150 Delancey Street
Manhattan, NY 10002BBL 1-00348-0036Map
Owner of record: Sc Delancey LLC
150 Delancey Street is a hotel built in 2011 in Manhattan, 10002. The owner of record is Sc Delancey LLC. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 33
- ECB violations
- 31
- HPD complaints
- 9
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 33
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Failure to correct swarmp conditions (facade) facade required
Cycle 9 failure to correct swarmp conditions
May 7, 2025
Dob violation - active - Hazardous condition (facade) facade required
Cycle 9b unsafe report filed
Jan 30, 2025
Dob violation - active - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Dec 11, 2024
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 26, 2024
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Nov 13, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed
Show 23 more ↓
- Low pressure boiler boiler required
Violation issued-failure to file 2019 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - No report and / or late filing (facade) facade required
Failed to file fisp cycle 9b technical report by 2/21/2023
Feb 22, 2023
Dob violation - active - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Apr 29, 2021
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 16, 2020
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Sep 2, 2020
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Jan 17, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 20, 2018
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 21, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 21, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 25, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 25, 2015
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 1, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 1, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Fail to certify class 1 none
Failure to certify correction on immediately hazardous (class 1) ecb violation
Feb 23, 2011
Dob violation - dismissed - Construction other optional
C-construction other optional
Apr 26, 2008
Dob violation - dismissed - Electric signs none
Es-electric signs none
May 29, 1990
Dob violation - dismissed
ECB violations · 31
- Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings. at time of inspection,access gained, violating conditions have been corrected; however, a ce
Sep 25, 2025 · Penalty $625
Resolve - Class - 2
Class 2 i6tem: brake maintenance tag expired. clean entire pit area.
Aug 5, 2025
Resolve - Class - 1
Class 1 item: replace fr3 2 amp hall button fuse and correct problem. class 2 items: brake maintenance tag expired. clean entire pit area.
Aug 5, 2025 · Penalty $3,125
Resolve - Class - 2
Work without permit. noted: four construction workers doing floor epoxy after hours under permit # m01081119-i1-gc without an after hours permit on sunday., obtain after hours variance; obtain an ahv for all af
Oct 6, 2024 · Penalty $1,250
Active - Class - 1
I observed the tie-offs securing the c hooks for the suspended scaffold not parallel or perpendicular to the face of the building. i noted the braided wiring located over the stairs of the elevated motor room a
Aug 9, 2024 · Penalty $5,000
Resolve - Class - 1
I observed the power supply for the suspended scaffold not properly protected as per ec requirements that flexible cords shall be protected from pinch points. i noted the cords over the edge of the parapet wall
Aug 9, 2024 · Penalty $1,600
Resolve - Class - 1
I observed on the roof the installation of the rigging system for the suspended scaffold not conforming to approved drawings. i noted tie offs and lifelines secured to stairs and the support dunnage of the gene
Aug 9, 2024 · Penalty $5,000
Resolve - Class - 1
I observed unlicensed electrical work performed on the roof area to supply power to the suspended scaffolds. no electrician on file in dob records. failure by the owner to ensure that a licensed electrician per
Aug 9, 2024 · Penalty $4,800
Resolve - Class - 1
I observed the installation of temporary power for the suspended scaffolds in place for the facade work as noted in permit # m01001730 no permit on file in dob records covers the temp wiring. the proper install
Aug 8, 2024 · Penalty $800
Resolve - Class - 1
Excessive storage of cardboard boxes, cleaning chemicals, machinery, and supplies, located inside mechanical rooms throughout cellar level. improperly storaging this material can lead to a fire hazard and or pr
Aug 8, 2024 · Penalty $2,500
Resolve
Show 21 more ↓
- Class - 2
Self-closing fire proof doors do not close and latch located throughout building., repair/replace door
Aug 8, 2024 · Penalty $625
Resolve - Class - 1
Door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, call the d.o.b. elevator division at (212) 393-2144 for a reinspection. class 2 items: miss
Aug 5, 2024 · Penalty $3,125
Resolve - Class - 1
Door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, call the d.o.b. elevator division at (212) 393-2144 for a reinspection. class 2 items: hois
Jul 25, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to submit an acceptable required cycle 9b report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control#914564.rem:submit acceptable required t
Apr 11, 2024 · Penalty $1,250
Active - Class - 1
Rope gripper defective perform necessary repair will not reset(cu).
Aug 20, 2021 · Penalty $312
Resolve - Class - 2
Governor defective banging noise as it run perform necessary.
Aug 20, 2021
Resolve - Class - 2
Failure to comply with commissioner's order to file a certificate of correction with the department of buildings.as noted at time of inspections building still has defects for summons#35466589y and 35458449m an
Sep 4, 2020 · Penalty $1,250
Resolve - Class - 1
Failure to maintain exterior building facade & appurtenances note at the time of inspection observe previously summo #35458449m has not been corrected yet as per all defective condition mention at previous summ
Jun 27, 2020 · Penalty $6,250
Active - Class - 1
Failure to maintain exterior building facade and appurenances.as notedbuilding has vertical cracking at corners throughout facade.spalled brick exposure 1:4th floor corner.step cracking or interior parapet wall
Mar 10, 2020 · Penalty $2,500
Active - Class - 1
05a10 cease use item. door restrictor has been tampered with/disabled and rendered inoperative.this is a safety device to ensure elevator passengers safety repair restrictor and contact nycdob at eir@building
Mar 27, 2017 · Penalty $1,000
Resolve - Class - 1
05a10 cease use item, door zone restrictor has been tampered (disabled or rendered inoperative. this is a safety device to ensure elevator passengers safety. repair restrictor and contact nycdob at eir@buildin
Mar 27, 2017 · Penalty $1,000
Resolve - Class - 2
Work does not conform to approved plans. noted:suspended 4 points scaffolds at 8th floor level plans section b-b not conform to approved plans. pictures dated copy of plans filed. stop all work on 4 point suspe
Dec 15, 2011
Resolve - Class - 1
(misc)bc3313.1flammable and combustible mixtures compressed gases.noted:@ time of inspection on an active construction site.forming foundation walls & footings.along with excavator & operation present @ exposur
Dec 16, 2010 · Penalty $1,600
Resolve - Class - 1
(misc)3304.4.5.placing of excavation equipment an excavation material.noted:@ time of inspection on an active construction site forming footings.excavator machine ontop of mound of excavated soil in excess of
Dec 16, 2010 · Penalty $1,600
Resolve - Class - 1
Failure to institute/maintain in safety equipment measures or temporary construction.as noted:@ time of insp @ a active construction site.workers working @ cellar level, failure to provide guardrail @ ground
Dec 11, 2010 · Penalty $2,400
Resolve - Class - 1
Failure to maintain sidewalk free from equipment as noted @ time of inspection @ a active const site concrete placement @ exp 2 foundation wall a concrete truck is blocking sidewalk in the st because of blocked
Nov 24, 2010 · Penalty $400
Resolve - Class - 2
Failure to safeguard all persons and property affected by construction operations. noted: debris from the demolition project located at 96 suffolk st has litter the property located at 98 suffolk street. const
Jun 23, 2009
Resolve - Class - 2
Sidewalk shed does not meet bldg code specification. noted: broken electrical conduit (hanging approx 2' from shed roof). remedy: comply w/code.
Nov 21, 2008 · Penalty $2,400
Resolve - Class - 2
Sidewalk shed does not meet code specifications. no lighting under shed as per code. remedy: conform to specs for shed.
Oct 30, 2008 · Penalty $2,400
Resolve - Class - 2
Sidewalk shed does not meet bldg code specification. noted: broken electrical conduit (having approx 2' down from shed roof) remedy: comply with code.
Oct 22, 2008 · Penalty $2,400
Resolve - Non-hazardous
27-1021(b) shed does not meet code. upon inspection shed has been installed with const fence sealed to underside of shed leaving 2' openingsthough out demo site. remedy: provide protection as per code.
Apr 23, 2008 · Penalty $2,000
Resolve
Complaints
- Heat/hot water
Entire building
Dec 22, 2025 · Apt 214
Close - Heat/hot water
Entire building
Dec 24, 2024 · Apt BLDG
Close - Water leak
Heavy flow
Feb 8, 2022 · Apt 414BTH
Close - Heat/hot water
Entire building
Dec 27, 2021 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 3, 2020 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 18, 2019 · Apt BLDG
Close - Heat/hot water
Entire building
Nov 17, 2019 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 5, 2018 · Apt 311
Close - Unsanitary condition
Garbage/recycling storage
Jan 17, 2018 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (H3)
- Year built
- 2011
- Floors
- 8
- Residential units
- —
- Building area
- 48,002 ft²
- Lot area
- 6,825 ft²
- Zoning
- C6-2A
- Community board
- 103
- Council district
- 1
- Block / lot
- 348 / 36
- Assessed value
- $7,063,200
- Landmark / historic district
- No
Questions about 150 Delancey Street
Who owns 150 Delancey Street?
The owner of record in NYC Department of City Planning PLUTO data is Sc Delancey LLC.
Does 150 Delancey Street have violations?
NYC HPD has no housing violations on record for this property.
Is 150 Delancey Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 150 Delancey Street built?
City records list 2011 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.