32 West 29 Street
Manhattan, NY 10001BBL 1-00830-0067Map
Owner of record: 32-34 West 29th Street Realty LLC
32 West 29 Street is a hotel built in 2012 in Manhattan, 10001. The owner of record is 32-34 West 29th Street Realty LLC. HPD has recorded 12 housing violations here, most recently on May 11, 2026.
- HPD violations
- 12
- DOB violations
- 26
- ECB violations
- 36
- HPD complaints
- 10
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 12
- ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
May 11, 2026
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 17, 2025
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Jun 16, 2025
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 22, 2024
Closed — Violation dismissed - CImmediately hazardous
Provide an adequate supply of heat from an approved central heating system, or an approved system of gas or electrical heating in good operating condition for the dwelling unit located at b-room 504, 5th story, 1st b-room from west at north
Jan 31, 2024 · Apt 504
Closed — Violation closed - CImmediately hazardous
Replace or repair the self-closing doors that is missing or defective hinge in the 1st entrance from north located at b-room 504, 5th story, 1st b-room from west at north
Jan 31, 2024 · Apt 504
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 15, 2023
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 31, 2023
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 2, 2022
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 10, 2022
Closed — Violation dismissed
Show 2 more ↓
- IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Mar 10, 2022
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 20, 2021
Closed — Violation dismissed
DOB building violations · 26
- Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 11, 2024
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2024
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Oct 16, 2024
Dob violation - dismissed - No report and / or late filing (facade) facade required
Failed to file fisp cycle 9b technical report by 2/21/2023
Feb 22, 2023
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2022
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2021
Dob violation - resolved - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Apr 29, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 5, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 5, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed
Show 16 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jul 9, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 9, 2019
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 16, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 13, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 13, 2017
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 23, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 23, 2015
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 30, 2014
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 4, 2014
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Jun 4, 2014
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 4, 2013
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 4, 2013
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 4, 2013
Dob violation - dismissed
ECB violations · 36
- Class - 1
Class 1 c/u: 1. alarm bell and emergency phone inoperative, failing required emergency alerting and two-way communication. as per asme a17.1 2.27 and 2.14; condition meets class 1 c/u criteria per 1 rcny 102-01
Aug 20, 2026 · Penalty $1,250
Active - Class - 2
Class 2: 1. emergency phone inoperative; respondent unable to hear occupant in the car, failing required two-way communication. as per asme a17.1 2.27. remedy: repair emergency phone and verify clear, reliable
Aug 20, 2026 · Penalty $625
Active - Class - 1
Electrical closet not dedicated to electrical distribution equipment only. observed on the roof the electrical closet and the elevator machine room in the basement the storage of building supplies ice maker, bu
Aug 18, 2026 · Penalty $1,200
Active - Class - 2
Miscellaneous violation of the electrical code technical standards. observed on all floors thru out building that the electrical closets and mechanical closets and fire alarm closets has no lighting for repairs
Aug 18, 2026 · Penalty $800
Active - Class - 1
Atoi observed through out the building obstructed sprinkler heads and painted caps by the 04 rooms the telecom/linen closets sprinklers had the protective caps on still and painted also stuffed to the heads wit
Aug 18, 2026 · Penalty $2,500
Active - Class - 1
Atoi observed pvc piping used on the laundry room washing machine waste & on the slop sink also the basement bathroom contrary to pc 1002.1 & pc 1101.10, repair and/replace
Aug 18, 2026 · Penalty $2,500
Active - Class - 2
Class 2: door reopening device protective lenses missing, install. in-car handrail loose, secure. alarm button inoperative, repair. in-car lobby button acknoledgement light inoperative, repair. top floor access
Aug 11, 2025
Resolve - Class - 1
Class 1 cease use item: door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, email the d.o.b. [email protected]. for a reinspection.
Aug 11, 2025 · Penalty $1,250
Resolve - Class - 1
Observed in the laundry room located in the basement commercial quick disconnect on commercial laundry equipment. as per 411 of the fuel gas code only commercial cooking equipment on casters shall be connected
Aug 7, 2024 · Penalty $3,125
Resolve - Class - 2
I observed in the basement laundry room a convenience outlet not of the gfci type nor gfci protected as required within 6 ft of a sink., install gfc1 protection; provide gfci protection.
Aug 7, 2024 · Penalty $2,400
Resolve
Show 26 more ↓
- Class - 1
I observed on all floors the failure to provide tamper-resistant/ proof receptacles as required for areas accessible to children. as per ll 39/2015 this is an immediate shock hazard.; ll39/2015, comply with ec
Aug 7, 2024 · Penalty $4,000
Resolve - Class - 2
I observed in the elevator motor room the use of an extension cord to supply power to the a.c unit., also noted on the first floor mezz. from the basement to supply power for a coffee maker. no flexible cords s
Aug 7, 2024 · Penalty $800
Resolve - Class - 2
I observed in the rooftop elevator motor room the fuses in the disconnect rated higher than the conductors allowable ampacity. i noted the fusing at 150 amps for conductors rated at 110 amps. conductors and fus
Aug 7, 2024 · Penalty $2,400
Active - Class - 2
In-car alarm bell inoperative. expired brake maintenance tag. provide an updated maintenance log.
Aug 5, 2024 · Penalty $1,562
Resolve - Class - 2
Expired brake maintenance tag. provide an updated maintenance log.
Aug 5, 2024 · Penalty $1,562
Resolve - Class - 2
Work without permit.noted:at front of bulding /restaurant on sidwalk level observed new outdoor counter with roof/grill was constructed without permit,size approx.13'l x6'w x 7'h.also observed approx. 5' w x
Aug 15, 2017 · Penalty $800
Resolve - Class - 1
Sec. 3301.1.2 failure to have fire safety manager present as required.at time of inspection observed,active job site. all interior trades onsite. no fire safety manager present as required by this section of
Oct 23, 2014 · Penalty $1,600
Resolve - Class - 1
No variance-work after hours w/out variance permit contrary to 105.12.5 at time of inspection i observed an active job site w/ multiple men working on the 4th fl through 9th fls these men were mixing cement lay
Jun 28, 2014 · Penalty $800
Resolve - Class - 1
Failure to have site safety manager present as required at time of inspection i observed multiple men working on the 4th through the 9th fls of the bldg doing things such as mixing cement laying tile and carryi
Jun 28, 2014 · Penalty $2,400
Resolve - Class - 2
3310.6designated site safety mgr noted at time of inspec. of 21 story nb udner const.the current site safety mgr vicente a majistrado lic#m001361 has no pw2 on record or provided at time of inspec.last pw2 was
May 29, 2014 · Penalty $830
Resolve - Class - 2
31h11 car roller guides worn, must replace. all car roller guides.
Mar 7, 2014 · Penalty $250
Resolve - Class - 2
Sec. bc 3303.12. hoist failure to have elevator in readiness. note: active job site observed hoist being repaired at 1st flr level. bldg complete to 21 stories. hoist not in compliance w/(fdny) use in the event
Mar 3, 2014 · Penalty $800
Resolve - Class - 1
Bc3318.3. 97#05-cease use as per rs18-7 rule #261.1.2 failure to perform & file on elv 3 test/inspection for jumps to mast.rmdy: comply withrule #26 1.1.2 and file elv3 inspection reports.
Mar 3, 2014 · Penalty $1,600
Resolve - Class - 1
Bc3318.5.1 05l10,05l10,68m07. 05l10-cease use device#iv23000.car door/gate bypassed car operates w/door opened.05l10-rear gate.tom a ho()defective must repair; 68m07-maintenance log missing provide a detailed m
Mar 3, 2014 · Penalty $1,600
Resolve - Class - 2
Failure to install ground fault circuit interrupter (gfci) protection as req'd. sidewalk shed: no gfci circuit provided. remedy: install gfci protection.
Jan 16, 2014 · Penalty $2,400
Resolve - Class - 1
Unapproved/ unsafe/ unsuitable electrical equipment, apparatus, materials, devices appliances or wiring in use. sidewalk shed: romex cables used outdoor. rem: comply w/ec code.
Jan 16, 2014 · Penalty $1,600
Resolve - Class - 1
Failure to ground electrical systems. sidewalk shed: no ground provided, non current carrying electrical conductive material is not grounded. remedy: provide grounding.
Jan 16, 2014 · Penalty $4,800
Resolve - Class - 1
Failure to safeguard all persons & property affected by construction operations. at time of inspection observed adjoining property located at 30 west 29 st set back being used as a storage area for active jobsi
Sep 11, 2013 · Penalty $2,400
Resolve - Class - 1
Failure to institute/maintain safety measures - guard rails. at time of inspection observed missing &/or broken guard rail system throughoutactive jobsite. potenial for workers to fall or material & debris to
Sep 11, 2013 · Penalty $2,400
Resolve - Class - 1
Failure to safeguard all persons & property affected by construction operations. at time of inspection observed entire length of active jobsite at exposure 3 providing no overhead protection for adjoining prope
Sep 11, 2013 · Penalty $2,400
Resolve - Non-hazardous
Oac failure to obtain permit for outdoor advertising sign. remedy: remove illegal signage.
Oct 4, 2007 · Penalty $20,000
Resolve - Non-hazardous
Sec. 26-262ac. property owner acting as an oac failure to obtain validoac registration # while engaging in outdoor advertising. remedy: remove illegal signage or register as oac.
Oct 4, 2007 · Penalty $20,000
Resolve - Non-hazardous
Sec. 26-262ac. property owner acting as an oac failure to obtain validoac registration number while engaging in outdoor advertising business. remedy: remove illegal signage.
Oct 4, 2007
Resolve - Non-hazardous
Property owner acting as an outdoor advertising company failure to obtain valid oac registration # while engaging in outdoor advertising business. remedy:remove illegal signage.
Mar 22, 2007 · Penalty $10,000
Resolve - Non-hazardous
Outdoor advertising company failure to obtain permit for outdoor advertising sign. remedy:remove illegal signage.
Mar 20, 2007 · Penalty $10,000
Resolve - Non-hazardous
Outdoor advertising company failure to affix decal bearing advertising signs dates of install. remedy:remove illegal signage.
Mar 20, 2007
Resolve
Complaints
- Heat/hot water
Entire building
Feb 20, 2026 · Apt 904
Close - Heat/hot water
Entire building
Feb 7, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 21, 2025 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 30, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 18, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 18, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 18, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Jan 16, 2024 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 29, 2023 · Apt BLDG
Close - Unsanitary condition
Pests
Jun 17, 2021 · Apt 1702
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (H3)
- Year built
- 2012
- Floors
- 22
- Residential units
- —
- Building area
- 50,150 ft²
- Lot area
- 4,351 ft²
- Zoning
- M1-8A/R12
- Community board
- 105
- Council district
- 3
- Block / lot
- 830 / 67
- Assessed value
- $11,896,650
- Landmark / historic district
- No
HPD registration #144882, last renewed Dec 2, 2025.
Questions about 32 West 29 Street
Who owns 32 West 29 Street?
The owner of record in NYC Department of City Planning PLUTO data is 32-34 West 29th Street Realty LLC.
Does 32 West 29 Street have violations?
Yes. NYC HPD has recorded 12 housing violations at this property.
Is 32 West 29 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 32 West 29 Street built?
City records list 2012 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.