Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 41

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2019

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 26, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 17, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 30, 2016

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
Show 31 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 1, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 13, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 8, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 8, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 1, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 23, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 22, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Elevator elevatorrequired

    1f5019

    Feb 3, 2000

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed

ECB violations · 69

  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 1st and2nd floors hallways installed/hung non fire retarted decorations to ceilings.rem:comply with code.

    Aug 6, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 1st fl cafeteria,stair c 2nd fl stair c hallway smoke doors near room 238,218basement stair c auditorium all doors are in disrepair/racked when tes

    Aug 6, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at basement auditorium,gym emergency lights and exit signs not working

    Aug 6, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing.noted:at 1st fl exit 1,3 doors are in disrepair/not closing when tested.rem:repair/replace door.

    Aug 6, 2026 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection. observed and noted at basement level gym and auditorium each place 2 exit door, basement level st. way 'd' 1 exit door, at 1st floor exit-2 outside

    Aug 13, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3; 27-345. fire stop missing in walls of gas meter room in pipe install done section of wall opened in 2 area walls not fixed or

    Sep 17, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue 35663415r. exit door not self-closing. 2 door in the gym not fully closing and 4 door in aud. alsp exit c one door need new hardware. remedy: repair/replace door.

    Sep 17, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing properly at the time of inspection, at 2nd floor stair "a" 2 exit doors, stair "c" one exit door & stair "b" one exit door (inside), one exit door (outside), at 1st fl gym 3 exit door

    Jun 9, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue35490647n failure to maintain bldg in codecompliant manner:illumination for exits discharges&public corridors per bc1006.1;27-781.noted:ato my insp i observed@2&3stair abc above smoke door371,241.corrido

    Jul 12, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Class 2 violation issued, items are, pit light not working, / electrical box under the car missing cover / in car ceiling light unsecured / top of car run box light not working / second floor hoist way door lig

    Mar 8, 2021 · Penalty $625

    Active
Show 40 more ↓
  • Class - 2

    Reissue#35423238m noted at the 3rd stair a,b,c above smoke door by 331,2nd floor stair a,b,c 2nd floor corridor by 241 1st floor stair a,b,c corridor by 101,107,basement stair a basement corridor by b22,b21,b19

    May 22, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35423239y noted at the 2nd floor stair a,b,c smoke by 220 1st floor stair c elevator doors at exit 1 and 2 the symnasium entrance by b15 and the auditorium main entrance the exit doors are not working

    May 22, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: through-out the building the emergency lights were not working when tested. remedy: repair and replace lighting

    Jun 24, 2019

    Resolve
  • Class - 2

    Exit door not self closing. noted: on the first and second floors staircase c the doors are not closing properly,the doors are hitting on teh door frame. remedy: repair /replace door.

    Jun 24, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: no fire stopping per bc712.3,27-345, observed holes around electrical pipes @ room 239 (corridor) & room b4. rem: provide/maintain fire stopping.

    Sep 27, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1, 27-342 observed: 90% of lights approx, doesnt work, properly like @ 3th

    Sep 27, 2016

    Resolve
  • Class - 2

    Exit door not self closing- observed @ auditorium, stage right side door & stair a @ cellar, near @ gym. rem: repair or replace door.

    Sep 27, 2016

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner-fail to provide wired vision panel as req.note:obs no wired glass on verious doors on flrs 1,2,3 and bsmnt lvl in rms:138,140,106,105,237,312,316,b18,gym.

    Sep 14, 2015

    Resolve
  • Class - 2

    27-334 reissue #35003040x protective guards/guardrail.note:protective guard rail @roof do not meet minimum height req of 3'-6".railing is approx 2'6".job #101880332 was signed oof 5/30/2002 for parapet.rem:com

    Sep 14, 2015

    Resolve
  • Class - 2

    Reissue #34987987r failure to maintain building in code-compliant manner.note:approx 0'-1" wide step cracks located at gym exit door areas. rem:repair defects.

    Sep 14, 2015

    Resolve
  • Class - 2

    Reissue #34987986p exit door not self-closing.note:at vestibule of exit # 1 and 2 doors (racked) & not self closing. rem:repair or replace doors.

    Sep 14, 2015

    Resolve
  • Class - 2

    27-371(b)reissue:35003041h plexi vision panels installed on various doors on 1st,2nd,3rd and basement level.ie, 138,140,106,105,237,312,316,b18,gym, etc.rem:provide required glass panels.

    Feb 5, 2014

    Resolve
  • Class - 2

    Reissue 35003039z. vestibule doors at exit lands are lands are racted gym exit door near stairway "a" clsoing. stay"a" 1st and 2nd floor doors are racked. remedy: replace doors.

    Feb 5, 2014

    Resolve
  • Class - 2

    Failure to maintain. crack in masonary wall is gym. wall is near exit door. remedy: repair defects.

    Feb 5, 2014

    Resolve
  • Class - 2

    Reissue 34950312j. vertical crack in masonry wall near window in room 206. remedy: repair wall.

    Jan 23, 2013

    Resolve
  • Class - 2

    Sec. 27-371(b) plexi vision panels installed on doors 305,316,321,323,325,320,322,324,326,336,340,339,342,343,344,218 and 243. remedy: provide required glass panels. remedy: provide required glass panels.

    Jan 23, 2013

    Resolve
  • Class - 2

    Reissue 34950311h. at vestibule of exit 1 and 2 doors are racked preventing them from closing properly. remedy: repair/replace doors.

    Jan 23, 2013

    Resolve
  • Class - 2

    Reissue 34950310x. protective guard rails at roof do not meet minimum height requirements of 3'6" railing is approx 2'6" noted job 101880332was signed off 5.30.02 for parapet. remedy:comply w/height requirement

    Jan 23, 2013

    Resolve
  • Class - 2

    Storage of tables,chairs and cabinets obstructing 3rd flr corridors. remedy: remove all obstructions.

    Jan 23, 2013

    Resolve
  • Class - 2

    Use of prohibited door hardware per bc 1008.1.8; 27-371(j). note: at 3rd fl corridor smoke doors near rooms 305 & 339 have hold-backs installed to keep doors open. remedy: remove prohibited hardware./provide s.

    Apr 12, 2012

    Resolve
  • Class - 2

    Sec. 1509.8 reissue: 34922481m protective guard rails at roof do not meet minimum height requirement of(3'6" ) railing is approx 2'high. also note: job #101880332 signed off 5/30/02 for parapet. remedy: comply

    Apr 12, 2012

    Resolve
  • Class - 2

    Reissue: 34909682m 2nd floor stwy'a' door raccked. 1st floor stwy'b' vestibule doors not closing. remedy: repair/replace doors.

    Apr 12, 2012

    Resolve
  • Class - 2

    Vertical crack in masonry wall of room 206 near window. remedy: repair wall.

    Apr 12, 2012

    Resolve
  • Class - 2

    (misc)bc1509.8reissue#34839471l.protective guard rails @ roof do not meet minimum height requirement of 3'6"railing is approx 2'high also not job#101880332 signed off 5/30/02 for parapet.rem:comply w/height req

    Jun 1, 2011

    Resolve
  • Class - 2

    Plaster spalling form ceiling in stairway "c" bulkhead & room 337 due to leaking roof. remedy: repair spalling plaster.

    Jun 1, 2011

    Resolve
  • Class - 2

    Roof leaking in stairway "c" bulkhead & above room 337. remedy: repai r leaking roof.

    Jun 1, 2011

    Resolve
  • Class - 2

    Eissue: 34839470j 32nd stairway "b" doors not closing. 1st flr cafete ria door near stairway "b" not closing. stairway "b" vestibule doors not closing. remedy: repair/replace doors.

    Jun 1, 2011

    Resolve
  • Class - 2

    Reissue: 34793027y. 3rd fl stwy "b" doors not closing corridor smoke doors near room 322 have been removed 2nd fl corridor smoke doors near rooms 204 & 221 have also been removed. stwy "b" door not closing. 1st

    Apr 22, 2010

    Resolve
  • Class - 2

    Sec. bc 1017.1 3rd fl corridor width have been decreased w/ cubbies throughout. also note : stwy "c" steps to bulkhead are partially blocked by crates. remedy: remove obstructions

    Apr 22, 2010

    Resolve
  • Class - 2

    Sec. bc1509.8 reissue: 34793025k, 34711418j, 34570614k, 34466167h, 34428320h. protective guard rials @ roof do not meet min height requirement of 3'6" railing is approx 2' high. remedy: comply w/ height require

    Apr 22, 2010

    Resolve
  • Class - 2

    3rd flr stwy 'b' doors not closing. corridor smoke doors near room 322 not closing or opening property. 1st flr stwy 'a' doors not closing. cafeteria exit doors near room 106 not closing & corridor smoke doors

    Jun 25, 2009

    Resolve
  • Class - 2

    All roof access doors locked from inside with sliding hatch hardware. remedy: remove illegal hardware.

    Jun 25, 2009 · Penalty $2,500

    Resolve
  • Class - 2

    Stairway id sign missing from all stairways at all flrs on stwy side. remedy: provide stwy i.d. signs.

    Jun 25, 2009

    Resolve
  • Class - 2

    Reissue: 34711418j protective guard rails at roof do not meet min height requirements of 3'6". railing is approx 2'high. remedy: comply withheight requirement.

    Jun 25, 2009

    Resolve
  • Class - 2

    Step cracks in elevator shaft wall st cellar in room b24. also note said wall is bulging. remedy: repair block wall.

    Jun 25, 2009

    Resolve
  • Class - 3

    Reissue 34570513z.failure to maintain bldg in code compliant manner.note:room b25 has large 8' x 2/4"vertical crack in bldg wall. remedy:reapir wall.

    Nov 13, 2008

    Resolve
  • Class - 3

    Reissue #34570614k.failure to maintain bldg wall or appurt.note:roof metal railing is substandard height approx2, not 3'6" as required.remedy:replace ( ) roof.

    Nov 13, 2008

    Resolve
  • Class - 3

    Failure to maintain bldg in code compliant manner.note:defective exit door does not open or close properly .location 2fl, stair c.remedy:repair/replace door.

    Nov 13, 2008

    Resolve
  • Hazardous

    A vertical crack in the interior wall in room b25 on bsmt level above the entry doorway to sub-bsmt level. remedy- repair crack in wall.

    Jul 13, 2007

    Resolve
  • Non-hazardous

    Re issue: 34466167h. protective guard rails on roof level does not meet min. height requirements (3'-6"). (existing guard rails are approx. 2' high). remedy- increase height of guard rail to 3'-6".

    Jul 13, 2007

    Resolve

Complaints

  • Appliance

    Refrigerator

    Sep 5, 2022 · Apt 25

    Close
  • Appliance

    Electric/gas range

    Sep 5, 2022 · Apt 25

    Close
  • Plumbing

    Toilet

    Sep 5, 2022 · Apt 25

    Close
  • Door/window

    Door

    Sep 5, 2022 · Apt 25

    Close
  • Unsanitary condition

    Pests

    May 19, 2022 · Apt 4

    Close
  • Plumbing

    Basin/sink

    May 19, 2022 · Apt 4

    Close
  • Unsanitary condition

    Sewage

    May 19, 2022 · Apt 4

    Close
  • Paint/plaster

    Wall

    May 19, 2022 · Apt 4

    Close
  • Unsanitary condition

    Garbage/recycling storage

    May 27, 2021 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Mar 23, 2017 · Apt 10

    Close
Show 1 more ↓
  • Heating

    Heat related

    Jan 4, 2013 · Apt BLDG

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1958
Floors
3
Residential units
—
Building area
125,048 ft²
Lot area
44,962 ft²
Zoning
R7-2
Community board
110
Council district
9
Block / lot
2042 / 35
Assessed value
$11,430,000
Landmark / historic district
No

Questions about 311 West 140 Street

Who owns 311 West 140 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 311 West 140 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 311 West 140 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 311 West 140 Street built?

City records list 1958 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.