2 Edgecombe Avenue

Manhattan, NY 10030BBL 1-01960-0001Map

Owner of record: NYC Department Of Education

2 Edgecombe Avenue is a school building built in 1925 in Manhattan, 10030. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
17
ECB violations
57
HPD complaints
3

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 17

  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
Show 7 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed

ECB violations · 57

  • Class - 2

    Reissue:35725229y exit door not self-closing.exits leading to streets#2,3,8 are not self closing and has rust.rem:comply with code.

    Aug 4, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35725227k failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per 1008.1.8;27-371(j).5th floor stair h,gym has illegal key locking device.rem:comply with code.

    Aug 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue:35725226z failure to maintain building in code-compliant manner.5th floor gym emergency lights are not working.rem:comply with code.

    Aug 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue:35725225r failure to maintain building in code-compliant manner.1st floor exit#3,2nd floor stair d,4th floor d,not self-closing.rem:comply with code.

    Aug 4, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self closing.noted:at 1st fl exit 3 2nd fl stair f,g 3rdfl stair d 4th fl stair d doors are in disrepair/not closing when tested.rem:repair/replace door.

    Sep 3, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:5th fl stair h,gym installed key locking devices where not allowed.rem:provide legal

    Sep 3, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb#35683045r failure to maintain building in code compliant manner.noted at exit 2,3,8 doors/frames rusting/corroding.rem:repair and/or replace.

    Sep 3, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 5th fl gym emergency lights not working when tested throughout vari

    Sep 3, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 2nd fl gym emergency light damage with missing/none of protective metal cage.rem:repair and/or replace.

    Sep 3, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain uilding in code-compliant manner. exterior door feame rusted with holes in some, at exit 2, exit 3, exit 8 inside door frame and storage room inside door frame, exit 5 exterior frame. remedy

    Sep 16, 2024 · Penalty $625

    Active
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code compliant manner.at time of inspection observed at exp #3 at 4th floor level under corpen stone water penetration through to facade causing water damage to ladies bathroom c

    May 24, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.at time of inspection observed at 5th floor level water leak when it rains causing water damage at 16 bulkhead at 5th floor also water penetration under to

    May 24, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner manner noted at (4th fl) rm 460 (basement) boiler rm (east side) water peentration/damage with staining to ceilings walls and floors repair and or replace

    Jun 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building inc ode compliant manner illumination for exits exit discharges and public corridors per bc 1006.1/27-381 noted at (5th fl) gym (3rd fl ) gym (1st fl) cafeteria auditorium emrgency

    Jun 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted at (1st fl) exit s door in disrepair/racked. repair and or replace

    Jun 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits, exit discharges and public corridors per bc 1006.1.27-381 at first floor lunch room near exit "3" one place 2 lights are not

    Jun 20, 2019

    Resolve
  • Class - 2

    Reissue # 35207887x date of issue 9/27/16. exit door not self closing properly at 3rd floor stair way "f" 2 door, 3rd floor stairway "g" one exit door 3rd floor stairway "c" 1 door. exit #7 at first floor

    Jun 20, 2019

    Resolve
  • Class - 2

    Exit door not self closing.noted: exit#7 @ 1st flr corridor doors, stairs d & f gym door @ 3rd flr, stair d @ 5th flr & smoke corridor door @ 4th flr. rem: replace/repair doors. comply w/ code.

    Sep 27, 2016

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner-fail to pro vide wire glass vision panels.note:doors # 415 and 416 do not have wired glass. rem: comply w/code.

    Sep 28, 2015

    Resolve
  • Class - 2

    Exit door not self-closing.note:exit 7 at 1st floor corridor doors, stair 'd' and 'f' at 3rd fl, gym door @ 3rd fl, stair 'd' @ 5th fl and smoke corridor door @ 4th fl. rem:repair/replace doors.

    Sep 28, 2015

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances.note:main entry on edgecombe ave light cover missing from entry light fixture. rem: replace.

    Sep 28, 2015

    Resolve
  • Class - 2

    3rd flr stwy "f" door is racked, 2nd flr corridor smoke door near room213 not closing. 1st flr stwy "d" door not closing. remedy: repair/replace doors.

    Feb 7, 2014

    Resolve
  • Class - 2

    Kick down door stops installed on doors to rms 308,310,312,313,314,263,209,206,205,202,105 and rear door of 3rd flr gym. remedy: remove doorstops.

    Jan 24, 2013

    Resolve
  • Class - 2

    Reissue 34839466r vertical cracks in glazed brick wall in 3rd floor gym above entrance. remedy: repair/replace defects.

    Jun 16, 2011

    Resolve
  • Class - 2

    Vertical cracks in glazed brick wall @ 3rd fl gym above main entrance.remedy: repair cracks

    Apr 21, 2010

    Resolve
  • Class - 2

    Exterior bldg wall has become pouros & allowing rain water to enter bldg to walls & ceilings @ 5th fl stwy "h" and room 407. remedy: water proof exterior bldg wall stop water penetration.

    Apr 21, 2010

    Resolve
  • Class - 2

    5th fl stwy "h" plaster spalling from wall. room 407 plaster spalling from wall & ceiling. remedy: repair spalling walls & ceilings

    Apr 21, 2010

    Resolve
  • Class - 2

    4th fl stwy "g" door not closing fully. corridor smoke doors hewr room455 not closing fully. remedy: repair / replace doors

    Apr 21, 2010

    Resolve
  • Class - 2

    5th flr stwy 'd' doors (lock) closing fully. remedy: repair/replace doors.

    Jun 25, 2009

    Resolve
  • Class - 3

    Failure to maintain bldg wall or appurt.note:flat roof throughout (main roof) is in disrepair w/bubbles & bulges & is torn w/exposed under 9 ) in several areas.remedy:replace roof at main bldg.

    Nov 14, 2008

    Resolve
  • Hazardous

    Interior plaster is spalling on the ceiling located in room 303 on the3rd level. remedy- repair plaster ceiling.

    Jul 16, 2007

    Resolve
  • Hazardous

    Horizontal cracks along the interior wall of room 302 on the 3rd fl level & staircase "e" b/w floors 5th & roof. remedy- repair horizontal cracks in wall.

    Jul 16, 2007

    Resolve
  • Non-hazardous

    Noted: cafeteria, kitchen exit (interior) door use of illegal hardware(slide bolt lock). remedy: remove illegal hardware on exit door.

    Jan 26, 2005

    Resolve
  • Non-hazardous

    Noted: north elevation, west end exit stone cornice gymnasium (crown molding) is cracked and open. remedy: repair stone cornice above exit doors.

    Jan 26, 2005

    Resolve
  • Non-hazardous

    Noted: east elevation, north end exit stone cornice (soffit area) has cracked and separated with crack opening approx 3/8" wide for entire door width. remedy: repair stone cornice above exit doors.

    Jan 26, 2005

    Resolve
  • Non-hazardous

    Noted: east elevation, south end exit stone cornice (soffit area) has cracked and separated with crack opening approx 3/8" side for entire door width. remedy: repair stone cornice above exit doors.

    Jan 26, 2005

    Resolve
  • Hazardous

    Failure to maintain building. defects noted: front main entrance, right side staircase to second floor has five cracked and loose marble treads. also noted: first floor granite stairs down to west 135 street

    Jul 1, 2004 · Penalty $10,000

    Resolve
  • Non-hazardous

    Failure to maintain building. defects noted: (1) exit 'f' 5th flr. missing closer (2) at 3rd flor. gym, exit doors on left side swing in (3) defectvie closer exit doors on right side- does not close (4) at cafe

    Jan 27, 2004

    Resolve
  • Non-hazardous

    Failure to maintain building. defects noted: (1) wall behind radiator damaged due to leak-landing at roof,north end stair (2) room 504, damage ceiling from leak at roof drain pipe (3) at gym. vertical crack in

    Jan 27, 2004

    Resolve
  • Non-hazardous

    Failure to maintain exterior building. defects noted:(1) cracks at parapet walls south & west (2) bubbling & cracking of asphalt roofing material (3) vertical cracks in stone molding-south side & cracks in ston

    Jan 27, 2004

    Resolve
  • Hazardous

    Reissue. failure to maintain building. defects noted: stairway1, 1st to 2nd floor has & cracked & loosed marble steps stair at 135 st. entrance has 2 cracked & loose steps. remedy: maintain building/repair as r

    Jan 27, 2004

    Resolve
  • Non-hazardous

    Use of illegal hardware. noted: exit doors ne @ exit doors #10nw (3) exit doors, stair 'e' & stair 'f' east (4) exit doors #9 sw (5) exit door se- from auditorium front/right illegal hardwate-throwbolt w/padloc

    Jan 27, 2004

    Resolve
  • Non-hazardous

    Failure to maintain buidling defects : boiler room : 15 floor plates ( metal approx 1" x 4" each ) are uneven to floor dur to rusted supportremedy : maintain buidling repair as needed

    Jan 13, 2003

    Resolve
  • Hazardous

    Failure to maintain building. defects : stairway / first to second floor has 4 cracked and loose marble steps stairs at 135 st entrance has 2 cracked and loose steps remedy : maintain buidling repair as needed

    Jan 13, 2003

    Resolve
  • Non-hazardous

    Failure to maintain,defects.missing heat radiator covers.locations:506,510,511,512,513,516,515,417,418,416,459,414,413,412,410,409,407,302,309 remedy:do repairs

    May 7, 2001

    Resolve
  • Non-hazardous

    Failure to maintain,defects.,damaged flooring tiles.locations:415,405,400 at door,307,201 remedy:do repairs

    May 7, 2001

    Resolve
  • Non-hazardous

    Failure to maintain,defects,concrete foundation support columns cracked with certical spalling.locations:basement at rearwall at oil tank room.remedy:do repairs

    May 7, 2001

    Resolve
  • Non-hazardous

    Failure to maintain,defects,metal gratings rusted and supports corroded.locations:west yard at gas vents adjacent chimney.remedy:do repairs

    May 7, 2001

    Resolve
  • Non-hazardous

    Failure to maintain,defects cracked plaster walls in corridors adjacent to rooms.locations:510,461,350 remedy:do repairs

    May 7, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defects,cracked plaster ceilings.locations:5th fl stair c.503,504,414,307,309.remedy:do repairs

    May 7, 2001

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jan 20, 2024 · Apt 70

    Close
  • Heat/hot water

    Entire building

    Nov 13, 2019 · Apt 8ONTHE

    Close
  • Plumbing

    Water supply

    Apr 26, 2009 · Apt 3

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1925
Floors
5
Residential units
—
Building area
119,370 ft²
Lot area
49,957 ft²
Zoning
R7-2
Community board
110
Council district
9
Block / lot
1960 / 1
Assessed value
$6,885,900
Landmark / historic district
No

Questions about 2 Edgecombe Avenue

Who owns 2 Edgecombe Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 2 Edgecombe Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 2 Edgecombe Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2 Edgecombe Avenue built?

City records list 1925 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.