roofy

442 West 31 Street

Manhattan, NY 10001BBL 1-00728-0060Map

Owner of record: 450 West 31st Ownrscp

442 West 31 Street is an office building built in 1918 in Manhattan, 10001. The owner of record is 450 West 31st Ownrscp. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
127
ECB violations
54
HPD complaints
1

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 127

  • Construction other optional

    Failure to maintain building in a code compliant manner.as noted at ti me of inspection,i observed at exp1 broken window panes on 10th fl.exp 3 south elev missing brick and damaged mortar joints at 8th fl,missing brick at southeast end of parapet wall.cracks in chimney brick work.cr acks in masonry bulkhead.remedy:repair and/or replace damaged facade

    Feb 9, 2026

    Dob violation - active
  • Construction other optional

    Structure rendered non-compliant. damages sustained are due to a vehicle impacting the sidewalk shed erected at exposure# 4 removing approx. 15' of verticle and horizontal supports causing a partial collapse.

    Oct 25, 2025

    Dob violation - dismissed
  • Construction other optional

    Structure rendered non compliant at time of inspection. damage observed to have been sustained two support beams displaced and out of plumb. two sections of cross bracing bent on the left hand side of sidewalk shed due to car impact. sidewalk shed approx 60x10

    Feb 9, 2025

    Dob violation - dismissed
  • Construction other optional

    Structure rendered non compliant. due to car into sidewalk shed. the f

    Feb 9, 2025

    Dob violation - dismissed
  • Construction other optional

    Structure rendered non compliant dut to car into sidewalk shed . the following damages occurred . 2 metal columns are out plumb , cross bra cing bent of left hand side of shed . side walk is approximately 70 x 12 '

    Feb 9, 2025

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
Show 40 more ↓
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 3, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Hazardous condition (facade) facade required

    Cycle 9b unsafe report filed

    Feb 17, 2023

    Dob violation - active
  • Plumbing none

    Special inspector, alberto roman, pe surrendered all filing privileges. stop all sprinkler/standpipe work under permit # m00652166

    Aug 15, 2022

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 2, 2022

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 19, 2022

    Dob violation - dismissed
  • Construction other optional

    Emergency work order. as per condition observed at exp 2 east elev such as cracks/spalled masonry facade were observed and no public protection/safety measures were noted at exp 2 east facade. due to unsafe facade condition and unsafe facade notification. remedy: take and provide immed safety measure/public protection where required

    Nov 23, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Mar 31, 2021

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Sep 2, 2020

    Dob violation - dismissed
  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2019

    Jun 29, 2020

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Feb 19, 2020

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2020

    Dob violation - resolved
  • Immediate emergency anythingoptional

    Install approx 134 linear ft sidewalk shed along west 31 st

    Jan 8, 2020

    Dob violation - dismissed
  • Facade safety program facade required

    Fisp-facade safety program facade required

    Mar 20, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 8, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 8, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 15, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 16, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 16, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 5, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 5, 2013

    Dob violation - resolved
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 7b technical report by 08/21/2012

    Aug 30, 2013

    Dob violation - dismissed
  • Construction other optional

    Boro-comm has issued an immediate stop work order. (more)

    May 8, 2013

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 19, 2013

    Dob violation - dismissed

ECB violations · 54

  • Class - 2

    At time of inspection, upon reviewing dob now and bis system reveal ssm / ssc/ cs uses his license on designated permits x01125111 including m00986067-i1-gc not in compliance with code bc 3301.3. stop all work

    Aug 20, 2026 · Penalty $2,500

    Resolve
  • Class - 2

    At time of inspection observe sidewalk shed erected at exposure-1 observe the missing parapet panels at exposure#1 and loose panels at exposure # 1 create an unsafe condition for pedestrial and vehicle traffic

    Apr 24, 2024 · Penalty $2,400

    Resolve
  • Class - 1

    Failure to maintain building in code compliant manner. at time of inspection observed at 1st floor commercial space exit pathway obstructed by steel gate with chain & padlock in locked position creating an imme

    Apr 4, 2023 · Penalty $1,250

    Resolve
  • Class - 2

    At the time of inspection 12 stories alt building i observed suspended scaffold on roof level and workers on the platform working on facade repairs and i request the forman his dob license that designated by sp

    Oct 12, 2022 · Penalty $625

    Resolve
  • Class - 2

    At the time of inspection 12 stories alteration i observed suspended scaffold on roof level with having parapet clamps used as tie back on parapet wall above coping stone i request pe letter for parapet wall ca

    Oct 12, 2022

    Resolve
  • Class - 1

    Failure to maintain building in code complaint manner i observed in the basement by the gas meters having a futures on gas line also gas meter valves is in the celling not exposed next to the gas meter. also ga

    Jul 26, 2022 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to provide adequate safety measures to protect public from a documented unsafe facade.as noted building failed to make steps to remedy summons#35640202l issued on 01/24/2022.to provide safety measure to

    Mar 14, 2022 · Penalty $10,000

    Resolve
  • Class - 1

    Failure to provide safety measures to protect public from a documentedunsafe facade.as noted bldg failed to make steps to remedy summons #35635481r & 356352982 to provide safety measures to protect public & pro

    Jan 24, 2022

    Resolve
  • Class - 1

    Reissue ecb#35635481r issued on 10/28/2021.failure to provide adequatesafety measures such as shed netting etc where required to protect andsecrure public safety from documented unsafe facade as per 1rcny103-04

    Dec 9, 2021

    Resolve
  • Class - 1

    Failure to provide adequate safety measures,such as shed netting etc where required to protect and secure public safety from documented unsafe facade as per 1rcny 103-04.facade technical report filed as unsafe

    Oct 28, 2021 · Penalty $10,000

    Resolve
Show 40 more ↓
  • Class - 2

    Missing manual reset low water cut off-at least one must bemanual reset type. as per-mc 1007.2/asme csd1. venting material must be listed and labeled for it's intended use as per manufacturer.as per fgc-503.4.1

    Jul 6, 2021 · Penalty $625

    Resolve
  • Class - 1

    Failure to repair swarmp conditions in a timely manner.owner failed to repair "repair of cracks within the terra cotta" within time frame recommended by qewi.qewi frank caminite recommended in his technical rep

    Jan 6, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to comply with the commissioner's order contained in summons/violation#35476089r issued on 3/6/20 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01.no certificate of correcti

    Sep 21, 2020 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to safeguard all persons & property affected by construction operations noted at time of inspection i observed at facade at exposure#1 a 10ft spring pipe scaffold does not have adequate tol plates end

    Mar 6, 2020 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to safeguard all persons and property affected by construction.operations at the time of inspection noted at facade exporsure#1-10ft spring pipe scaffold does not have adequate toe plates,end caps also

    Jan 11, 2020 · Penalty $10,000

    Resolve
  • Class - 1

    Bc3314-supported scaffold does not meet d.o.b specifications.as noted supported scaffold at 10 floor to 12 floor has ripped loose debris metting.debris netting must be maintained as per d.o.b code specification

    Nov 18, 2019 · Penalty $6,250

    Resolve
  • Class - 2

    Failure to submit a required cycle 8b report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control # 801485. remedy: submit required technical

    Oct 15, 2018 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to file an acceptable cycle 7 technical report in compliance with code provisions: periodic inspection of exterior walls & appurtenances as required by article 28-302 & the dept of bldgs rules & regulat

    Jul 1, 2014 · Penalty $4,000

    Resolve
  • Class - 2

    42g11 41r11 41t07 60b07 67l10. 42g11-replace insufficent fuses. 41r11-replace emr door nhh self-closing self-locking. 41t07-provide emr signage. 60b07-provide adaquate motor rm lighting. 67l10-repair 2-way comm

    Jun 30, 2014 · Penalty $2,500

    Resolve
  • Class - 3

    56y13,41b7,100l10. 56y13-hoist machine has oil leak seal machine; 41b7provide self closing, self locking machine room door; 100l10-repair machine room access stairway, railing has broken welds and is insuffic

    Feb 7, 2014 · Penalty $500

    Resolve
  • Class - 1

    Oac sign on display w/o a permit. (yankees.com) remedy: remove illegalsign.

    Jun 25, 2012 · Penalty $10,000

    Resolve
  • Class - 1

    Oac failure to have licensed sign hanger attach or erect sign. (yankees.com) remedy: remove illegal sign.

    Jun 25, 2012

    Resolve
  • Class - 1

    Oac sign prohibited in c6-4 zone. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012 · Penalty $10,000

    Resolve
  • Class - 1

    Oac failure to have licensed sign hanger attach or erect sign. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012

    Resolve
  • Class - 1

    Oac failure to have licensed sign hanger attach ul classification markor date of sign's erection to corner of sign fabric. (yankees.com) remedy: remove illegal sign.

    Jun 25, 2012

    Resolve
  • Class - 1

    Oac failure to have licensed sign hanger attach ul classification markor date of sign's erection to corner of sign fabric. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012

    Resolve
  • Class - 1

    Property owner acting as oac failure to obtain oac registration # while engaging in the outdoor ad business. (yankees.com). remedy: remove illegal signs/register.

    Jun 25, 2012

    Resolve
  • Class - 1

    Oac failure to register sign w/i 900' of mapped arterial of lincoln tunnel. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012

    Resolve
  • Class - 1

    Oac sign on display w/o a permit. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012 · Penalty $10,000

    Resolve
  • Class - 1

    Oac sign prohibited in c6-4 zone. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012 · Penalty $10,000

    Resolve
  • Class - 1

    Oac failure to register sign w/i 900' of mapped arterial of lincoln tunnel. (yankees.com). remedy: remove illegal sign.

    Jun 25, 2012

    Resolve
  • Class - 2

    60x10.41m07.61l10.100d06.100m10.09v 60x10 repair lights in motor rm 41m07 provide missing door closure 61l10 repair main line disconnect sw.opens with main line on 100d06 properly secure handrail to motor room

    Oct 20, 2008 · Penalty $500

    Resolve
  • Hazardous

    03e10.84m07. 03 car rubbing while at top landing repair 84 provide hoitway sign for all windows in hoistway

    Feb 4, 2008 · Penalty $350

    Resolve
  • Hazardous

    41g07.41d06.43h10.51o02.58o11.55y13.56y13.09i10.13x10.84x10.38o02.38q03 41 properly fuse controller & secure capacitors on back of board 43 sheave worn 58 brake lineup dirty caked with grease replace 557 56

    Feb 4, 2008 · Penalty $350

    Resolve
  • Non-hazardous

    B4a,16,24b,32a,34a,38,50,50a,b,c,d,e.50-modular boiles missing rattling plate.50a-module flues manifolded together(manufactured approved)flue pipe required.50b-back flow preventor under ratted,btu ratting.50c-

    Apr 27, 2007 · Penalty $180

    Resolve
  • Hazardous

    Occupancy contrary to that allowed by the dob records illegal occupancy noted photo/video studio is being use as a place of assembly on the eighth floor.remedy:discontinue se.

    Oct 12, 2003 · Penalty $800

    Resolve
  • Non-hazardous

    Operation of a place of assembly contrary to the cofo or dob records when the current cofo or dob records does not allowed.note photo/videostudio is being use as a place assembly at eight floor.more that 75

    Oct 12, 2003 · Penalty $180

    Resolve
  • Non-hazardous

    54r09. 54- remove device from main line supply main line supply for elevator use only.

    Jun 20, 2000 · Penalty $350

    Resolve
  • Non-hazardous

    35i11/35o02/40o02/73t16/53i11/36i11/ 35- repair damaged sky-light; remove buckets of water from motor room. 35 clean motor room of debris. 73 provide city id tags on all devices. 53 machine room lighting. 36

    Jun 20, 2000 · Penalty $350

    Resolve
  • Non-hazardous

    37g 46q 35o 50y 74o 37g12 properly fuse controller 46q03 install rope fused front 35 002 clean motor room 50 414 seal oil leak 74002 clean car top.

    Jan 13, 1999

    Resolve
  • Non-hazardous

    Altered bldg occupied without a valid c of o. 8 thru 12 floors.alternation#304-81.remedy:obtain a valid c of o.

    Aug 28, 1995

    Resolve
  • Non-hazardous

    Failure to file a report of compliance with local law 16/84 certifying to the installation of required fire protection system. remedy: file report.

    Jul 27, 1994 · Penalty $500

    Resolve
  • Non-hazardous

    05i,18d,46t,74r. 05 west gate. 74 key by pass switch.

    Feb 25, 1994 · Penalty $200

    Resolve
  • Non-hazardous

    36d,46h,50y.

    Feb 25, 1994 · Penalty $200

    Resolve
  • Non-hazardous

    Failure to file a report of compliance with local law 16/84 certifyingto the installation of required fire protection systems. remedy:file report.

    Sep 23, 1993 · Penalty $400

    Resolve
  • Non-hazardous

    Failure to provide adequate emergency power exit lights pursuant to bec standards. failure to provide adequate emergency power exit/directional signs pursuant to bec standards. remedy:provide adequate emergen

    Sep 23, 1993 · Penalty $800

    Resolve
  • Hazardous

    05i,18b,42f

    Jul 22, 1992 · Penalty $500

    Resolve
  • Non-hazardous

    Failure to file a report of compliance with local law 16/84 certifying to the installation of required fire protection systems. remedy: file report

    Apr 25, 1992 · Penalty $500

    Resolve
  • Non-hazardous

    Failure to provide durable elevator landing signs throughout floors. failure to provide floor numbering signs throughout. failure to providestair identificat signs and/elevator identification signs throughout.

    Mar 25, 1992 · Penalty $1,500

    Resolve
  • Non-hazardous

    Failure to provide emergency power exit light. throughout floor areas (not including staircase). failure to provide emergency power to exit directional signs throughout. failure to provide adequate exit/directi

    Mar 25, 1992 · Penalty $1,500

    Resolve

Complaints

  • Heat/hot water

    Apartment only

    Dec 23, 2022 · Apt G2L

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Office building (O3)
Year built
1918
Floors
12
Residential units
—
Building area
112,146 ft²
Lot area
13,900 ft²
Zoning
C6-4
Community board
104
Council district
3
Block / lot
728 / 60
Assessed value
$8,983,800
Landmark / historic district
No

Questions about 442 West 31 Street

Who owns 442 West 31 Street?

The owner of record in NYC Department of City Planning PLUTO data is 450 West 31st Ownrscp.

Does 442 West 31 Street have violations?

NYC HPD has no housing violations on record for this property.

Is 442 West 31 Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 442 West 31 Street built?

City records list 1918 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.