430 East 100 Street
Manhattan, NY 10029BBL 1-01694-0001Map
Owner of record: Nys Urban Development Corporation
430 East 100 Street is a school building built in 1973 in Manhattan, 10029. The owner of record is Nys Urban Development Corporation. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 151
- ECB violations
- 142
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 151
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 30, 2024
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 2, 2020
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 22, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/ts
Jan 3, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active
Show 40 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/ts
Nov 14, 2016
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - active - Elevator elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/ts
May 30, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7a technical report by 02/21/2012
Jan 31, 2013
Dob violation - dismissed - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7a technical report by 02/21/2012
Jan 31, 2013
Dob violation - dismissed - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7a technical report by 02/21/2012
Jan 31, 2013
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2010 inspection report
Dec 13, 2011
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed
ECB violations · 142
- Class - 2
Failure to maintain building in code compliant manner.noted:at ground fl hallway smoke door near rm 64 glass panel cracked/shattered.rem:repair and/or replace.
Jul 22, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542.noted:at 2nd fl gym rm 205f not installed/provided without em
Jul 22, 2026 · Penalty $1,250
Active - Class - 2
Reissued ecb#35724667j failure to maintain building in code-compliant manner.noted at 3rd fl hallway smoke door near rm 305,art rm door 302 2nd fl hallway smoke door near doors 201,206,stair b 1st fl stair b gr
Jul 22, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: the double main entry doors and frame need to be replaced. both doors do not oeprate correctly and the center mullion is loose causing doors to shak
Sep 24, 2025 · Penalty $1,250
Active - Class - 2
Class 2 items: provide a door lock monitor tag on controller.category 1 test tag expired. clean excessive oil from drip pan under oil tank.
Jan 13, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at first floor in front of auditorium,missing floor tiles approx.b sq ft area.rem:make necessary repairs.
Aug 28, 2024 · Penalty $625
Resolve - Class - 1
Cease use item: all car door retainers (gibs) are not secure and worn. need to be corrected. remedy: restore to service immediately and call the dob elevator division at (212) 393-2144 for a re-inspection. 97-x
Aug 20, 2024 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1.8-27-371(j) noted at the tim eof my inspection observed both cafeteria smoke door and auditorium hall
Jul 27, 2021 · Penalty $625
Resolve - Class - 2
Reissue #35495438j failure to maintain building in code compliant manner illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 noted throughout the building all of the emergency light
Jul 27, 2021 · Penalty $1,562
Resolve - Class - 1
No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor
Jun 8, 2020 · Penalty $6,250
Active
Show 40 more ↓
- Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit bdischarges & public corridors per bc 1006.1;27-381. noted: throughout the bldg most of the emergency lights were not working when
May 28, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted on the 2nd flr @ the auditorium the door hinges is broken, causing the door not to close. rem: repair &/or replace.
Jun 8, 2017
Resolve - Class - 2
/11x10/10d06/16i10/17d06/12x10/70y02/70o02/72b09/ 11x10-card reader inoperative-repair. 70o02-remove rags from pit area. 23x10-card reader inoperative-repair. 72b09-remove existing run/stop switch. 16i10-sight
Mar 25, 2015
Resolve - Class - 2
Re-issue # 34996188p. defective doors. at corridor 301,305,307,3c, racked doors & broken door closers. remedy: repair doors to operate properly.
Jun 3, 2014
Resolve - Class - 2
Combustibles in corridors. at corridors 205,306, combustible cubbies with storage of personal items, clothes, paper... remedy: remove combustible items.
Jun 3, 2014
Resolve - Class - 2
Defective doors at rooms 301,307b,202c,doors are racked,w/pulled hingers & not slf closing properly. remedy: repair doors.
Jan 25, 2013
Resolve - Class - 2
Emergency exit not illuminated at various locations all floors,numerious emergency "exit" signs are not illuminated. remedy: repair signs,replace bulbs.
Jan 25, 2013
Resolve - Class - 2
Reissue 34927077n. concrete entrance ramp is spalling under side of ramp has exposed rebar. rem:repair spalling concrete.
Jun 22, 2012
Resolve - Class - 2
27-766: reissue 34927076l. no fresh air vent in gas meter room. rem:provide fresh air vent.
Jun 22, 2012
Resolve - Class - 2
27-371(b):reissue 34927079r. plexi vision panels installed at various doors throughout 2nd & 3rd flrs. rem:provide code compliant visions panels.
Jun 22, 2012
Resolve - Class - 2
Roof north side coping is cracked & spalling. rem:repair/replace defective coping.
Jun 22, 2012
Resolve - Class - 3
Unauthorized storage. at elctric room,storage of maintenance equipment.remedy:remove all items,maintain service room storage free.
Aug 17, 2011
Resolve - Class - 2
Cracked cmu block. at room 124,vertical crack in cmu block at fara corner.remedy:repair cmu block masonry.
Aug 17, 2011
Resolve - Class - 2
Defective ceiling. at corridor marked 306, broken,loose & hanging suspended ceiling tiles. remedy:repair ceiling.
Aug 17, 2011
Resolve - Class - 2
27-371(b)misc.vio.plexi vision panels. plexi(thermo plastic)vision panels installed at various corridor doors throughout 2nd & 3rd flrs, & various corridor rooms nd & 3rd flr.remedy:provide code compliant visio
Aug 17, 2011
Resolve - Class - 2
Reissue#34791335r water penetration. the foundtion ha become proous allowing water to penetrate into boiler rm & adjacent room w/electric panel w/1" standing water at time of inspec.-dryday-remedy:water proof f
Aug 17, 2011
Resolve - Class - 2
Reissue#34863761j spalling concrete. at entry ramp, spalling concrete exposing re-bar.at east side,spalling concrete exposing re-bar at various areas, 1st & 2nd flrs.remedy:repair exterior masonry.
Aug 17, 2011
Resolve - Class - 2
27-766misc.vio.reissue# 34863762l no fresh air vent. at gas meter room,no fresh air ventilation. remedy:provide fresh air vent.
Aug 17, 2011
Resolve - Class - 2
Reissue #34863763n missing fire stop.at gas meter room,no fire stop at pipe & conduit penetrations.remedy:provide fire stop.
Aug 17, 2011
Resolve - Class - 2
Reissue: 34791335r concrete entrance ramp cut front is spalling,rebar exposed. also note at east side small play area,exterior wall concrete spalling rebar exposed. remedy: repair spalling concrete.
Aug 12, 2010
Resolve - Class - 2
No fresh air vent in gas meter room. remedy: provide fresh air vent for gas meter room.
Aug 12, 2010
Resolve - Class - 2
Holes in wall of gas meter room near pipe penetrations. remedy: provide/maintain fire stopping.
Aug 12, 2010
Resolve - Class - 2
Reissue: 34791337k 3rd floor stwy'c' doors not closing. 2nd floor stwy'a & d' doors not closing. 1st floor stwy 'c & d' & east side cafeteria exit doors not closing. ground floor corridor smoke doors near room
Aug 12, 2010
Resolve - Class - 2
3rd fl stwy c doors not closing 2nd fl stwy a&d door not closing 1st fl stwy d&c and east side cafeteria exit door not closing also note glass section of corridor smoke doors near room g13 is missing rem: repai
Jun 3, 2009
Resolve - Class - 2
Approx 11 cars parked at east playyard entrance near fdr drive rem: discontinue illegal use of amend c/o
Jun 3, 2009
Resolve - Class - 2
Reissue 34657757j foundation wall has become porous and allowing water into bldg in boiler rm adjacent to electrical panel at cellar lvl also note under side of concrete entrance ramp is spalling rebar exposed
Jun 3, 2009
Resolve - Hazardous
Reissue: 34576731r foundation wall has become porous and allowing rain water into the building causing interior damages in the boiler room adjacent to the electrical panel unit. at cellar level. remedy: water p
Jun 20, 2008
Resolve - Non-hazardous
Exit door not self closing. 1 fl- stairway 3- 1 door closer broken. remedy: replace door closers.
May 24, 2007
Resolve - Non-hazardous
Reissue #34517289n. failure to maintain- exterior. cellar- boiler rm- wall w/ electric panel on it, by phone rm, water is penetration the wall & causing damage to the wall. remedy: repair wall, stop water
May 24, 2007
Resolve - Non-hazardous
Reissue #34517288l. failure to maintain- interior all class rm doors on the 4 fl do not have self closers. remedy: replace/ install self closers.
May 24, 2007
Resolve - Hazardous
Reissue: 34465994r. exterior concrete wall has become porous & allowing rain water to enter the bldg & causing damage to the interior finishlocated in the boiler room on the 1st flr. remedy: waterproof wall.
Apr 5, 2006
Resolve - Hazardous
Reissue: 34465996k. fireproof self closing door (f.p.s.c.) @ the 4th flr located thruout the classrooms are not self-closing. remedy: install self-closing (door checks)
Apr 5, 2006
Resolve - Non-hazardous
Water leaking form wall in boiler room next to phone roomreissue:34283863j. remedy:locate leak or water proof wall at the above location.
Feb 18, 2005
Resolve - Non-hazardous
All class room door's on 4floor do not have self closer's (fpsc) remedy: provide self closer's on class room door's on 4th floor (fpsc).
Feb 18, 2005
Resolve - Non-hazardous
50d 42/50e 50 50a 50b 50c 50) oil leak at burner. 50a) both pressure controls piped to boiler on one 1/4 syphon loop. 50b) boiler safety valves not piped down. 50c) link plate rotted away.50d) boiler insolation
Sep 24, 2004
Resolve - Non-hazardous
R5-1ssue failure to maintain building defect broken doors at exterior of exit 4 and also at exterior staircase room near exit 4 remedy:maintain bulding repair/replace doors.
Jan 7, 2004
Resolve - Non-hazardous
Failure to maintain defects broken door chocks 3rd floor exit 3(1),4( 1)boy & girls rms 2nd 4boys & girls rooms and 202(1) 1st ext 5(1), 2(1)and room 133 ground exit 4(2) remedy:maintain building replace as req
Jan 7, 2004
Resolve - Non-hazardous
Failure to maintain exterior building wall vertical cracks in concretewall defects vertical cracks in concrete wall (approx 1/2 to 1)wide and 4'to 8')at sw cornor next to north parking garage causing water dam
Jan 7, 2004
Resolve - Non-hazardous
R5-issue failure to maintian defects door do not close at 3rd fl opens 3 & 5 room 302 at 2nd fl exits 2,3,4,5 room 205 ground fl exits 2,3
Jan 7, 2004
Resolve - Non-hazardous
Re issue failure to maintain bldg noted water damage causing falling plaster at ceiling of the ground floor hallway at two location first location near exit 2 approx 4sq ft second room g38 approx 2sqft also at
Jan 7, 2004
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1973
- Floors
- 4
- Residential units
- —
- Building area
- 88,300 ft²
- Lot area
- 71,040 ft²
- Zoning
- R7-2
- Community board
- 111
- Council district
- 8
- Block / lot
- 1694 / 1
- Assessed value
- $7,773,300
- Landmark / historic district
- No
Questions about 430 East 100 Street
Who owns 430 East 100 Street?
The owner of record in NYC Department of City Planning PLUTO data is Nys Urban Development Corporation.
Does 430 East 100 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 430 East 100 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 430 East 100 Street built?
City records list 1973 as the year it was built.