roofy

59 West 91 Street

Manhattan, NY 10024BBL 1-01205-0006Map

Owner of record: NYC Department Of Parks And Recreation

59 West 91 Street is a school building built in 1972 in Manhattan, 10024. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
20
ECB violations
58
HPD complaints
7

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 20

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 20, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 5, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
Show 10 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed

ECB violations · 58

  • Class - 2

    Reissue ecb #35717454k. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) auditorium emergency lights no

    Mar 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed and noted that at 1st floor auditorium two

    Apr 16, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building walls or appurtenances.observed at roof level staircase c bulkhead vertical crack along exterior brick wall andmortar joints spanning approx 5ft.remedy:maintain exterior building wa

    Feb 23, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code fc1027.4 observed throughout floors 1,2,and 3 excessiveamount of artwork and combustible paper material attached to corridor

    Feb 23, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381.observed exisitng emergency lights not operational when tested.on 2nd floor g

    Feb 23, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:observed fire proof self-closing doors not closing/opening properly.on first floor staircase b,two doors are racked.by room 134 double corridor doors not op

    Feb 23, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue 35486637h failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 note at 1st fl auditorium emergency lights not working.remedy:

    Mar 9, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner note at roof level roof leaks in various areas causing damage to ceilings below ie in gym& stairways a&c. remedy:repair and/or replace.

    Mar 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door and or hardware per bc 1008.1-8;27-371(j0 noted at auditorium at main entry door and at 3rd floor room #208 doors have kick donw door

    Apr 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits discharges and public corridors per bc 1006.1;27-381 noted at gym 3 emegrency eixt lighing auditorium has 2 and at 3rd floor 2 exit l

    Apr 15, 2020 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code copliant manner noted at roof top brick chimney w/ visible horizontal crack approx 3ft make necessary repairs

    Apr 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain buidling in code compliant manner noted at first floor onbe door @ staircase a,b and at 3rd floor one door @ stairwell do not operate properly due defectiev hardware repair/replace doors

    Apr 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner use of prohibited door hardware.fire corridor smoke doors on 1st and 2nd flr (hook & eye) auditorium door stop. rmdy: comply w/nov.

    May 20, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. use of prphibited door hardware. fire corridor smoke doors on 1st & 2nd floor (hook & eye). auditorium door stop. remedy: rmeove illegal hardware.

    Mar 28, 2014

    Resolve
  • Class - 2

    Reissue # 34921744k. interior glazed concrete block wall tiles are cracked (sharp edges) in cafeteria and at various locations of hallway. remedy: repair/replace defects.

    Feb 3, 2012

    Resolve
  • Class - 2

    Holes in wall of electrical room above door at pipe penetrations. remedy: provide/maintain fire stopping.

    Feb 3, 2012

    Resolve
  • Class - 2

    Reissue # 34921746y,34921745m. at main entry; door racked. 1st floor stwy "e" doors not closing. 2nd floor stwy "ab"&"e" doors not closing. 3rd floor stwy "e" door racked. stwy bulkhead door to roof racked. re

    Feb 3, 2012

    Resolve
  • Class - 2

    Prohibited hardware. at smoke doors 1st to 3rd flrs, installed hook & eye hardware that prohibits proper operation of fire proof self-closing doors. remedy: remove illegal hardware.

    Jul 28, 2011

    Resolve
  • Class - 2

    Sec. 27-371(b). plexi vision panels. installed plexi vision panels at various rooms 1st flr. remedy: remove thermo plastics, provide code-compliant vision panels.

    Jul 28, 2011

    Resolve
  • Class - 2

    Racked door. at main entry, the left fire proof self-closing door is racked to frame & jammed shut. remedy: repair door to properly open & self-close.

    Jul 28, 2011

    Resolve
  • Class - 2

    Broken door checks. broken door checks on fire proof self-closing doors at 1st & 2nd flr stwy e. remedy: replace door checks so doors properly self-close.

    Jul 28, 2011

    Resolve
  • Class - 2

    Reissue #34871318p. cracked glazed block. at cafeteria, cracked glazedblock at various column corners w/sharp edges. remedy: repair glazed block walls.

    Jul 28, 2011

    Resolve
  • Class - 2

    The plaster on the ceiling is spalling & cracked located at roof bulkhead a & b leaving the rebars exposed.remedy:repair and/or replace plaster on ceiling.

    Aug 13, 2010

    Resolve
  • Class - 2

    The gas meter room is lacking fresh air ventilation at the cellar level.remedy: provide fresh air ventilation in the gas meter room.

    Aug 13, 2010

    Resolve
  • Class - 2

    Reissue: 34779932n; interior glazed concrete blocks in the wall is caracked leaving sharp edges in the cafeteria at the 1st floor level. remedy:repair and/or repalce block tiles wall.

    Aug 13, 2010

    Resolve
  • Class - 2

    Reissue: 34711987j 3rd flr corridors door not closing rear 330,staircase door a","b","d". 2nd flr staircase doors near 229 roof door near staircase "a","b" south west exit door ("b") north cafeteria doors,corri

    May 21, 2009

    Resolve
  • Class - 2

    Reissue: 34711988l glazed block wall tile inside cafeteria cracked in various locations (sharp edges). remedy: repair replace wall.

    May 21, 2009

    Resolve
  • Class - 2

    Reissue 34585993l glazed block wall on north side of cafeteria still have cracks in block wall. remedy: repair/replace walls.

    Oct 21, 2008

    Resolve
  • Class - 2

    3rd flr corridor not closing near 330 door racked at staircase 'b' 2nd staircase 'c' door rack near room 228 corridors door rack near 229 roof door near 237 gym door no door check. remedy: repair/replace doors

    Oct 21, 2008

    Resolve
  • Class - 2

    Corridors on north 7 south sides with desk decreasing space in corrid or. remedy: remove all obstructions in passage way.

    Oct 21, 2008

    Resolve
  • Hazardous

    Reissue: 34513425x interior glazed block walls are cracked located inside the cafeteria on the wall adj to exit doors. remedy: repair/replace wall.

    Jul 20, 2007

    Resolve
  • Hazardous

    Reissue vi #34281696m. defect throughout interior of school hallway block walls have cracks, spalling & in cafteria. remedy: repair defectedblock.

    Apr 26, 2006

    Resolve
  • Non-hazardous

    Failure to maintain building defect noted:(1)at rooms # 312 & 304 along east wall minor seperation of ceiling from wall approx va(2)at metervertical step crack on block wall remedy:maintain building/repair as r

    Feb 13, 2004

    Resolve
  • Non-hazardous

    Exit passaceway corridors obstructed noted: 3 floor hallways have manysmall tables and chairs for kids and also requair (adults) chairs and bench. remedy: remove all obstructions from passagways.

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware defect: gymnasium (occupancy 388) has no panic hardware at rear exits. remedy; provide panic hardware.

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Painci hardware in place of assemply inoperative. defects: auditorium (occupancy 400) has inoperative panic hardware at rear exits by stage. remedy; repair replace panic hardware where required.

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defect: roof leak causing water damage in hallway near 306. remedy; maintain building repair as needed.

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defects doors do not close 3 floor stairway c 2 fllor f, a,b, 208,342, roof door by 237 1 floor c, cafeteria kitchen 2, exit f, 108 basement d and 2 doors near boiler room missing d

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defects door checks broken or missing 3 floor st airway d,f fire doors by 303/304, rooms 303,8,19,24,26,32,36,38,40. 2 floor stwy d, rooms 230,36,28,26,24,19,18,12,6,2,200 gym. 1 fl

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defect broken door stops at cafeteria (2), stariway c & a room 104, 112, 116, 117, 126 remedy : maintain building repair / repalce door stops

    Jan 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defect roof leak above hallway by room 306. remedy; maintain building repair as needed.

    Jan 24, 2003

    Resolve
  • Hazardous

    Failure to maintian - broken, defective, "missing" seat backs in auditorium location : first row seat 102 and 112. remedy : maintain building : make necessary repair remove hazard

    Feb 26, 2002

    Resolve
  • Hazardous

    Failure to maintain building exterior; defect noted : cracked, broken,liffing, sagging, separated, missing large hole in concrete paved surface at rear kindergaten playground. also noted. excessive settelment o

    Feb 26, 2002

    Resolve
  • Hazardous

    Failure to maintain - defect noted ; cracked, loose, protruding concrete block in danger of falling. location : 1st floor hallwat ( top of wall, 6' ) at roll down gate and kindergarten room # 106 remedy : maint

    Feb 26, 2002

    Resolve
  • Non-hazardous

    Exit door not self - closing - interior- location. hall / corridor andstairwell. doors ( fire ) approx. percentage of doors = 50 % remedy : repair / replace all defective fore doors make self - closing

    Feb 26, 2002

    Resolve
  • Non-hazardous

    Exit door swings against the flow of egress : location : kindergarten room 106. door with "exit" leading to playarea ( outside ) and w 91 s treet. remedy : repair and or replace exit door to proper swing

    Feb 26, 2002

    Resolve
  • Non-hazardous

    Failure to maintain building interior -, missing concrete block wall ( 5 blocks ) open fire stopping location : 2nd floor level. between rooms 238 and 240 remedy : maintain building; replace missing concrete cl

    Feb 26, 2002

    Resolve
  • Non-hazardous

    Panic hardware inoperative ; defective, missing parts. location : auditorium remedy : repair / replace panic hardware

    Feb 26, 2002

    Resolve
  • Non-hazardous

    Failire to provide hardware where required by law. location : (1) gymnasium - occupant load = 388 persons (2) cafeteria - occupant load = 400 persons remedy : provide all panic hardware where required by law

    Feb 26, 2002

    Resolve
  • Hazardous

    Failure to maintain defects are broken store steps on stair well to auditorium doorway, creating sercous tripping hazard. location: at stair b auditoriumegress. remedy: do repairs.

    Mar 5, 2001

    Resolve

Complaints

  • Door/window

    Door frame

    Jul 17, 2024 · Apt 5A

    Close
  • Door/window

    Door

    Jul 17, 2024 · Apt 5A

    Close
  • Heat/hot water

    Apartment only

    Jan 28, 2022 · Apt 3A

    Close
  • Heat/hot water

    Entire building

    Jan 11, 2019 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Feb 4, 2017 · Apt 1

    Close
  • Heating

    Heat related

    Jul 22, 2004 · Apt 1

    Close
  • Electric

    Bell-buzzer/intercom

    Mar 24, 2004 · Apt 1

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W3)
Year built
1972
Floors
3
Residential units
—
Building area
115,280 ft²
Lot area
82,575 ft²
Zoning
R7-2
Community board
107
Council district
6
Block / lot
1205 / 6
Assessed value
$25,337,700
Landmark / historic district
No

Questions about 59 West 91 Street

Who owns 59 West 91 Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 59 West 91 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 59 West 91 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 59 West 91 Street built?

City records list 1972 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.