mar 28, 2019 · Apt 5RW

    Close
  • Heat/hot water

    Apartment only

    Sep 5, 2016 · Apt 705

    Close
  • Heat/hot water

    Entire building

    Feb 21, 2016 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H3)
Year built
2009
Floors
8
Residential units
—
Building area
28,850 ft²
Lot area
4,970 ft²
Zoning
R7-2
Community board
112
Council district
10
Block / lot
2155 / 26
Assessed value
$3,268,350
Landmark / historic district
No

HPD registration #144323, last renewed Dec 1, 2025.

Questions about 507 West 181 Street

Who owns 507 West 181 Street?

The owner of record in NYC Department of City Planning PLUTO data is 505 Wash LLC.

Does 507 West 181 Street have violations?

Yes. NYC HPD has recorded 15 housing violations at this property.

Is 507 West 181 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 507 West 181 Street built?

City records list 2009 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.