roofy

52 William Street

Manhattan, NY 10005BBL 1-00040-0016Map

Owner of record: 52 William Street Propco LLC

52 William Street is a hotel built in 1902 in Manhattan, 10005. The owner of record is 52 William Street Propco LLC. HPD has recorded 12 housing violations here, most recently on November 17, 2025.

HPD violations
12
DOB violations
110
ECB violations
51
HPD complaints
19

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
Last violation Nov 17, 2025

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 12

  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Nov 17, 2025

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective hinges at fire door leading to fire command center at south at public hall, 1st story

    Jun 6, 2025

    Closed — Violation closed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Jun 4, 2025

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Mar 16, 2023

    Closed — Violation dismissed
  • A

    § 329, m/d law and dept. rules and regs. provide a completed certificate of inspection visits in a proper frame at or near mailboxes, bottom edge of frame between 48-62 inches above floor sign missing at public hall, 1st story

    Sep 28, 2021

    Closed — Violation dismissed
  • A

    Post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building. at public hall, 1st story

    Sep 28, 2021

    Closed — Violation dismissed
  • A

    Post and maintain a proper notice on wall of the entrance story in english and spanish on the availability of the agencys housing information guide. a sample notice can be found at www.nyc.gov/hpd.

    Sep 28, 2021

    Closed — Violation dismissed
  • A

    Post, in a form approved by the commissioner, and maintain a notice in a common area of the building regarding the procedures that should be followed when a gas leak is suspected

    Sep 28, 2021

    Closed — Violation dismissed
  • A

    File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.

    Apr 2, 2021

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 10, 2018

    Closed — Violation dismissed
Show 2 more ↓
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Oct 2, 2015

    Closed — Violation dismissed
  • I

    And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.

    Feb 3, 2015

    Closed — Violation dismissed

DOB building violations · 110

  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 2, 2024

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2023

    Dob violation - dismissed
  • Hazardous condition (facade) facade required

    Cycle 9b unsafe report filed

    Apr 21, 2023

    Dob violation - active
  • Immediate emergency anythingoptional

    Provide sidewalk shed with a total of 220 linear feet including 100lf at exp#1 - west elevation9william street) and 120lf at ex#2 -north ele vation(pine street) to protect public from hazardous conditions existi ng on the building facade

    Apr 13, 2023

    Dob violation - dismissed
  • No report and / or late filing (facade) facade required

    Failed to file fisp cycle 9b technical report by 2/21/2023

    Feb 22, 2023

    Dob violation - dismissed
  • Construction other optional

    Emergency work order due to failure to provide public safety measure (note:professional filed unsafe notification#900128 filed on 4/3/23) as of today 4/11/23,no safety measures observed as required by qewi on expsure#1 west elevation and exposure#2 north elevation.immediately in install sidewalk shed

    Jan 11, 2023

    Dob violation - active
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jun 2, 2022

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2021

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Apr 29, 2021

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - resolved
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 4, 2021

    Dob violation - resolved
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jan 6, 2021

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Nov 2, 2020

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 2, 2020

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2020

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 12, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 12, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Aug 3, 2019

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 2, 2019

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 29, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 29, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 30, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    May 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2016

    Dob violation - resolved

ECB violations · 51

  • Class - 2

    Class 2 rts: failure to maintain building in code compliant manner. upon inspection, the device is found to be out of service. remedy: restore to service.

    Aug 19, 2026 · Penalty $1,562

    Active
  • Class - 2

    Class 2: restore to service

    Aug 14, 2025 · Penalty $312

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner. observed exposed electrical without cover., repair and/replace

    Aug 11, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observed holes penetration at mechanical throughout the building. potential fire

    Aug 11, 2025 · Penalty $2,500

    Resolve
  • Class - 1

    Class 1. return to service. : failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a ha

    Jun 30, 2025 · Penalty $625

    Active
  • Class - 1

    Class 1. return to service. : failure to maintain building in code compliant manner. service elevator equipment as per bc3001.2 & 27-987. upon inspection, the device is found to be out of service, creating a ha

    Jun 30, 2025 · Penalty $625

    Active
  • Class - 2

    Electrical & gas meter menchanical room door does not self-close located at cellar level and throughout building., repair/replace door

    Jul 31, 2024

    Resolve
  • Class - 2

    Open holes, hole penetration, and removed fire-stopping found throughout building and mechanical rooms., provide/maintain fire stopping

    Jul 31, 2024 · Penalty $625

    Resolve
  • Class - 2

    Observed in the sub cellar active water leak on valve on steak piping, also storage tank that is housed in the sub cellar has a hole that is now leaking water. as per 102.3 of the pc maintenance. installations,

    Jul 31, 2024 · Penalty $625

    Resolve
  • Class - 2

    Walls erected/installed obstructing/blocking pathways and emergency exits located #1 floor prep and service area including commercial space exits, ground floor level., provide proper corridor width

    Jul 31, 2024

    Resolve
Show 40 more ↓
  • Class - 2

    I observed in the boiler room and the garbage area outside of the main electrical room the shut off switch for the electric fan., secure/support per ec; terminate conductors and devices properly.

    Jul 31, 2024 · Penalty $800

    Resolve
  • Class - 1

    I observed on all floors the failure to install tamper resistant/proof outlets in the halls as required in ll 39/2015. this is an immediate shock hazard., repair and/replace; make tamper-resistant/ proof.

    Jul 31, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Observed on the 2nd floor office and the 3rd floor hallway concealed sprinkler head is being obstructed by ceiling. also throughout building concealed sprinkler head escutcheons are missing., repair and/or repl

    Jul 31, 2024

    Resolve
  • Class - 2

    Improper storage underneath metal staircase located at cellar level., repair and/or replace

    Jul 31, 2024

    Resolve
  • Class - 2

    Emergency lighting is missing throughout building., repair and/or replace lighting

    Jul 31, 2024

    Resolve
  • Class - 2

    Observed excessive storage in the gas meter room located in the sub cellar. as per e3 of the fgc gas meter rooms, when provided, shall at all times be kept clear of all rubbish; and shall not be used in any way

    Jul 31, 2024

    Resolve
  • Class - 1

    I observed on the roof the generator in the beginning stages of corrosion as per ec 110.11 all electrical equipment shall be protected against deteriorating agents. this is an immediate hazard as this is part o

    Jul 31, 2024 · Penalty $1,600

    Resolve
  • Class - 2

    I observed on the roof multiple disconnect switches with no equipment ground conductor installed as required when the use of flexible raceways and for permanent equipment installed., comply with ec; install equ

    Jul 31, 2024 · Penalty $800

    Resolve
  • Class - 1

    I observed the installation of transformers, raceways and wiring for the installation of new elevators. no permit on file for this scope of work. permit #m01001751 is for elevator devices only and does not cove

    Jul 31, 2024 · Penalty $1,600

    Resolve
  • Class - 2

    I observed on the roof, the 5th roof, and in the subcellar boiler room, the failure to provide/ install gfci protection as required for outdoor locations and within 6 feet of a sink. photos taken., install gfc1

    Jul 31, 2024 · Penalty $1,200

    Resolve
  • Class - 1

    Door zone restrictor inoperative. this is a safety feature which ensures passenger safety. remedy: to restore service, call the d.o.b. elevator division at (212) 393-2144 for a reinspection. class 2 items: adju

    Jul 30, 2024 · Penalty $1,250

    Resolve
  • Class - 1

    Class 1 c/u door zone restrictor bypassed. provide to repair or replace. provide a updated maintenace log.

    Jan 26, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Device is out of service. provide to return to service.

    Jan 26, 2024 · Penalty $625

    Resolve
  • Class - 1

    Return to service

    Jan 26, 2024 · Penalty $1,250

    Resolve
  • Class - 1

    Class 1 c/u door zone restrictor bypassed. provide to repair.

    Jan 26, 2024 · Penalty $1,250

    Resolve
  • Class - 1

    Class 1: upon inspection found device to be out of service. restore to service repair immaediately as per 1rcny 11-02.

    May 8, 2023

    Resolve
  • Class - 1

    Class 1: upon inspection found device to be out of service. restore to service repair immaediately as per 1rcny 11-02.

    May 8, 2023

    Resolve
  • Class - 1

    Failure to provide adequate safety measures such as shed,netting etc.where required to protect public and property from documented unsafe facade.facade technical report filed unsafe by qewi(pe/ra)on 02/13/2023

    Mar 2, 2023 · Penalty $10,000

    Resolve
  • Class - 2

    Failure to submit acceptable req cycle8b report of critical exam doc condition of exterior wall&appurtenances req by 28-302.4 for control800128.agg1:prior nov 37021682j under 28-302.4 submit acceptable req tech

    Oct 19, 2022 · Penalty $3,125

    Resolve
  • Class - 1

    97,x,10 restore to service class 1. replace resisters and call dob for proper inspection.

    Aug 10, 2022 · Penalty $625

    Resolve
  • Class - 1

    5/x/10 car cease use class 1 car door restrictor is not working plunger stuck in up direction repair

    May 23, 2022 · Penalty $1,250

    Resolve
  • Class - 1

    97/x/17 class 1 restore to service for proper inspection by dob.

    May 11, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to submit acceptable required cycle 8b report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control #800128.remedy:submit acceptable required

    Jun 1, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to comply w/the comm's order contained in summons/vio#35475597z issued on 10/08/20 & to file a cert of correction pursuant to 28-201.1 & 1rcny 102-01. failure to maintain bldg in code compliant manner.

    Dec 15, 2020 · Penalty $1,250

    Resolve
  • Class - 1

    Faiure to maintain at roof level accumulated of unsecurred construction debris from water tower sitting on roof.rem:repair,replace,remove debris.

    Oct 8, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to file an acceptable cycle 7 technical report in compliance with code provisions: periodic inspection of exterior walls & appurtenances as required by article 28-302 & the dept of bldgs rules & regulat

    Jul 1, 2014 · Penalty $400

    Resolve
  • Class - 2

    41b10-properly secure secondary machine room door.

    Aug 12, 2013

    Resolve
  • Class - 1

    Designated site safety manager. note: at the time of my inspection on construction site,log book indicates that the designated site safety manager on the pw2 has not been on the site for the past 2 weels need

    Jun 11, 2013 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to comply rules promulgated by the commissioner - site safety rules. note: at the time of my inspection on construction site work inprogress on the facade at exp #2. site safety log book indicates that

    Jun 11, 2013 · Penalty $2,500

    Resolve
  • Class - 2

    Partial swo (north and west elevation) issued pursuant to 28-207.2 andposted at premises. no roof protection installed as per approved drawings. at time of inspection suspended scaffold installed at roof level

    Oct 15, 2012 · Penalty $250

    Resolve
  • Class - 2

    70o02,39o02,39q03,17h11,39m07,68m07. 17h11-where as needed. 39m07-antispin device.

    Oct 13, 2009 · Penalty $250

    Resolve
  • Non-hazardous

    02l10/10h11/17h11/83e10 02-emergency phone in car inoperative 10-car door gibs worn, replace 17-hoistway door gibs worn replace 83 car rubbing fascia between 1st and 2nd floors.

    Dec 20, 2004

    Resolve
  • Non-hazardous

    41r09. 41-r-09- remove green jumper from controlled.

    Nov 13, 2003

    Resolve
  • Non-hazardous

    73b,provide means to properly dismantle side walk elevator and secure to street opening.

    Dec 4, 1998

    Resolve
  • Non-hazardous

    31l 57o 31 repair defective top of car light switch

    Nov 18, 1998 · Penalty $350

    Resolve
  • Non-hazardous

    31l 57o 57d 56m repair defective car light switch on top of car 57 prperly secure pit ladder of pit floor 56 provide pit stop switch at access

    Nov 18, 1998 · Penalty $350

    Resolve
  • Non-hazardous

    Failure to file a report of compliance with local law 16/84 certifying to the installation o frequired fire protection systems.

    Nov 12, 1996

    Resolve
  • Non-hazardous

    Work without permit construction of interior partitions,soff its and hvac system installation was in various stages of completion under application # 101099749. at the time of inspection no permits had been iss

    Feb 15, 1996

    Resolve
  • Non-hazardous

    Work without permit- rough plumbing for supply and waste lines were installed on the 1st and 2nd floor of the above address wothout a permit issued from this dept. application # 101099749, for this work was app

    Feb 15, 1996

    Resolve
  • Non-hazardous

    Failure to provide approved plans at premises at time of inspection. this is contrary to code in that a set of plans stamped by the dept of buildings must be kept on site at all times for the alterations being

    Feb 15, 1996

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Aug 19, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Aug 18, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Aug 18, 2026 · Apt BLDG

    Close
  • Unsanitary condition

    Garbage/recycling storage

    Jul 15, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 4, 2026 · Apt 802

    Close
  • Heat/hot water

    Entire building

    Dec 12, 2025 · Apt 707

    Close
  • Heat/hot water

    Entire building

    Jun 6, 2025 · Apt 1102

    Close
  • Heat/hot water

    Entire building

    Jan 6, 2024 · Apt 916

    Close
  • Unsanitary condition

    Pests

    Dec 1, 2022 · Apt RADISS

    Close
  • Heat/hot water

    Entire building

    Mar 13, 2022 · Apt BLDG

    Close
Show 9 more ↓
  • Heat/hot water

    Entire building

    Feb 9, 2022 · Apt 1011

    Close
  • Heat/hot water

    Entire building

    Feb 7, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Apartment only

    Jan 28, 2022 · Apt 610

    Close
  • Heat/hot water

    Entire building

    Jan 24, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 7, 2022 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Sep 28, 2021 · Apt 816

    Close
  • Unsanitary condition

    Pests

    May 12, 2019 · Apt 515

    Close
  • Heat/hot water

    Entire building

    Mar 14, 2017 · Apt 816

    Close
  • Appliance

    Sprinker cert

    Jul 26, 2004

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Hotel (H3)
Year built
1902
Floors
20
Residential units
—
Building area
119,467 ft²
Lot area
6,497 ft²
Zoning
C5-5
Community board
101
Council district
1
Block / lot
40 / 16
Assessed value
$13,932,000
Landmark / historic district
No

HPD registration #141907, last renewed Jan 13, 2026.

Questions about 52 William Street

Who owns 52 William Street?

The owner of record in NYC Department of City Planning PLUTO data is 52 William Street Propco LLC.

Does 52 William Street have violations?

Yes. NYC HPD has recorded 12 housing violations at this property.

Is 52 William Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 52 William Street built?

City records list 1902 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.