roofy

130 East 39th Street

Manhattan, NY 10016BBL 1-00894-7505Map

Owner of record: 130 East 39 LLC

130 East 39th Street is a condominium built in 1927 in Manhattan, 10016. The owner of record is 130 East 39 LLC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
0
ECB violations
20
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 0

No DOB violations on record

ECB violations · 20

  • Class - 1

    At the time of inspection observed on the roof on the cooling tower unit a cracked valve also pipe connection made with fernco couples . mc 908.1 - cooling towers: cooling towers shall be installed in accordanc

    Aug 13, 2026 · Penalty $2,500

    Active
  • Class - 1

    Unapproved/unsafe/unsuitable electrical equipment, apparatus, materials, devices, appliances or wiring in use. observed in the main lobby and back storage area exposed bx and sj cord feeding hung heaters sj cor

    Aug 13, 2026 · Penalty $1,600

    Active
  • Class - 1

    Electrical work without a permit. observed in the basement 4 new 200 amp disconnect sw and 1 1600 amp distribution installed with bx risers. also in lobby and basement hung electric heaters installed with bx an

    Aug 13, 2026 · Penalty $2,500

    Active
  • Class - 1

    Unapproved/unsafe/unsuitable electrical equipment, apparatus, materials, devices. observed thru out hallways and children play room no installation of tamper resistant receptacles and in the mechanical rms no g

    Aug 13, 2026 · Penalty $1,600

    Active
  • Class - 1

    At the time of inspection observed throughout the building, multiple automatic sprinkler heads were observed obstructed. multiple sprinkler heads were observed with their escutcheons/caps painted and or missing

    Aug 13, 2026 · Penalty $2,500

    Active
  • Class - 1

    Class 1: 1. dlm malfunctioning and not providing required door lock monitoring. as per asme a17.1 2.12. remedy: repair dlm to restore proper monitoring. class 2: 2. car produces whistling noise while traveling.

    Aug 13, 2026 · Penalty $1,250

    Active
  • Class - 1

    Class 1 c/u: 1. compensation chain dragging on pit floor, creating hazardous interference with pit equipment. as per asme a17.1 2.2. remedy: adjust and secure compensation chain to maintain compliant floor clea

    Aug 13, 2026 · Penalty $1,250

    Active
  • Class - 2

    Class 2: missing lobby braille tags, install. emrgency phone volume too low, adjust. car operating panel key switches labels worn, provide new labels.

    Aug 12, 2025 · Penalty $625

    Resolve
  • Class - 2

    Class 2: missing lobby braille tags, install. emrgency phone volume too low, adjust. car operating panel key switches labels worn, provide new labels.

    Aug 12, 2025 · Penalty $625

    Resolve
  • Class - 2

    Class 2: missing drop ceiling in the car exposing unguarded light, install clear drop ceiling. missing device id on the car operating panel, provide. missing in-car emergency phone, install.

    Aug 12, 2025 · Penalty $625

    Resolve
Show 10 more ↓
  • Class - 1

    Failure to install grounding electrode conductor in accordance with section. observed no secondary grounding electrode. located in watermain room and throughout electrial rooms., properly install ground electro

    Aug 5, 2025 · Penalty $12,000

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed hole penetrations throughout sprinkler control valve rooms and basement

    Aug 5, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per bc 1008.1.8 (2014 code); 27-371; bc 1008.1.9 (2014 code); bc 1010.1.8 (2022 code); bc 1010.1.9 (2022 code). obse

    Aug 5, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    Door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, call or emailthe d.o.b. [email protected]. elevator division at (212) 393-2144 for a re

    Nov 26, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    I observed on the roof the failure to install the equipment ground conductor as required for permanently installed exterior equipment with the use of flexible wiring. as per ec 350.60 photos taken.; ec 350.60,

    Aug 2, 2024 · Penalty $800

    Resolve
  • Class - 1

    I observed in the electrical closets the installation of branch circuit wiring to and receptacles in the data cabinets installed in the electrical closets. no permit on file in dob records covers this work., ob

    Aug 2, 2024 · Penalty $1,600

    Resolve
  • Class - 1

    I observed in the basement water meter room the electrical service ground in a state of corrosion, the cable raceway the terminal lug and the wire were showing various states of rust. as per ec 110.11 all elect

    Aug 2, 2024 · Penalty $1,600

    Resolve
  • Class - 1

    I observed on floors# 3,6,9,12,&15 the installation of a data cabinet to supply wifi throughout the building, as per ec code 110.25 the electrical closet shall be dedicated to electrical distribution equipment

    Aug 2, 2024 · Penalty $1,200

    Resolve
  • Class - 1

    I observed in the restrooms on the 1st and 2nd floors defective gfci outlets in use. also noted no tamper resistant outlets in hallway accessible to the children and exposed, energized wiring in use in the base

    Aug 2, 2024 · Penalty $1,600

    Resolve
  • Class - 2

    Category 1 test tag expired. repair car lighting. provided elevator manuals and schematics for this device. eliminate noise when car runs between floors.

    Aug 2, 2024 · Penalty $625

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Condominium (RC)
Year built
1927
Floors
15
Residential units
—
Building area
141,803 ft²
Lot area
10,887 ft²
Zoning
R10
Community board
106
Council district
4
Block / lot
894 / 7505
Assessed value
$16,312,050
Landmark / historic district
No

Questions about 130 East 39th Street

Who owns 130 East 39th Street?

The owner of record in NYC Department of City Planning PLUTO data is 130 East 39 LLC.

Does 130 East 39th Street have violations?

NYC HPD has no housing violations on record for this property.

Is 130 East 39th Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 130 East 39th Street built?

City records list 1927 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.