259 Madison Street
Manhattan, NY 10002BBL 1-00269-0041Map
Owner of record: NYC Department Of Education
259 Madison Street is a school building built in 1966 in Manhattan, 10002. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 35
- ECB violations
- 72
- HPD complaints
- 4
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 35
- Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 - multiple years (2020)
Jun 20, 2021
Dob violation - dismissed - Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2019
Jun 29, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 14, 2019
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 21, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 24, 2014
Dob violation - resolved
Show 25 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Sep 25, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 25, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 27, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 31, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 22, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 15, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Oct 1, 2005
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 23, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 20, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 2001
Dob violation - dismissed - Elevator elevatorrequired
3p2658
Mar 7, 2001
Dob violation - resolved - Elevator elevatorrequired
1s3828
Jun 20, 2000
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 6, 1998
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
May 31, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed - Elevator elevatorrequired
51)sw elev 3828 restore to service (rei)supercades violation #10/31/86-e 1385-3-1
Feb 28, 1989
Dob violation - resolved
ECB violations · 72
- Class - 2
Reissue#35724611k failure to maintain building in code compliant manner.noted:there are cracks at exterior facade.exit#2 and 5 and flaking of masonry was noticed.rem:repair/replace.
Jul 8, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.noted:the ceiling in the gym is leaking whenever it rains.damage to ceiling and gym floor.also effects activities in the gym.rem:repair leak/repair damage.
Jul 8, 2026 · Penalty $1,250
Active - Class - 2
Re-issue #35684816k. failure to maintain building in code-compliant manner. noted: at various locations exit 5, 2, exp. 1 and 3 cracks and flaking need repair. remedy: repair/replace.
Aug 28, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35684815z. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors as per bc 1006.1; 27-381. em. exit lights at gym and cafeteria were not o
Aug 28, 2025 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted at 1st fl gymnasium 2 emergency lights & at cellar cafeteria 7 emergen
Aug 27, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building wall(s)or appurtenances facade defects noted at exit#5 vertical crack approx.8 ft above doors.exit#2 step crackat ground level south elevation.at exp#1 & 3(front & rear)spalling con
Aug 27, 2024 · Penalty $1,250
Active - Class - 2
Reissue#35657704m failure to maintain building in code-compliant manner:illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.at time of inspection i observed exiting emergency light
Apr 5, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination for exits exit discharges & public corridors per bc 1006.1; 27-381.noted:observed existing emergency lights throughout 1st floor corridors stai
May 3, 2022 · Penalty $625
Resolve - Class - 2
28-118.1 building or open lot occupied w/o a valid c of o. noted:observed a four(4) story bldg occupied as a public school(m056) under a temporary certificate of occupancy(t.c.o)#67873-te that has expired on 11
May 3, 2022 · Penalty $1,250
Resolve - Class - 2
Restore to service so a full inspection can be made by this department.
Oct 14, 2021 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Sec. 28-301.1 failure to provide natural or mechanical ventilation to occupied spaces per mc 401.2. note: at cellar level storage of gas equipment 2 gas blowers 1 weed wacker & gas can. remedy: comply w/violati
May 28, 2020 · Penalty $1,250
Resolve - Class - 2
Reissue#35415532n failure to maintain bldg code compliant manner illumination for ecxits,exit discharges & public corridors per bc 1006.1;27-387. note: at 1st fl auditorium emerhgency lights on both side wall
May 28, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35415530j failure to maintain bldg in code compliant manner. note: at main entrance stair treads chipped & damage causing a trippinghazard. remedy: repair & or replace.
May 28, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. use of prohibited door & or hardware per bc 1008.1.8;27-371(j). note: thhe following doorhave illegal kick stops installed: room 436,429,427,428,423,417,415,
May 28, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self-closing.noted:exit-b1,exit6 on the first floor the doors are not closing properly.rem:repair /replace doors.
Apr 16, 2019
Resolve - Class - 2
Re-issue #35330974h failure to maintain building in code compliant manner. noted: main entrance stairs treads chipped and damage. remedy: repair and or replace
Apr 16, 2019
Resolve - Class - 2
Re-issue#35333132j. failure to maintain building in code compliant manner. noted: at fourth floor stair c landing buckled flooring; creatinga tripping hazard. remedy: repair and/or replace
Apr 16, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. noted:in the auditorium 6 of the emergency lights were not working when tes
Apr 16, 2019
Resolve - Class - 2
Exit doors not self closing 3 floor near room 334 cross over corridorsmoke door broken/missing door check. rmdy: repair/replace door.
Mar 2, 2018
Resolve - Class - 2
Reissue #35207298h. failure to maintain building in code-compliant manner. main entrance stair treads chipped, damaged and broken. rem: repair/replace.
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code-complaint mannner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371. at library(3) dead bolts locks mounted to (3) doors. as per chapter(10) 2014 code no fixed
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner.at exit #2-4'x8'glass panel in exit door is loose.moves when touched.rem:repair/replace
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. at gymnasium ceiling loose damaged hvac vent risk of falling. rem: repair/replace.
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. outside of cafeteria, light cage loose/hanging. rem: repair/replace.
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: main entrance stairs treads chipped, damaged and broken. rem: repair/replace.
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner at 4 floor landing stair (c) buckleted flooring materials creating tripping hazard also at 1st floor exit (2) 4x8' glass panel door/glass panel is loose whe
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner. at basement steam room ceiling lights not operational. rmdy: repair/replace.
Mar 2, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner.at 4th floor stair landing buckled flooring materials creating potential tripping hazard.rem:repair/replace
Mar 2, 2018
Resolve - Class - 1
Failure to maintain bldg walls or appurtenances reissue#35148363h.noted on the 3rd level fl exterior wall outside rm 319 below the window sill,bricks are cracked & loose.rem maintain exterior bldg
Nov 27, 2015
Resolve - Class - 3
Failure to maintain building in code compliant manner. noted: in the gymnasium the ceiling tiles are water damaged in various locations. rmdy: comply with nov.
Oct 7, 2015
Resolve - Class - 2
Reissue 35093376l exit door not self-closing. noted: at 24d floor smoke doors not self closing adjacent to room 317 an dexit 6 vestibule door. closer broken. rmdy: comply with nov.
Oct 7, 2015
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances. noted: in the gymnasium water is penetrating the roof at various locations. rmdy: comply w/nov.
Oct 7, 2015
Resolve - Class - 1
Failure to maintain building wall(s) or appurtenances. noted: on the the 3rd flr exterior wall (outside room 319) below the window sill bricks are crackeda nd loose. exterior wall is adjacent exit and yard on
Oct 7, 2015
Resolve - Class - 2
Partial corridor obstruction. adjacent to 3rd floor stair "c", 6' tall (paper) combustible free standing art work on display in center of fire corridor. remedy: remove excessive combustible art from corridor.
Mar 19, 2014
Resolve - Class - 2
Re-issue # 34987590z. prohibited hardware. at 4th floor, the smoke doors have kick stops installed preventing doors from operating properly. remedy: remove prohibited hardware.
Mar 19, 2014
Resolve - Class - 2
Re-issue # 34987589l. exit doors not self closing. at 3rd & 4th floors, smoke doors not self closing with broken closers. remedy: replace door closers.
Mar 19, 2014
Resolve - Class - 2
Reissue 34953854h. defective door 3rd flr corridor door near room 317b,exit 6 vestibule door. doors not closing properly. remedy: repair/replace doors.
Jan 14, 2013
Resolve - Class - 2
Illegal hardware at 4th flr corridor doors. door stops in place holding doors open. remedy: remove hardware.
Jan 14, 2013
Resolve - Class - 2
Reissue 34953853x. exit signs are obstructed on 4th flr. multiple banners hanging & blocking all exit signs on 4th flr. remedy: remove forthwith!
Jan 14, 2013
Resolve - Class - 2
Sec. 27-369 exit sign obstruction on 4th fl & 3rd fl corridors,banners,paper hanging across ceiling obstructing exit signs to staircases. remedy: remove obstructions.
Apr 23, 2012
Resolve - Class - 2
Defective doors at 3 fl corridor door near room 317b,also 2fl stair c ,& exit 6 vestibule door. doors not closing properly. remedy: repair/replace doors.
Apr 23, 2012
Resolve - Class - 2
Defective drop ceiling.at cafeteria,corner drop ceiling approx 16'x18'adjacent to stairway d,the drop section has broken,bent,loose,& missing perferated metal panels througout.remedy:repair drop ceiling.
Feb 23, 2011
Resolve - Class - 2
Defective protective guard rail. at clinton street side,2nd story setback above street exit at stairway c,the chain link protective guard rail has been bent & is leaning toward roof side.rem:repair protective g
Feb 23, 2011
Resolve - Class - 2
Defective or missing stair identification per bc 1019.7/27-393.stairway identification & floor numbering are missing inside and/or out @ allstairways and all floors.remedy:provide proper stair & floor identific
Feb 23, 2011
Resolve - Class - 2
No fire stopping per bc 712.3/27-345. fire stopping missing around electric conduit at 4th floor room 431,room 413, and room 401.remedy: provide fire stopping.
Feb 23, 2011
Resolve - Class - 2
Illegal hardware on 4fl corridor doors noted:holiday door open foot peg/door stop. remedy:remove hardware keep doors shut.
Jun 24, 2009
Resolve - Class - 3
Missing corridor door on 4fl near room 419. remedy:replace door.
Jun 24, 2009
Resolve - Class - 3
Missing corridor door on 4floor near room 419. remedy:replace door.
Nov 17, 2008
Resolve - Class - 2
Illegal hardware on roof access doors key cylinder in place on all doors.also on all floors door stops (foot peg) holding corridor doors open. remedy:remove illegal hardware.
Nov 17, 2008
Resolve - Non-hazardous
83x10,85bb05.
Dec 5, 2007
Resolve
Complaints
- Electric
Power outage
Jan 18, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Dec 9, 2020 · Apt BLDG
Close - Heat/hot water
Entire building
Mar 11, 2020 · Apt BLDG
Close - Heating
Heat related
Jan 14, 2004 · Apt BLDG
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1966
- Floors
- 4
- Residential units
- —
- Building area
- 184,328 ft²
- Lot area
- 93,564 ft²
- Zoning
- R7-2
- Community board
- 103
- Council district
- 1
- Block / lot
- 269 / 41
- Assessed value
- $23,134,500
- Landmark / historic district
- No
Questions about 259 Madison Street
Who owns 259 Madison Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 259 Madison Street have violations?
NYC HPD has no housing violations on record for this property.
Is 259 Madison Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 259 Madison Street built?
City records list 1966 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.