1160 St Nicholas Avenue
Manhattan, NY 10032BBL 1-02125-0001Map
Owner of record: NYC Department Of Education
1160 St Nicholas Avenue is a school building built in 1961 in Manhattan, 10032. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 32
- ECB violations
- 80
- HPD complaints
- 5
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 32
- Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 18, 2019
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 7, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 24, 2014
Dob violation - resolved
Show 22 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 12, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2011
Dob violation - resolved - Elevator elevatorrequired
3
Apr 15, 2010
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 15, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 4, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatorrequired
1p37183
Jul 24, 2002
Dob violation - resolved - Elevator elevatorrequired
1p37183
Apr 10, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 18, 1993
Dob violation - dismissed
ECB violations · 80
- Class - 2
Reissue ecb #35691816x. failure to maintain building in code-compliantmanner. no fire stopping per bc 712.3; 27-345. noted no five stopping at cellar level electrical room. multiple pipes penetrations through w
Feb 19, 2026 · Penalty $3,125
Active - Class - 2
Reissue ecb #35691814m. failure to maintain building in code-compliantmanner. both stairway doors leading to/from cellar missing panic bars.remedy: repair and/or replace.
Feb 19, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: smoke doors 1st floor and smoke door by exit #1 not self-closing. remedy: repair and/or replace.
Feb 19, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noted: exit door #11 hard to open and not self-close, exit door #4 not self-closing. remedy: repair/replace door.
Feb 19, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: crumbling concrete on main entry outside steps. remedy: repair and/or replace.
Feb 19, 2026 · Penalty $1,250
Active - Class - 2
Reissue: exit door not self closing: fire-proof doors 1st and 2nd floors. exit #7,8, 9 and 10 are not self-closing. remedy: comply with code.
Feb 27, 2025 · Penalty $1,562
Resolve - Class - 2
Reissue: 35676136r-failure to maintain building in code-compliant manner: no fire-stopping per bc 712.3, 27-345. at cellar level electrical rm has multiple pipes penetrations through wall w/out firestopping. re
Feb 27, 2025 · Penalty $3,125
Active - Class - 2
Reissue: 35676143p-failure to maintain building in code-compliant manner: electrical meter room 3 hole are exposed measuring 2'x3' creatinga tripping hazard. remedy: comply with code.
Feb 27, 2025 · Penalty $3,125
Resolve - Class - 2
Reissue: 35676143p-failure to maintain building in code-compliant manner: the concrete stairway leading to street level on 169th st has multiple cracks. remedy: comply with code.
Feb 27, 2025 · Penalty $3,125
Resolve - Class - 2
Reissue: 35676141l-failure to maintain building in code-compliant manner: both starways leading to/from cellar entry/exit door are missing panic/bars, pushbars. remedy: comply with code.
Feb 27, 2025 · Penalty $3,125
Active
Show 40 more ↓
- Class - 1
Failure to provide unobstructed exit passageway. on top floor there are wooden lockers throughout w/out a sprinkler system in place. remedy:comply with code.
Feb 27, 2025 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing. noted: at 1st flr. 2nd means of egress foroccupied 3k classrooms have exits #7, #8, #9 and #10, which are directexits to the exterior. the fireproof self-closing doors are not genera
Feb 2, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumniation for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at various locations throughout the occupied 4-story school buil
Feb 2, 2024 · Penalty $625
Resolve - Class - 2
28-301.1 unlawful placement of furnishings, decorations or other objects at exits that obstruct access to, egress from or visibilty thereof per fdny 2008 code; fc 1027.4. noted: at classrooms #308, #301, #209 a
Feb 2, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at both stairways leading to/from cellar,the entry/exit door for the staircase are missing panic/push bar.rem:repair and/or replace,install panic bar.
Feb 2, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at main entrance,the concrete stairway leading to/from street level on 169 st have multiple cracks and spalling concrete that are causing the concrete
Feb 2, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: no fire stopping per bc712.3; 27-345. noted: at cellar level, electrical meter room has multiple pipes penetrating through the wall that are missing fire-s
Feb 2, 2024 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at cellar,corridor leading to electrical meter room has approx.3 large holes in the floor measuring approx 2"x3".creating a hazard to anyone walking n
Feb 2, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at 3rd flr., public corridor has multiple cubbies which are creating a fire hazard in the event of a fire and/or emergency evacuating. remedy: repai
Feb 2, 2024 · Penalty $625
Resolve - Class - 2
Reissue35495453h failure to maintain bldg in codecompliant manner.noted:ato my insp i observed@cellar@electrical rm no firestopping where pipes penetrate thru wall,v35495453h issued5/12/20 for violating conditi
Jun 22, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue35495452x failure to maintain bldg in codecompliant manner.illumination for exits,exit discharges&public corridors per bc1006.1;27-381 note ato my insp i observed@gym&auditorium emergency lights not work
Jun 22, 2021 · Penalty $1,562
Resolve - Class - 1
No door lock monitoring installed in controller as mandated in appendix k 3 of 2014 building codes. remedy: install dlm, file and perform test with nyc dob
Feb 16, 2021 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & publuc corridors per bc 1006.1;27-381. note at gym & auditorium emergency lights not working. remedy: repair & or repl
May 12, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. note in auditorium left side of stage wall trhat protects stage is in disrepair falling apart. remedy: repair & or replace.
May 12, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. note in cellar at electrical room no fire stopping where pipes penetrare thru wall. remedy: provide & maintain fire stopp
May 12, 2020 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing at 3rd fl.at stairway "e" one door is not self closing properly,2nd fl.corridor exit door near rm.-215 one door not self closing properly,@1st floor stairway "e" 2 doors are not self
May 13, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc1006; 27-542. noted: 2 lights at gym don't work plus 1 at auxiliary lunch
Mar 27, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.lack of emergency exit lighting for exits,exit discharges & public corridors per bc1006.1;27-542 throughout various locations all levels emergency exit lights f
Jul 6, 2015
Resolve - Class - 2
Mis. 27-371(b) on 3rd, 2nd and 1st floors, various class room doors have plexi vision panels installed. remedy: replace plexi vision panels with approved safety glass
Feb 14, 2014
Resolve - Class - 2
3rd fl stwy 'b" door not closing 2nd fl stwy "c" racked. 1st fl smoke doors to gym are racked, stwy 'b" & "c" not closing. basement level main fl cafeteria door racked. remedy: repair / replace door
Feb 14, 2014
Resolve - Class - 2
3rd fl corridors partial obstruction by cubbies. remedy: remove obstruction
Feb 14, 2014
Resolve - Class - 2
Reissue 34908300n excessive combustible alt work at 3rd floor on walls and hanging from ceiling rem: remove excessive art work
May 8, 2012
Resolve - Class - 2
Reissue 34910548j 1st fl stwy b & c doors not closing bsmt lvl main floor exit #6 vestibule door not closing rem: repair / replace doors
May 8, 2012
Resolve - Class - 2
Reissue 34910549l 3rd fl corridor partial obstruction w/ tables and chairs rem: remove obstructions forthwith
May 8, 2012
Resolve - Class - 2
67x10.69m07.77q03. 67x-repair communication in car (telephone). 77q-install guard for light under car.
Feb 15, 2012
Resolve - Class - 2
Partial corridor obstruction.@ 1st,2nd,3rd flr corridor partial obstruction with tables,chairs book cases w/books,set up for student instruction.rem:remove all items,maintain corridor width clear
Apr 27, 2011
Resolve - Class - 2
Defective doors.the fire proof self closing doors are racked to frame and not self closing properly @ 1st flr gym exit 6 & 1st flr stairway b&c.rem:repair doors to properly open and self close
Apr 27, 2011
Resolve - Class - 2
Excessive combustible art work in corridors.@ 2nd & 3rd flrs the fire corridor have excessive combustible art work & decorating flr to ceiling across corridors & hanging from ceiling
Apr 27, 2011
Resolve - Class - 2
Failure to maintain bldg in code compliant manner noted:auditorium stage stairs & exit marked f have no handrails installed.rem:maintain bldg-repair &/or replace
Jul 15, 2010
Resolve - Class - 2
Occupancy contrary to that allowed by the cofo or bldg dept records noted:c/o#100130231-1st flr gym boys & girls lockerrooms/bathrooms converted into offices & classroom reissue nov#34792592m.rem:discontinue il
Jul 15, 2010
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.noted:reissue nov34791927k no firestopping for pipe penetrations in gas room.rem:maintain bldg-repair &/or replace
Jul 15, 2010
Resolve - Class - 2
Failure to maintain bldg in code complaint manner - exterior roof 0 machine room door -not self closing front doors not self latching.remedy:maintain bldg in code compliant manner.
May 14, 2009
Resolve - Class - 2
Reissue:344771047y.occupancy to that allowed by c of o. alt #100130234 corner of w 169 st & audobon ave -n play yard occupied as parking lotapprox 7 cars 1fl gym bthrm converted into offices.remedy:conform to
May 14, 2009
Resolve - Class - 2
Occupancy contrary to that allowed by c of o alt #100130234 1st flr gym bathrooms converted into offices. this ecb supersedes ecb violation 34791925r. remedy: conform to the c of o.
May 14, 2009
Resolve - Class - 2
Reissue 34593114x-roof. failure to maintain bldg in code compliant manner-exterior main roof does not meet minimum required height for parapet (parapet 24" high) required 42". remedy: raise parapet height to
May 14, 2009
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. exits lights not operational. 1-stair b. 2-exit light outside room 24. 3- exit light at cafeteria. remedy:maintain bldg in code compliant manner.
May 14, 2009
Resolve - Class - 2
Failure to maintain bldg in code complaint manner.gas meter room no fire stopping at penetrations. remedy:maintain bldg in code complaint manner.
May 14, 2009
Resolve - Class - 2
Occupancy contrary to that allowed by c of o #100130234.noted:small school yard in front now being fully occupied as parking lot approx 8 cars in yard.remedy:discontinue illegal use! or legalize current conditi
Apr 20, 2009
Resolve - Hazardous
08v11.12m0.55y13.85u05. 08 adjust levelling to fls 12 provide top of car lighting 55 seal & clean machine 85 perform & file 5yr test
Jun 20, 2008
Resolve - Non-hazardous
50a,50b,50c; national rad.ftfb, ld steam,oil fired,1960.50a-excessive temperature at the metal housing of the refernced boiler's #6 oil burner. evidence of a defective fiewall refractory in the furnace enclosur
Mar 20, 2008
Resolve
Complaints
- Heat/hot water
Entire building
Jan 15, 2022 · Apt 2A
Close - Heat/hot water
Entire building
Mar 3, 2019 · Apt BLDG
Close - Heating
Heat related
Jan 8, 2010 · Apt 34
Close - Heating
Heat related
Dec 23, 2009 · Apt BLDG
Close - Heating
Heat related
Dec 22, 2009 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1961
- Floors
- 5
- Residential units
- —
- Building area
- 77,712 ft²
- Lot area
- 55,259 ft²
- Zoning
- R7-2
- Community board
- 112
- Council district
- 10
- Block / lot
- 2125 / 1
- Assessed value
- $10,026,450
- Landmark / historic district
- No
Questions about 1160 St Nicholas Avenue
Who owns 1160 St Nicholas Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 1160 St Nicholas Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 1160 St Nicholas Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 1160 St Nicholas Avenue built?
City records list 1961 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.