488 Hudson Street
Manhattan, NY 10014BBL 1-00585-0041Map
Owner of record: NYC Department Of Education
488 Hudson Street is a school building built in 1916 in Manhattan, 10014. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 17
- ECB violations
- 91
- HPD complaints
- 2
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 17
- Construction other optional
C-construction other optional
Apr 1, 2007
Vw*-violation - work w/o permit dismissed - Construction other optional
C-construction other optional
Feb 3, 2007
Vw*-violation - work w/o permit dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
Show 7 more ↓
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Construction other optional
C-construction other optional
Mar 26, 1993
Vp*-violation unserved ecb- dismissed
ECB violations · 91
- Class - 2
Reissue ecb#35720608l failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted emergency lights not working throughout buildin
Jun 25, 2026 · Penalty $3,125
Active - Class - 2
Reissue ecb#35720607j failure to maintain building in code-compliant manner.noted main h.w.heater valve leaking in the boiler room.rem:repair and/or replace.
Jun 25, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.noted broken/cracked window glass panels in wall between classroom#400 and main corridor and above door entry to classroom#401.rem:repair and/or replace.
Jun 25, 2026 · Penalty $1,250
Active - Class - 2
Re-issue #35682924z. failure to maintain building in code-compliant manner. noted: the h.w. heater in the boiler room needs attention. it's leaking water, ponding on floor. remedy: repair/replace.
Jul 14, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35682922p. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: at t. o. i. there were several emergency lig
Jul 14, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building leak in bathroom 212,410,104 leak in wallrem:repair or replace.
Aug 29, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building water heater in boiler room valve leaking water and heater blow up hole in tanks.rem:repair and replace.
Aug 29, 2024 · Penalty $625
Active - Class - 2
Failure to maintain buiding no light work in yard and eng light not work in full building.rem:repair or replace.
Aug 29, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building window in rear of cafe room bx exit e & ftop to window broken stays open does not go up anymore.rem:repair and replace.
Aug 29, 2024 · Penalty $625
Resolve - Class - 2
Reissue #35555970h date 3/26/21.failure to maintain building wall(s) or appurtenances.at time of inspection observed at cellar level water penetration throughout cellar walls at 4th fl rm #405 water penetration
May 4, 2022 · Penalty $3,125
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code compliant manner illumination for exits exit discharges & public corridors per bc 1006.1;27-381 1st fl auditorium no emergency exit light operational when tested at time of
May 4, 2022 · Penalty $625
Resolve - Class - 2
Exit door not selfclosing properly atoi.atoi i observed that@1fl exit51exit door not selfclosing properly,@1fl auditorium 2exit door (way tocafeteria) not selfclosing properly,@3fl exit-ab 1exit door not selfcl
May 4, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances note@cellar level water penetration thruout cellar walls also@4fl rm405 water penetration thru wall on grovest side of bldg above window w/ acunit.maintain bldg e
Mar 26, 2021 · Penalty $1,250
Resolve - Class - 2
Reissue#35321736h date of issue 3/6/18 failure to maintain building incode compliant manner at cellar level bricks are deteriorating&fallingapart in some areas throughout the cellar. remedy:repair and/or replac
Apr 8, 2019
Resolve - Class - 2
28-301.1 reissue#35321733m date of issue 03.06.2018 failure to maintain bldg in code compliant manner gas fillled snow blower stored in cellar fan rm as per (fe) 303 no storage fuled equipmnet in bldg.
Apr 8, 2019
Resolve - Class - 2
Reissue#35321735x date of issue 3/6/18 failure to maintain building incode compliant manner no fire stopping per bc 712.3;27-345 at cellar level in main electrical room&tank room missing block&holes around pipe
Apr 8, 2019
Resolve - Class - 2
Failure to maintain bldg code-compliant manner:no fire stopping per bc712.3;27-345 noted:@cellar level in main electrical room & tank room missing block & holes around pipes not.fire stooped.rem:provide/maintai
Mar 6, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner noted:@cellar level bricks are deteriorating & falling apart in some area's throughout thecellar.rem:repair &/or replace.
Mar 6, 2018
Resolve - Class - 2
28-301.1 reissue #35234956y failure to maintain bldg in code-compliantmanner.gas filled snow blower stored in cellar fan rm as per fc 303 nostorage fueled equipment in bldg.rem:comply w/code.
Mar 6, 2018
Resolve - Class - 2
Reissue# 35234955m failure to maintain bldg in code-compliant manner.loose metal frame around glass panel over doors of exit e/f staircase on 4th & 3rd fl.rem:repair &/or replace.
Mar 6, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner- emergency lights not operational when tested at cellar staircase g and cafeteria exit door #4. rmdy: repair/replace lighting/comply with code.
Mar 7, 2017
Resolve - Class - 2
28-301.1 failure to maintain bldg in code compliant manner. unlawful placement of furnishings or other objects at exits that obstruct access to egress as per b206-28-301.1. numerous metal garment racks on whee
Mar 7, 2017
Resolve - Class - 2
28-301.1 failure to maintain bldg in code-compliant manner. gas fueledlawn mower stored in cellar fan room as per fc 303. no storage or por table fueled equipment in bldg. rmdy: comply with code/remove from bld
Mar 7, 2017
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. loose metal frame around glass panel over sair e/f door. rmdy: repair/replace/comply w/ code.
Mar 7, 2017
Resolve - Class - 2
Reissue# 35128640z. failure to maintain building in code compliant manner, provide required corridor width per bc1016.2; 27369. noted: obstructions, note: 5th flr corridor has numerous mobile coat racks,garbage
Jun 22, 2016
Resolve - Class - 2
Sec: 27-766. reissue# 35128638j. miscellaneous violations. noted: vision panels. note: room 411 class room corridor access door installed is missing code compliant vision panel. rem comply w/ code.
Jun 22, 2016
Resolve - Class - 2
Combustible material in corrdiors.note:@ 5th fl corridor rear room 504combustible material(signs)are hanging from light fixtures.rem:comply w/ notice of violation.
May 5, 2015
Resolve - Class - 2
Failure to maintain bldg in code-compliant;provide corridor width per bc 1016.2;27-369(partial obstruction).note:5th fl corridor has numerous mobile coat racks garbage buckets etc...throughout entire corridor.a
May 5, 2015
Resolve - Class - 2
27-371(b)reissue:35093123n.vision panles.note:room 411 classroom corridor access door installed is missing code compliant vision panel.rem:comply w/ notice of violation.
May 5, 2015
Resolve - Class - 2
Partial corridor obstruction.@ 2nd,3rd,4th & 5th fl,fire corridors reduced width to 50% w/ coat racks,cubbies,plastic bins,tables & chairs.rem:remove all items-maintain corridor width clear.
Mar 14, 2014
Resolve - Class - 2
27-371(b),missing vision panel.@ rm 411,classroom corridor acess door installed is missing code compliant vision panel.rem:provide vision panel.
Mar 14, 2014
Resolve - Class - 2
Reissue #34995732p defective steel grate.@ cellar adjacent to boiler rm(bird pit),defective cast iron glass eye vault cover w/ temp shoring.rem:replace grate or seal vault overhead.
Mar 14, 2014
Resolve - Class - 2
Excessive combustibles in fire corridor.@ corridor adjacent to "3d",wall to wall hanging paper art work @ head height.rem:remove all wall towall strings/ribbons & hanging paper.
Mar 14, 2014
Resolve - Class - 2
No fire stopping-missing.@ 3rd & 4th fl stair "e/f",wire glass panels replaced w/ thermo plastic panels to fire stairwells.rem:maintain firestopping(rating)-replace w/ code compliant panels.
Mar 14, 2014
Resolve - Class - 2
No exterior handrails.@ all entrance/exit stairs,no exterior handrailsw/ 5 risers.rem:provide handrails.
Mar 14, 2014
Resolve - Class - 2
Reissue 34897293n, 34941653n. defective grating in (bird pit) open shaftway cracks noted from underside. remedy: replace grating.
Jan 15, 2013
Resolve - Class - 3
Reissue 34941654p, 34897291j. glass missing (transomes) in corridor. remedy: replace missing glass.
Jan 15, 2013
Resolve - Class - 2
Plaster damage at 2nd flr under bathroom ceiling 3'x5' 4 flr teachers bathroom and room 401a. remedy: repair ceiling.
Jan 15, 2013
Resolve - Class - 2
Exit passageway partial obstructed at 5,4,3,2,1 flrs w/cubbies, file cabinets, coat racks, musical equipment. remedy: remove all obstructions from corridor.
Jan 15, 2013
Resolve - Class - 2
Reissue # 34897293n. grating defective at cellar boiler room adjacent vault cast iron glass eye style vault cover. remedy: repair/replace grating.
Mar 21, 2012
Resolve - Class - 2
Exit passageway obstructed with clothing racks,file cabinets,keyboard on all levels in corridors. remedy: remove obstructions.
Mar 21, 2012
Resolve - Class - 3
Reissue # 34897291j. missing glass panels throughout bldg on all levels transomes in corridors. remedy: replace glass panels.
Mar 21, 2012
Resolve - Class - 2
Fpsc door not closing properly at lunch room leading to stairway 'e' &f door racked and not closing properly. @ auditorium @ right " fire p roof self closing" (fpsc) door is not closing properly. remedy: repair
Feb 2, 2011
Resolve - Class - 3
Glass missing at corridor. above class room 307 - 3 glass missing above class room 206 - 1 glass missing. remedy: replace glass
Feb 2, 2011
Resolve - Class - 2
Partial corridor obstruction. @ 4th fl near stairwell ' e' & 'f' partially obstructed by 3 large file cabinets in corridor @ 2nd fl near stairwell ' e & f partially obstructed by 2 file cabinets in corridor. re
Feb 2, 2011
Resolve - Class - 2
Grating defective @ cellar - boiler room - adjacent vault cast iron glass eye style vault cover grating is defective and correctly supported with temp reshores. remedy: make repairs - provide r.a./ p.e. struct
Feb 2, 2011
Resolve - Class - 2
Plaster spalling from walls ceilings at stairway a&b c rooms 511 & 405 rem: repair replace plaster on walls & ceilings
Aug 14, 2010
Resolve - Class - 2
27-369 bc1020.1 5th floor stwy a&b c & d are partially blocked w/ design chairs boxes & tv carts rem: remove obstructions forthwith
May 14, 2010
Resolve - Class - 2
1st fl stwy d door racked bsmt stwy g door racked rem: repair replace doors
May 14, 2010
Resolve - Class - 2
Reissue: 34780096p 34711654l exterior brick facade has become porous &allowing rain water into the bldg causing interior damages to walls of room 511 405 stwy a&b and stwy c rem: waterproof exterior brick facad
May 14, 2010
Resolve
Complaints
- Heat/hot water
Entire building
Jan 29, 2021 · Apt BLDG
Close - Unsanitary condition
Garbage/recycling storage
Apr 6, 2016 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1916
- Floors
- 5
- Residential units
- —
- Building area
- 71,305 ft²
- Lot area
- 33,125 ft²
- Zoning
- R6
- Community board
- 102
- Council district
- 3
- Block / lot
- 585 / 41
- Assessed value
- $7,902,900
- Landmark / historic district
- Greenwich Village Historic District
Questions about 488 Hudson Street
Who owns 488 Hudson Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 488 Hudson Street have violations?
NYC HPD has no housing violations on record for this property.
Is 488 Hudson Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 488 Hudson Street built?
City records list 1916 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.