48 Stanton Street
Manhattan, NY 10002BBL 1-00422-0072Map
Owner of record: NYC Department Of Education
48 Stanton Street is a school building built in 1920 in Manhattan, 10002. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 46
- ECB violations
- 81
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 46
- Elevator annual inspection / test elevatorrequired
Violation issued to elevator - failure to file category 1 2017 inspection/test
Apr 5, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 19, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 4, 2016
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 23, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed
Show 36 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Nov 14, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 28, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 12, 2006
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 4, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 1, 2004
Dob violation - resolved - Elevator elevatorrequired
1p22335
Jun 3, 2002
Dob violation - resolved - Elevator elevatorrequired
1p22335
May 15, 2001
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Elevator elevatorrequired
1p22335
Jan 28, 1999
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 28, 1993
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 17, 1992
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 17, 1992
Vp*-violation unserved ecb- dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed
ECB violations · 81
- Class - 2
Reissue#35693259l failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:there are several penetrations in walls and ceilings of the electric meter room that need firest
Aug 6, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.noted:more than half the windows in this school are not working.some are nailed or sorowed closed.many rooms without ventilation.rem:repair/replace.
Aug 6, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:the masonry steps at exterior of exit#3 are cracked,chipped,uneven and overall deteriorating.this condition coasos a trip hazard.rem:repair/replace.
Aug 6, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:the iron fence at the building perimeter has several gates missing and is brokenor bent out of shape in many places.the missing gates allow easy acces
Aug 6, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at the concrete walkway against the building wall between exits 3 and 4,there isa collapsed sink hole.this condition presents the risk of serious inju
Aug 6, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner: no firestoppingper bc 712.3; 27-345. noted: at time of inspection, the electric meterroom has several opening at walls and ceilings that need firestopping.
Aug 13, 2025 · Penalty $1,250
Active - Class - 2
Re-issue #35688669h. failure to maintain building in code-compliant manner. there are broken and cracked steps at exit 1, 3, and 5. flaking and peeling at bulkhead f. several glass panels missing at stairwell w
Aug 13, 2025 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner. at 3 floor room311, 314, 2fl. 205, 206, 207, 209, 1fl. kitchen by 115, 114, auditorium left and 107 doors are not closing correctly. remedy: repair and/or
Sep 12, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-comliant manner: illumination forexits, exit discharges, and public corridors per bc 1006.1; 27-381. at1 floor box #1 by exit 1, cafeteria, auditorium, gym and lobby emergen
Sep 12, 2024 · Penalty $625
Resolve - Class - 2
Exit door not self-closing. observed a smoke 5 floor stair b, f, 4fl. stair d, exit 1, 3, 1fl stair c, d. exit 3, 5 door are not closing correctly. remedy: repair/replace door.
Sep 12, 2024 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Reissue #35674756z. failure to maintain building in code-compliant manner. observed at exit 1, 3, 5 broken steps cracked, stair f spalling bulkhead, all stairwells missing glass panels 8, exit 1 saddle building
Sep 12, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35657964z failure to maintain building in code-compliant manner: at time of inspection i observed that at exit 1 at main entry concrete steps cracked and damaged, also retaining wall is cracked and dama
Apr 25, 2023 · Penalty $1,562
Resolve - Class - 2
I observed workers on exp. # 1, along forsyth street dismantling the pipe scaffold, contrary to the description of work on the after hours variance permit # 1068608, obtain after hours variance
Jan 10, 2023 · Penalty $625
Resolve - Class - 2
Reissue35558079m date4.28.21 failure to maintain bldg in codecompliantmanner.atoi i observed that@exit1@st level concrete steps cracked&damaged also retaining wall cracked&damaged repair&replace.repair &or repl
May 20, 2022 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing properly atoi.@1fl main entrance (outside) 2exit doors@1fl@exit2 2exit doors not selfclosing properly atoi.@5fl stiarwayb 1exit door,@4fl stairwayd 1exit door,2fl stairwayb 1exit door
May 20, 2022 · Penalty $625
Resolve - Class - 2
Reissue#35495769y failure to maintain bldg in code compliant manner. noted: at time of inspection,i observed at exit 1 at street level concrete steps cracked & damaged also retaining wall cracked & damaged viol
Apr 28, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35415421k failure to maintain bldg in code compliant manner. noted: at time of inspection i observed at exit 1 street level concretesteps cracked/damaged also retaining wall cracked damaged need to make
May 28, 2020 · Penalty $1,562
Resolve - Class - 1
Sec. 3314.4.4 maintain supported scaffold netting. at the time of my inspection of a 5 sty bldg. i observed debris netting loose & hanging @exp#1,3,&4. fail to maintain scaffold could create a hazard & unsafe
Apr 13, 2020 · Penalty $2,500
Resolve - Class - 2
Reissue #35325055k date of issue 03/13/2018 failure to maintain building in code compliant manner. at stair 1 5th floor, 4th floor, 3 floorand stair 5th floor vertical and horizontal cracks plaster walls thro
Apr 30, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination forexits, exit discharges and public corridors per bc 1006.1; 27-381. at first floor auditorium 3place 1 light,2 place 3 lights and first floor
Apr 30, 2019
Resolve - Class - 2
Reissue #35325053r date of issue 03.13.2018 exit door not self closingat fith floor stair"a" one door and 3rd floor stair "d" one door not self closing properly at the time of inspection when tested. rmdy:repa
Apr 30, 2019
Resolve - Class - 2
Reissue #35325054a date of issue 03.13.2018 failure to maintain build ing wall(s) or appurtenances at exit 1 street level concrete steps cracked/damaged also retaining wall cracked damaged. rmdy: maintain
Apr 30, 2019
Resolve - Class - 2
Reissue 35325052p date of issue 03.13.2018 failure to maintain build ing in code compliant manner no fire stopping per bc 712.3. 27-345 at cellar no fire stopping for electrical room. rmdy: provide/maintain
Apr 30, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. use of prohibited door/and or hardware per bc 1016.2 - 27-369. at 5 floor all stair emergency doors have locking devices that require a key to operate. rmd
Mar 13, 2018
Resolve - Class - 2
Work without a permit. at cellar erected double doors with chain lock. 10' x 8' built out of combustible material(pressboard). rem: obtain required permits.
Mar 13, 2018
Resolve - Class - 2
Failure to maintain building walls or appurtenances at exit 1 street level concrete steps cracked/damaged also retaining wall cracked,damag ed. rmdy: maintain building walls and appurtenances.
Mar 13, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner. at stair 1 5th floor, 4 floor, 3 floor, and stair 5th floor vertical and horizontal cracks in plaster walls throughout also at cellar old cola hoist water
Mar 13, 2018
Resolve - Class - 2
Exit doors not self closing. exit doors not self closing at following locations 3 floor near room 309,209,cafeteria exit (2). rmdy: repair/ replace doors.
Mar 13, 2018
Resolve - Class - 2
Reissue #35253459r. failure to maintain building in code-compliant manner. no fire stopping per bc712.3; 27-345 at cellar. no fire stopping for electrical room. rem: provide and maintain fire stopping.
Mar 13, 2018
Resolve - Class - 2
Unlawful placement of furnishings, decorations or other objects at exits that obstruct access to egress on visibility thereof fc 1027.4. 1stfloor exit (3) partial obstruction of doors due ot garbage cans also a
Mar 13, 2018
Resolve - Class - 2
Reissue #35253461h. failure to maintain building in code-compliant manner. 1st floor exit (g) door is broken. exit (e) in gym area broken. rem: comply with code.
Mar 13, 2018
Resolve - Class - 2
Reissue #35253458p. exit door not self-closing. 4th floor near room #409 and 4th floor stair (a) and 3 floor stair (a). rem: repair/replace doors.
Mar 13, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j) illegal hardware includes use of rock stops,bolts and chains on fpsc doors. 5th floor,ent
Apr 24, 2017
Resolve - Class - 2
Exit door not self-closing. stairway"f" on 4th flr, door not close properyt; swing-out door in 4th floor next to room 409 is not close prop erly, stairway"a" on 4th floor not close properly, 3rd floor swing-out
Apr 24, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1: 27-381. existing emergency light are not operational when tested in electrica
Apr 24, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at 1st flr, exit "6" door closer is broken, exit "e" in gym area no door knobs. rmdy: repair and/or replace.
Apr 24, 2017
Resolve - Class - 2
Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. in cellar area, electrical storage room.there are no fire stopping on upper right side toward ceiling, there are 2
Apr 24, 2017
Resolve - Class - 2
Reissue #34980699k defective doors @ 2,3,4 flrs smoke doors adjacent to rms 209,309,409 doors are broken & secured open. remedy: replace doors.
Apr 4, 2014
Resolve - Class - 2
27-371(b) missing vision panels @ 2a,3a,4a,5a corridor exit doors missing vision panels. remedy: provide code compliant vision panels.
Apr 4, 2014
Resolve - Class - 2
Plexi vision panels @ 4th fl. thermoplastic vision panels installed all doors. remedy: provide code compliant wire glass vision panels.
Apr 4, 2014
Resolve - Class - 2
Prohibited termination gas vents terminate within 10' of grade & within 10' of windows w/gas smell entering classrooms on 2nd & 3rd flrs. remedy: comply w/code-properly terminate gas vents to parapets.
Apr 4, 2014
Resolve - Class - 2
Defective exterior concrete @ stanton st entry w/ramp, cracked-spalling-loose concrete @ base of hand/guardrails approx 5' high concrete. remedy: repair concrete masonry.
Apr 4, 2014
Resolve - Class - 2
Prohibited chain & padlock . bulkhead mesh gates installed chain & padlocks. remedy: remove prohibited hardware-chain & padlocks.
Apr 4, 2014
Resolve - Class - 2
Missing exterior handrails @ entrance/exit along stanton street & forsyth street frontages w/4 & 6 risers. remedy: replace handrails.
Apr 4, 2014
Resolve - Class - 2
Defective emergency lighting @ 1st flr auditorium, lunchrm, playrm the emergency lighting w/battery backup is not operating. remedy: repair or replace lighting.
Apr 4, 2014
Resolve - Class - 1
Exterior flashing on top of roof decorative cornice loose throughout south & south west corner,some areas are peeled up,to much play noted when minor force applied to other areas. remedy: make safe.
Jan 29, 2013
Resolve - Class - 2
Reissue #34950110l,34906835k defective doors staircase,corridor,exit vestibule doors throughout,to many to list doors hitting frame,spit doors. remedy: replace/repair doors.
Jan 29, 2013
Resolve - Class - 1
Bc 904.11. fail to provide the automatic fire extinguishing system for commercial cooking equipment. in the commercial kitchen located on the 1st floor of public school gas fired cooking equipment installed w/o
Mar 16, 2012
Resolve - Class - 2
Reissue # 34906835k. defective doors staircase 5c,4a,3a,2a,1d,e, exit vestibule doors 2,3,4,5,6, also corridor doors 4,3,2 floors near room 209,309,409, doors not closing. remedy: repair/replace defective door
Mar 14, 2012
Resolve - Class - 2
Failure to maintain east facade noted: shifting of inner bearing wall at east wall inside stair (f) from 5 fl to 1 fl causing cracks & separation between stairs & wall. remedy: provide engineers report atestin
Mar 14, 2012
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1920
- Floors
- 5
- Residential units
- —
- Building area
- 77,580 ft²
- Lot area
- 19,933 ft²
- Zoning
- C4-4A
- Community board
- 103
- Council district
- 1
- Block / lot
- 422 / 72
- Assessed value
- $3,482,100
- Landmark / historic district
- No
Questions about 48 Stanton Street
Who owns 48 Stanton Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 48 Stanton Street have violations?
NYC HPD has no housing violations on record for this property.
Is 48 Stanton Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 48 Stanton Street built?
City records list 1920 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.