2296 Adam C Powell Blvd
Manhattan, NY 10030BBL 1-01940-0035Map
Owner of record: Abyssinian Culturalbuilding Corp.,
2296 Adam C Powell Blvd is a school building built in 1924 in Manhattan, 10030. The owner of record is Abyssinian Culturalbuilding Corp.,. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 61
- ECB violations
- 18
- HPD complaints
- 21
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 61
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 26, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 26, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 26, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 20, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 20, 2018
Dob violation - active
Show 40 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Nov 20, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 21, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 21, 2016
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 15, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 15, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 15, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 23, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 23, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 23, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2012
Dob violation - active - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jan 1, 2012
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 19, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 19, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 19, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 19, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 26, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 26, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 26, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 29, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 29, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 29, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 19, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 19, 2007
Dob violation - resolved
ECB violations · 18
- Class - 2
Reissue ecb#35721320r exit door not self closing.noted:at 1st fl exit 2 door indisrepair/not closing when tested.rem:repair/replace door.
Aug 4, 2026 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at roof/6th fl bulkhead/stair a with water damage/staining with spacing of plaster/paint of ceiling/walls/windows areas.rem:repair and/or replace.
Aug 4, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:at basement cafeteria,stair a all doors are in disrepair/racked.rem:repair and/or replace.
Aug 4, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing properly at the time of inspection observedand noted at 6th floor gym 1 exit door, 5th fl stairway "a" 2 exit door, 2nd fl stairway "a" 3 exit door cellar level stairway "a" 2 exit do
Aug 11, 2025 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 1st floor main entrance
Aug 11, 2025 · Penalty $1,250
Resolve - Class - 2
Found hb smith boiler series 28x6, blr #2 not operable due to leaking section, also found exposed wiring.
Oct 26, 2023 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.no fire stopping per bc 712.3,27-345 noted at cellar level gas and electrical meter room has holes in various areas throughout provide/maintain fire stoppin
May 21, 2020 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing properly. at 6th floor stair way "a" one exit door not self closing properly at the time of inspection when tested. remedy: repair/replace door
Jun 19, 2019
Resolve - Class - 2
Emergenc signs at elevator call station missing. kitchen delivery elevator missing emergency signage at both flrs. rmdy: install signage.
Sep 10, 2015
Resolve - Class - 2
Bulkhead door to roof at stwy "a" is sticking hard to open. remedy: repair/replace door.
Feb 7, 2014
Resolve
Show 8 more ↓
- Class - 2
Reissue: 35002833l. 2nd flr and cellar level stwy "a" doors not closing. remedy: repair/replace doors.
Feb 7, 2014
Resolve - Class - 2
Reissue 34954418x. doors at stair a cellar, 2,4, & 5 flrs are racked preventing them from completely opening or completely closing. remedy:repair/replace doors.
Jan 16, 2013
Resolve - Class - 2
Cellar level stwy a door not closing.rem:repair/replace doors.
Apr 26, 2012
Resolve - Class - 2
Building occupied & temp c/o #102296150t011 has exp 2/7/07. remedy: obtain valid c of o or discontinue illegal occupancy.
Jun 24, 2009
Resolve - Class - 2
Altered/changed bldg occupied w/o a valid c/o as per 28-118.3.1-28-118.3.2. noted: above premises is occupied and temp c/o 102296150t011 hasexp 2.7.07. remedy: obtain a valid c/o.
Jun 24, 2009 · Penalty $2,500
Resolve - Non-hazardous
Failure to maintain building defect noted : rm # 701 ( elev. mach r. ) crack in block near floor opp. dr. remedy : maintain building / repair as required
Apr 2, 2004
Resolve - Non-hazardous
Failure to maintain building defect noted : 2nd flr. stair "a" 1st door defective ( does not close properly ) remedy : maintain building / repair as required
Apr 2, 2004
Resolve - Non-hazardous
37r7,73o2. 37-remove alligator clips from back of controller. 73- clean installation.
Jan 7, 1999
Resolve
Complaints
- Unsanitary condition
Mold
May 13, 2025 · Apt 4N
Close - Unsanitary condition
Pests
May 13, 2025 · Apt 4N
Close - Unsanitary condition
Pests
May 13, 2025 · Apt 4N
Close - Heat/hot water
Entire building
Nov 2, 2023 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 18, 2022 · Apt BLDG
Close - Unsanitary condition
Garbage/recycling storage
Sep 24, 2021 · Apt 5A
Close - Door/window
Window frame
Sep 24, 2021 · Apt 5A
Close - Heat/hot water
Entire building
Dec 23, 2019 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 2, 2019 · Apt BLDG
Close - Unsanitary condition
Pests
Jul 17, 2019 · Apt 36
Close
Show 11 more ↓
- Plumbing
Water supply
Jul 20, 2015 · Apt 2F
Close - Heat/hot water
Apartment only
Jul 20, 2015 · Apt 2F
Close - Heat/hot water
Entire building
Jul 20, 2015 · Apt 2F
Close - Plumbing
Water supply
Jul 20, 2015 · Apt 2F
Close - Water leak
Heavy flow
Apr 30, 2014 · Apt 2A
Close - Door/window
Window frame
Apr 30, 2014 · Apt 2A
Close - General
Mold
Jul 6, 2006 · Apt 2A
Close - Plumbing
Water-leaks
Jul 6, 2006 · Apt 2A
Close - Paint/plaster
Ceiling
Jul 6, 2006 · Apt 2A
Close - General
Locks
Jul 6, 2006 · Apt 2A
Close - Nonconst
Vermin
Jul 6, 2006 · Apt 2A
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1924
- Floors
- 6
- Residential units
- —
- Building area
- 85,310 ft²
- Lot area
- 13,540 ft²
- Zoning
- R7-2
- Community board
- 110
- Council district
- 9
- Block / lot
- 1940 / 35
- Assessed value
- $11,564,100
- Landmark / historic district
- No
Questions about 2296 Adam C Powell Blvd
Who owns 2296 Adam C Powell Blvd?
The owner of record in NYC Department of City Planning PLUTO data is Abyssinian Culturalbuilding Corp.,.
Does 2296 Adam C Powell Blvd have violations?
NYC HPD has no housing violations on record for this property.
Is 2296 Adam C Powell Blvd rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 2296 Adam C Powell Blvd built?
City records list 1924 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.