90 Trinity Place
Manhattan, NY 10006BBL 1-00051-0015Map
Owner of record: 90-100 Trinity Owner LLC
90 Trinity Place is a school building built in 1973 in Manhattan, 10006. The owner of record is 90-100 Trinity Owner LLC. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 96
- ECB violations
- 63
- HPD complaints
- 0
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 96
- No report and / or late filing (facade) facade required
Failed to file fisp cycle 9c technical report by 2/21/2024
Feb 22, 2024
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 10, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 5, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 5, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 5, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 5, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed
Show 40 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2019
Dob violation - resolved - Elevator elevatorrequired
Cease use
Feb 6, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 16, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 16, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 16, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 16, 2018
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2017
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 2, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 28, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 28, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 28, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 30, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 30, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 6, 2014
Dob violation - resolved - No report and / or late filing (facade) facade required
Failed to file fisp cycle 7c technical report by 02/21/2013
Dec 31, 2013
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 1, 2013
Dob violation - resolved
ECB violations · 63
- Class - 2
Failure to submit an acceptable required cycle 9c report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control #900150. remedy: submit acceptable requ
Apr 8, 2025 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed at roof level,mechanical room has 2 exit signs that are defec
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35675083h-failure to maintain building in code-compliant manner.noted:observed at roof level,chiller pipe line has a leak that is non-stop and creating puddles of water at various location.rem:repair an
Sep 19, 2024 · Penalty $1,562
Resolve - Class - 2
Emergency signs at elevator call stations missing,defective or non-compliant with section requirements.noted:observed at 6 flr,5 flr,4 flr,3flr and 2 flr.the signage that is required to be installed is no longe
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed at exp.1,ground floor glass panel(store front)on the far right by thames st has a possible bullet hole approx.2 ft from the ground that has t
Sep 19, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35675080m-failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:observed at cellar level,electrical meter room has several pipes that are penetrating through th
Sep 19, 2024 · Penalty $3,125
Resolve - Class - 2
Reissue#35657969h 5/26/22 failure to maintain building in code-compliant manner.no firestopping per bc 12.3:27-345.noted:observed during inspection of cellar level electrical room,firestopping missing around pi
May 25, 2023 · Penalty $3,125
Resolve - Class - 2
Reissue#35657970p 5/26/22 failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors.noted:observed during inspection of emergency exit lights at 13 fl lib
May 25, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35657968x 5/26/22 failure to maintain building in code-compliant manner.noted:observed at time of inspection by rm 815,electrical box loose/detached from wall under water fountain.rem:repair and/or repl
May 25, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:observed during inspection of roof level at 15th floor,railing detached/loose and below 40 inches all throughout.rem:repair and/or replace.
May 25, 2023 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner.noted:observed during inspection of roof top chiller broken pipe under chiller pouringout water non stop.also water heater at 15th floor has a broken pipe t
May 25, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:observed during inspection of fireproof self closing doors.doors at location 1017 and 317,were not operational/closing due to racking.rem:repair and/o
May 25, 2023 · Penalty $625
Resolve - Class - 1
Out of service. upon inspection, the device is found to be out-of-service. remedy: restore to service immediately and, notify nycdob the device has been returned to service. e-mail [email protected] so an i
May 31, 2022 · Penalty $1,250
Resolve - Class - 1
Provide motor room light guards., repair in-car emergency phone., provide in-case of fire sign (basement)., provide current brake maintenance tag (missing)., provide counter weight anti-spin., cease use item :
May 31, 2022 · Penalty $1,250
Resolve - Class - 2
Repair in- car emergency phone., provide brake maintenance tag (missing)., provied counter weight anti-spin., repair pit light.
May 31, 2022 · Penalty $625
Resolve - Class - 2
Repair in-cr emergency phone., provide current brake maintenace tag (missing)., shorten hoist ropes., provide counter weight anti-spin., repai pit light.
May 31, 2022 · Penalty $655
Resolve - Class - 2
Reissue#35553992j issued on 5/4/2021.failure to maintain building in code compliant manner.no fire stopping per bc712.3;27-345.at the time of inspection,i observed that at cellar level electrical room,holes in
May 26, 2022 · Penalty $3,125
Resolve - Class - 2
Reissue#35553993l issued on 5/4/2021.failure to maintain building in code compliant manner.at room 815 exposed box electrical wirre and outlets in contact with metal.water plumbing risk of unintentional contact
May 26, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1;27-381.at the time of inspection,i observed that at 13th floor 2 emergency exit sign
May 26, 2022 · Penalty $625
Resolve - Class - 2
Reissue#35496093h failure to provide adequate fire stopping at cellar electrical room at the of inspection. noted: areas around pipe penetration & mechanical parations no adequate fire stopping. remedy: comply
May 4, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to maintain bldg in code compliant mannerat hallway drinking oundations near room #1015 & 815 exposed bx electrical wire & outlets in contact w/metal water piping/plumbing risk of unintentional contact
May 4, 2021 · Penalty $625
Resolve - Class - 1
Sec. 28-104.7.1 misc violation at time of inspection. noted: at cellargas meter room-storage of 2 gas fueled snow blowers & 1 gas fuled lawnmower also 2 containers of gasoline each approx 2 gallons. no storage
May 4, 2021 · Penalty $2,500
Resolve - Class - 2
Reissue #35442175h failure to maintain building in code compliant manner no fire stoppping per bc 712.3;27-345 noted at time of inspection i observed at cellar level at electrical room electrical conduits pene
Jun 1, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner; no fire stopping bc 712.3; 27-345. noted: observed @cellar's electrical room, electrical conduits penetrating through cmu wall, also openings in conduit
Jul 5, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, discharges and public corridors per bc1006.1; 27-381 in 9th floor exit "b" one exit sign and 4th floor exit "b" one exit sign exist
May 1, 2018
Resolve - Class - 2
Reissue #35216850r, date of issue 10/31/2016. failure to maintain building in code-compliant manner. no fire-stopping per bc712.3; 27-345. cellar mechanical/electric room, no fire stopping in sheetrock wall to
May 1, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner.water accumulated on cellar electrical room floor near electrical panels.rem:repair replace.
Aug 31, 2017 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code compliant manner.unsecured electric outlets and exposed bx wire#under drinking fountains 10flr near rm#1015 and 8flr near room.#815.(risk of contact to live electicity)rem:
Aug 31, 2017 · Penalty $2,500
Active - Class - 2
Reissue #35216850r failure to maintain bldg in code compliant manner no fire stopping per bc 712.3 27-345 no fire stopping at cellar mechanical room. rmdy: provide maintain fire stopping.
Aug 31, 2017 · Penalty $2,500
Resolve - Class - 2
Reissue# 35128087m. failure to maintain bldg in code compliant manner: @ cellar mechanical/electric room no fire stopping in sheetrock wall to concealed space behind & pipe penetration in cmu block wall. rem: p
Oct 31, 2016
Resolve - Class - 2
Reiusse:34907613j.failure to maintain bldg walls or appurtenances.note:@roof level approx 5' x 5' sheet metal shaft cover is missing mounting bolts & is not fully secured.rem:comply w/notice of vio.
Apr 13, 2015 · Penalty $620
Resolve - Class - 2
Reissue:35107798x.emergency signs @ elevator call stations missing,defective or non-compliant w/ section requirements.note:@ 12th & 8th fl emergency signs are missing.rem:comply w/ notice of violation.
Apr 13, 2015
Resolve - Class - 2
Reissue:35107797y.failure to maintain bldg in code-compliant manner:nofile stopping per bc 712.3;27-345 note:@ cellar level electrical room holes in sheetrock wall to concealed space.rem:comply w/ notice of vio
Apr 13, 2015
Resolve - Class - 2
Exit door not selfclosing.note:stwy a door is racked @ 12,10,7 & 4th fl.also note:2nd fl room 206(p/a space)lecture room has door stops installed @ bottom of doors not self-closing.1st fl exit stwy a door to st
Apr 13, 2015
Resolve - Class - 2
Failure to file an acceptable cycle 7 technical report in compliance with code provisions: periodic inspection of exterior walls & appurtenances as required by article 28-302 & the dept of bldgs rules & regulat
Dec 12, 2014 · Penalty $800
Resolve - Class - 2
Reissue #34996153p missing fire stopping. at celalr electric room, no fire stopping in sheetrock wall to concealed space behind and penetra tion in cmu block wall to adjacent sprinkler room. rmdy:provide/mainta
Aug 8, 2014
Resolve - Class - 2
Reissue #34996149m missing emergency sign at elevator call station. at 8th flr and 12th flr. rmdy: provide-post emergency sign.
Aug 8, 2014
Resolve - Class - 2
Reissue #34907612h defective door. at 14th flr stwy a, door racked andnot closing properly. remedy: repair door.
Jan 11, 2013
Resolve - Class - 2
Missing signage at 8th flr and 12th flr, no emergency signs at elevator call stations - missing. remedy: replace missing signs.
Jan 11, 2013
Resolve - Class - 2
Missing fire stopping. at electric sevice room, no fire stop at wall penetrations to concealed space in wall. remedy: provide fire stopping
Jan 11, 2013
Resolve - Class - 2
Reissue # 34907612h. defective doors noted: most staircase (a) doors not closing properly hitting frame. remedy: repair/replace defective doors.
Mar 21, 2012
Resolve - Class - 2
Racked doors the fire proof self closing doors are racked and not self closing properly at 14th floor stairway a cellar lvl stairway a rem: repair doors to properly self close
Apr 6, 2011
Resolve - Class - 2
Failure to maintain building walls or appurtenances. noted: at roof level,approx 5'x 5' sheet metal shaft cover has missing mounting blots & partly secured with wire & may become totally displaced in high wind.
Apr 6, 2011 · Penalty $500
Active - Class - 3
Missing handrail at stairway a from the 5fl to 6fl staircase hand railis missing on cmu block wall rem: replace missing handrail
Apr 6, 2011
Resolve - Class - 2
Construction
Jan 27, 2010 · Penalty $800
Active - Class - 2
2nd flr stwy "a" and cellar stwy "a" door missing door check. remedy: repair/replace doors.
Jan 12, 2010
Resolve - Class - 2
Gym at cellar level tiles missing and some in danger of falling. remedy: repair/replace ceiling tiles.
Jan 12, 2010
Resolve - Class - 2
Gas meter room (closet) is being used to store boxes, fire extinguishers and wood. remedy: remove storage items from gas meter room.
Jan 12, 2010
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. 1)access panel (appx 3' x 3') missing hardware. rm 309 (onto roof) front of rm. remedy: obtain hardware-maintain bldg in code compliant manner.
Jun 12, 2009
Resolve - Non-hazardous
Failure to maintain- interior. gym fl-basement-wooden floor buckled and warped. remedy- repair/replace floor.
Aug 1, 2007
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1973
- Floors
- 15
- Residential units
- —
- Building area
- 83,362 ft²
- Lot area
- 5,882 ft²
- Zoning
- C5-5
- Community board
- 101
- Council district
- 1
- Block / lot
- 51 / 15
- Assessed value
- $7,175,700
- Landmark / historic district
- No
Questions about 90 Trinity Place
Who owns 90 Trinity Place?
The owner of record in NYC Department of City Planning PLUTO data is 90-100 Trinity Owner LLC.
Does 90 Trinity Place have violations?
NYC HPD has no housing violations on record for this property.
Is 90 Trinity Place rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 90 Trinity Place built?
City records list 1973 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.